Tech Talk - What Is A Ghost Voltage And How To Test It

  Рет қаралды 5,128

Erik's Electronics Workbench

Erik's Electronics Workbench

2 ай бұрын

Tech Talk at Erik's Electronics Workbench. What is a ghost or phantom voltage and how do you test it? How can you tell if it is a ghost voltage or not? Follow along as Erik explains the details.
#learnelectronics #electronics #techtalk

Пікірлер: 21
@johnfitzpatrick2469
@johnfitzpatrick2469 2 ай бұрын
Greatly appreciate your lesson. Australia supplies 240v L N G * I will seek a meter with Z * Will check for ghost V 💫🇦🇺
@robharley9838
@robharley9838 2 ай бұрын
Very interesting subject Eric, thanks for exploring it! I've never encountered the concept. None of my DMMs have a low Z setting, but it is fun food for thought as to how one might measure the ghost other ways. Appreciate your work! - jrh
@timharig
@timharig 2 ай бұрын
In order to remove the "ghost" voltage, there must be a load impedance significantly lower than the output impedance of the "ghost" voltage. That lower impedance can but does not have to be provided by the meter itself. You can simply add an appropriately sized resistor in parallel to the meter to provide enough load to pull down the "ghost" voltage.
@robharley9838
@robharley9838 2 ай бұрын
@@timharig Thanks for the insight timharig! Impedance is still a little bit mysterious for me in some situations, but discussions like this help with my understanding. Appreciate it.-jrh
@timharig
@timharig 2 ай бұрын
@@robharley9838 Don't let the word scare you. For the purposes of this video, since there is only one frequency involved and we are not dealing with reactive components, you can treat impedance just like resistance. Ohms law for impedance is the same as for resistance: V= IZ Serial impedances are additive: Zt = Z1 + Z2 + Z3 + ... Parallel impedances follow the same rule as parallel resistances: Zt = 1/(1/Z1 + 1/Z2 + 1/Z3 + ...) The voltage dropped in series impedances drop in proportion to their impedances: V1 = V*Z1/(Z1+Z2) V2 = V*Z2/(Z1+Z2) etc. If you have a 120V ghost voltage with an output impedance of 2Meg ohm and you connect a meter with a 10Meg ohm input impedance, then the voltage that the meter measures will be the drop across its 10Meg ohm input: V = 120*(10Meg/(10Meg + 2Meg)) = 100V If however, measure the same 120V@2Meg Ohm ghost voltage with a meter that only has a 100k Ohm input impedance, then most of the voltage is dropped across the ghost voltage's impedance and the meter will only measure: V = 120(100k/(100k + 2Meg)) = 5.7V If you have a 10Meg ohm meter and you want to reduce its apparent input impedance, you could take the 100k ohm resistor and connect it in parallel with the meter. Then the meter's apparent impedance is: Zm + Zr = 1/(1/100k + 1/10Meg) = 99k ohm If you wanted to further remove the ghost voltage, then you could use an even lower value resistor. Assuming a 1k ohm resistor: Zm + Zr = 1/(1/1k + 1/10Meg) = 1k V = 120(1k/(1k + 2Meg)) = 60mV Note however, that if the voltage being measured is NOT a ghost voltage and the output impedance of the REAL voltage was say 0.1 ohm, then the current flowing through such a small resistor could be significant: V = 120(1k/(1k+0.1)) = 120V I = 120/1k = 120mA That is enough to make a small resistor warm and enough to interfere with the operation of lower power circuits -- which is why volt meters usually try to have as high of an input impedance as possible. Also note that if we ARE dealing with reactive components (inductors [coils] and capacitors) then the equations above still work; but, we have to treat impedance as a complex vector and we need to be concerned with how the impedance of reactive components changes with frequency.
@robharley9838
@robharley9838 2 ай бұрын
@@timharig Many thanks for the lesson! OHMs law rules. I'll be pondering this for sure. -jrh
@sharg0
@sharg0 2 ай бұрын
Now to check if any of my (cheap) multimeters have a low impedance setting, I doubt it.
@migsvensurfing6310
@migsvensurfing6310 2 ай бұрын
Just add a resistor across the terminals of the meter.
@davidfalconer8913
@davidfalconer8913 2 ай бұрын
Some older small LED lamps exhibit a ( ghost ) glow when turned off ... this is due to the leakage capacitance of the switch drop wires ... many folk find this annoying ... but ... these amazing lamps give an ( almost free ? ) NIGHT LIGHT ! ! ... ( handy to avoid tripping over the cat at night ? ? ) ..... ( tried - n - tested ) .......... DAVE™🛑
@EriksElectronicsWorkbench
@EriksElectronicsWorkbench 2 ай бұрын
Yes LED's require very little current to operate (compared to an incandescent bulb) and with necessary current limiting resistors they are fairly high impedance loads.
@Janktzoni
@Janktzoni 2 ай бұрын
Free: unfortunately not, while it is very little energy it is measured by the utilities meter.
@davidfalconer8913
@davidfalconer8913 2 ай бұрын
@@Janktzoni I did say : ALMOST free .... this tiny glow would probably cost about ( ? UK , £1 ) for the whole year , which is VERY affordable ( Ha - Ha ! ) ........ DAVE™🛑
@Janktzoni
@Janktzoni 2 ай бұрын
