It's a voyager unit. Voyager coils don't splotches. Spray with coil cleaner and use a pressure washer. Should have cleaned coil first before dumping in almost 7 pounds of r22 to see actual pressures since head pressures were so high to begin with. The motor was running hot because you over tightened it. You should have about a half inch play in the belt. Always verify belt drive motor amps after adjusting tension to make sure its not over Amping. Not trying to sound like jerk just giving you some pointers.
@TaddyDigest Жыл бұрын
Good tip!
@walterpena2430 Жыл бұрын
I agree,you need to use a power washer
@Pacman2403 Жыл бұрын
glad i wasnt the onl1 thinkin he over tightend
@extremeair1199 Жыл бұрын
Yes 100% always make sure good airflow and clean coil before adding refer.
@Nylphinx Жыл бұрын
You don't know how much you've help me out with the information from this video, thanks Tad
@TaddyDigest Жыл бұрын
Glad to help Thank you so much Watching my friend
@ares3914 Жыл бұрын
Take this as constructive citizism. First before adjusting belts. Look at motor data and see the run amps. Then amp the motor with doors closed. Then adjust belts then check amos again. On a hot day you shouldnt exceed the amp rating but you should close to it. Then before charging the unit, do leak check with a sniffer or bubbles. If leak is found then you ask what they wanna do. Dont assume they want topped off. Then you need to remove the refrigerant and see what the weight is and check data plate what the proper lbs and oz are before you add. Add what you took out then add to what data plate says. What i see here in this video is a rush. No need to rush no need to put your clients or home owners in a place where they have to pay you without knowing and then a week or a month later they have the same issue. At that point they wont trust and and have to pay double. If your honest with them then gain clients or home owners for life. Build the habit in things right the first time
@daleborg9070 Жыл бұрын
A leak was my concern as well. Pretty good leak if it took that much refrigerant. Find the leak first. Then decide what to after that. Repair, replace?
@taiptran15 күн бұрын
thank you and HAPPY NEW YEAR
@AaronMeyer-t7o Жыл бұрын
Had the same problem on the same type of unit and just poured nu Brite (the blue stuff) on top of the coils and it pushed the dirt and stuff out then hosed it off worked great
@evilspacech1cken13 күн бұрын
Along with all the other advice, if your head pressure is still abnormally high after cleaning the condenser coil and your suction pressure is low, it’s time to check out the metering device. Does not sound like low charge if one side is high and one side is low. it could potentially be low but it’s best to always check the txv, piston, eev, etc before adding refrigerant.
@Anonymous-bk3qx26 күн бұрын
How did you think high superheat was airflow? I don’t get it
@eulaliorodriguez53258 ай бұрын
I learned a lot for a being HAVC. LIKE MYSELF. Thank for this video.
@TaddyDigest8 ай бұрын
You're welcome my brother. I'm so glad that you like the video
@ErickHernandez93 Жыл бұрын
Power wash works for those just dont hit coil diretly and use less abbrasive fittings, I do bit commercial units 6 times the size of those so trust me pressure washers works without damaging the coils, pressures looked okay before gassing a unit man, should have just tried to clean the coils first, I always says it isn’t clean unless i clean it and make sure it’s out the way specially if it’s a customer I don’t do maintenance for, gets u out of the roof faster than breaking your head going back and forth, stay cool brother
@Lonny-hm3td Жыл бұрын
Man from residential to commercial is a different beat. One day maybe you can make a video about how to wire up the electrical components because in commercial I see 3 or 4 Contactors and a relay
@Lonny-hm3td Жыл бұрын
I hope you can***** pardon me lol
@prestonwillie5422 Жыл бұрын
Thanks you so much, I learned a lot from the video, and I want to be your student, from Liberia'.
@TaddyDigest Жыл бұрын
Excellent you're welcome Thank you so much for watching. Please share the video when you can
@emmroot59172 жыл бұрын
Ran into a similar situation and what we did was spray from one side with the hose and the other side we used a shop vac with the attachment at the end that has the small brushes so we're not damage the coil. Blowing the hose with one end while simultaneously sucking on the other hand with the Shop-Vac will fix you up good next time. I have the same gauges by the way. Nice content
@TaddyDigest2 жыл бұрын
That's a great idea very cool How do you like the gages?
@emmroot59172 жыл бұрын
@@TaddyDigest gauges are great. Especially the Eli Tech I got him for 150 bucks on sale.. Super solid and accurate manifold.
@spacemanwithraygun39336 ай бұрын
I have a customer with two of these that have dumped three charges just this year. I have mentioned that it may need a new coil or unit. They seem to be ok with fixing the leak and refilling with r22 each time. The compressor area panel I always put a screw through the top of panel while the panel is leaning after having them fall a hundred times.
@kevinlawson81242 жыл бұрын
Really enjoy videos, I’m technician in Louisiana
@TaddyDigest2 жыл бұрын
Awesome Kevin thank you so much for watching
@DaveTheHVACguy7 ай бұрын
I just bought the same electronic gauges...It was nice to see you have same-sorry to see the door fell forward on them-glad to know there built tuff!. One set was on 410a but I figured you would catch that later I learned about double coils...interesting! I was kinda surprised when you gassed both units before cleaning and didn't use a gas sniffer to find a leak, but maybe your customer is used to that. Did you use R22? Ever tried a drop in-less expensive! I'm thankful you got the unit running but it's not over...you got job security for sure.
@MegaIsok2 жыл бұрын
I’m an apprentice commercial HAVAC tech. Sometimes we run across condenser coils that have three coils like this. From what I’ve seen there not much you can do about it. We use coil guns that mix the solution inline with the water hose and that helps. We have used some heavy duty coil cleaner and that works well if you rinse well after. Also Viper has a no-rinse cleaner in a can that foams up like shaving cream. Works much better than the old green can of evap cleaner.
@TaddyDigest2 жыл бұрын
Wow Very Cool Thank You for this info John
@SouthFloridaSound2 жыл бұрын
Not trying to give you a hard time, but.... Where do you think the missing gas went? Other then cleaning the condenser that was a gas and go. I would think at R22 prices the customer would have been happy to find the OBVIOUS leaks(s).
@TaddyDigest2 жыл бұрын
I really appreciate you saying something actually I agree I told the customer it's probably time to upgrade and I got them a price Now I wonder what they'll do Thank you for watching Have a blessed day brother
@scal760 Жыл бұрын
Is this the same with my residential package unit (electrical) mine is stuck on heat and everything else works fine
@thecleanfreaks7 ай бұрын
Thank you for your video it was awesome, my top heating carrier three-phase unit has a bad fuse by the main power which I have replaced still has no power going in the main unit other words still not powering on can you help?
@TaddyDigest7 ай бұрын
If there's no power coming to the unit, if you check the disconnect and the breaker and they are good, you may need to call the power company
@xraybravo71803 ай бұрын
How do you like that gauge? Set? I believe it's a cheaper one. There's a lot of advertisement that comes across my face book
@jstacitizen7 ай бұрын
Does the blower wheel need replacing if not cooling enough in the office? The motor was changed last year.
@TaddyDigest7 ай бұрын
blower wheel only needs replacement when broken
@steelcrusher2 ай бұрын
I learned how to adjust the fan belt properly! I would take off that outer nut and then loosen the other nut and manually slide over the pulley! SMH
@cristianjavier14852 жыл бұрын
Your digital gauges are set for 410A 😅
@70acrefirearms276 ай бұрын
@@cristianjavier1485 I came to say the same thing.
@Dicktoben5 ай бұрын
Me three
@edgar201099 ай бұрын
Thanks for teaching
@TaddyDigest9 ай бұрын
It's my pleasure
@joejoeesqueda11 ай бұрын
freakin awesome!!!
@jimgarcia51657 ай бұрын
Maybe it’s freezing out because you have the evaporator door open the airflow is not going through the evaporator coil so it will freeze up if the doors open
@joshuapratt42145 ай бұрын
Im finna be a new graduate which would be the best residental or commerical?
@TaddyDigest3 ай бұрын
residential
@drodriguez3945 ай бұрын
i see a few issues here. high superheat is not an indication of low airflow. in addition to that, that 42 superheat is wrong too because you were mapped to 410a so your calculated superheat was off of the wrong saturation temperature. you don't add refrigerant to " bring up your pressure so it doesn't freeze" we add based on superheat and subcooling im sure you're a good guy and decent tech. but this video could be revised.
@TaddyDigest3 ай бұрын
thanks
@aljanepuso4 ай бұрын
how much of your digital gauge
@TaddyDigest3 ай бұрын
not sure
@lonnieroberts35907 ай бұрын
Would you not want to check for leaks
@jessec.92958 ай бұрын
That insullation is going to get sucked up by the blower
@jacquesdaoud42638 ай бұрын
I learn how to flip a fan LOL
@rocker86926 ай бұрын
Commercial looks funner than residential.
@kennysinclair11515 ай бұрын
It is, I made the switch like a year ago
@burtminshew48128 ай бұрын
Old school terrible advice is splitting coils to clean. Many manufacturers will tell you to stop that nonsense. When i spray both sides i never have an issue. Splitting coils has just been bad advice thats lasted the years. My experience is 37 years and teach. Its like that newer nad advice of checking your capacitors under load calculation.... Love your videos.
@TaddyDigest8 ай бұрын
Thank you for your knowledge brother
@MrDBWeatherMan2 жыл бұрын
You digital manifold was set to r410a but you said the unit was r22.
@TaddyDigest2 жыл бұрын
I know I caught it later on in the video
@MrDBWeatherMan2 жыл бұрын
@@TaddyDigest ah I’m still watching guess I jumped the gun on the comment lol
@MrDBWeatherMan2 жыл бұрын
@@TaddyDigest did you go back and do a leak detection or clean charge and go?
@TaddyDigest2 жыл бұрын
lol 😆 Thank you for watching my friend
@TaddyDigest2 жыл бұрын
1st time was a charge and go then Came back found the leak gave the customer the price on replacing the coil They went with a new unit
@lorenzobrown38474 ай бұрын
Why didn’t you just reclaim and see how much refrigerant is in unit then add nitro and look for the leak then weigh in the correct charge refrigerant doesn’t just leak out on its own
@TaddyDigest4 ай бұрын
Great idea.Thank you for your knowledge.Thank you for sharing to help others
@johneichhorn81722 жыл бұрын
Did you find the leak?
@TaddyDigest2 жыл бұрын
yes indoor coil
@joshmejia891Ай бұрын
i joined
@SuperSincere15 ай бұрын
You probably should have checked the coils before dumping expensive ass R-22 refrigerant in the unit.......
@robertmeyer4170 Жыл бұрын
I joined
@TaddyDigest Жыл бұрын
kzbin.info/door/uMyjTVlkM4xZ5z_eSyoB1wjoin
@christopherlapierre78782 жыл бұрын
42 degrees sh. on gauge was wrong .. your digital manifold gauge was set for 410a . oops r22 system. easy mistake,....
@TaddyDigest2 жыл бұрын
Hey Christopher I was wondering how many people would notice I actually noticed by the end of the video I just got these gages last week I'm doing some testing I gotta remember to do that Thank you for watching my friend
@robertmeyer4170 Жыл бұрын
Yes, I noticed it was on r410 but like a great tech you recognized it and changed it.
@arbalestdeathcore29629 ай бұрын
THIS IS PRETTY METAL.
@joequixotic30392 жыл бұрын
I learned that AC units are not all that complex. A friend of mine did a school/apprenticeship for HVAC but quit because they kept giving him the dirty jobs where he had to go in dirty crawl spaces and stuff. I don't blame him because another friend of mine died from a respiratory infection he got doing HVAC in a crawl space... After seeing this and a few other videos, I'm more confident that I can install and commission (is that the word) the mini-split AC I want and I don't have to go with Mr. Cool DIY. I can get gauges, a vacuum pump, trim my lines and evacuate them by myself. I'm building as much of the rest of the house as I can so it's good to know I'm not going to have to pay a tech to install it or maintain it.
@TaddyDigest2 жыл бұрын
Awesome Joe I love to hear This You go do it yourself. Save the money and maybe the Time and YOU are investing in YOU. Great Idea and Mindset
@influenz14902 жыл бұрын
Wait till you mess something up you'll be calling someone alright 😂
@TaddyDigest2 жыл бұрын
lol 😆 🤣
@joequixotic30392 жыл бұрын
@@influenz1490 I'm a metal fabricator gone amateur and "plumber". The only thing that worries me about AC is the wiring but it doesn't seem like it's networked, just analog signals which are easy to diagnose. Anything that doesn't require an IT professional to troubleshoot is ok with me. Eventually I'll try to tackle home networking but I'm prepared for that to be a work in progress for a long time.
@Kiddfamous2 жыл бұрын
Pressure washer 🤣
@Jeckhart0210 ай бұрын
High head pressure....let's add refrigerant 😂 silly