Thanks for this refresh, very clear and well explained! The use of metal boxes and conduits in domestic situations is making me somewhat nervous. The reason is that so many things can go wrong with these and the 'user' cannot safely or visually detect it is wrong or not without measurement equipment and the knowledge on how to use it. I believe the lower metal box itself on the isolation transformer should be earthed too. After all it is a metal box and the internal wiring can come loose and put the box on a dangerous potential. _Only the box_ and NOT the socket, as you correctly point out. (KZbin police mode on) Constructive criticism: Although you correctly explain that on the analog meter the red scale is applicable for AC, you're actually pointing to the black DC scale multiple times. The AC scale is not completely linear, the first 10% is shorter than on the DC scale. Admitted, this doesn't make a significant difference in this context and I would probably have made the same 'mistake'. (KZbin police mode off ;-)
@EriksElectronicsWorkbench
@EriksElectronicsWorkbench 2 ай бұрын
The metal box with the isolation transformer outlets should not be earth grounded. The reason is, suppose a wire comes loose and contacts inside the metal box. And suppose the box were grounded. Now one side of the isolation transformer has a ground reference and a shock hazard exists from the opposite secondary winding end to ground which completely defeats what the isolation transformer was supposed to protect against. With the box not grounded, suppose a wire comes loose and contacts inside the box. A shock would only occur if you touch the metal outlet box and at the same time the opposite secondary winding end which is very unlikely to occur (but of course not impossible). Regular testing of the whole isolation system for such faults is needed and if you prefer a plastic outlet box can be used. I will try to be more clear when pointing to the meter scales as to which tic marks I'm using but I did mention the AC voltage is taken on the red scale.
@timharig
@timharig 2 ай бұрын
The entire POINT of an isolation transformer is to isolate the connection from ground for safety. That way you cannot get shocked by grounding yourself out accidentally. The only way you get shocked is by bridging the two legs of the transformer. If one of the wires from the isolation transformer contacts the metal box, it's fine because the only path back to the transformer is through the other leg of the transformer. However, if you connect ground to metal box and one of transformer legs also touches the metal box, then ground becomes a path back to the transformer and you can once again electrocute yourself by accidently grounding yourself.
@izzzzzz6
@izzzzzz6 2 ай бұрын
something i don't understand with isolation transformers. The voltage is still the same so must still be dangerous but you are also isolating from the RCD protection circuit so how does that male it safer? I guess if you touch both live and neutral on the other side of an isolation transformer you are more likely to just burn yourself rather than have the current flow through you (possibly essential organs) to ground but if you touched one of eack terminal in one of each hands then you would be at a greater risk.
@EriksElectronicsWorkbench
@EriksElectronicsWorkbench 2 ай бұрын
Yes the secondary of the isolation transformer is just as dangerous as the normal AC line voltage. If you contact between both ends of the transformer's secondary you will be shocked. The protection or isolation the transformer offers is that there is no longer a ground reference which reduces the shock hazard. In other words, if you contact ONE SIDE of the transformer's secondary (and assuming the transformer and wiring is set up correctly) there is no path the current can take through your body to ground.
@Happymacer_P
@Happymacer_P 2 ай бұрын
Yes, but the second important benefit of an isolation transformer is that on mains powered test gear, the probe return wire is usually connected to ground. By making your test gear float you can protect both your test gear and yourself by preventing a live-earth short during testing.
@paulstaf
@paulstaf 2 ай бұрын
My Fluke 87V has a LoZ setting, however it read 120 volts through my isolation transformer to ground. When I used my Fluke 117 that also has a LoZ setting, the reading was close to zero, congruent to your video. I connected a light bulb through my isolation transformer to ground and it did not light. Any idea why the Fluke 87V did not read correctly?
@paulstaf
@paulstaf 2 ай бұрын
Nevermind, my 87V does NOT have LoZ setting, it has an Lo setting for "Low Pass" filter. My 117 has an LoZ setting.
@EriksElectronicsWorkbench
@EriksElectronicsWorkbench 2 ай бұрын
The Fluke 87V doesn't have a Lo impedance setting. The LO feature in yellow marking by the AC volts range is actually a low pass filter useful when measuring noisy devices like variable frequency drives for motors. The standard way to show the two functions is that the low pass filter is shown by the marking LO with the flat and sloping line over the letters, the Lo impedance feature is shown by the marking LoZ.
Weston Instruments 432 Wattmeter Teardown And Repair
32:10
Erik's Electronics Workbench
Рет қаралды 731
Ghost Voltages - Interesting and Confounding!
14:14
Taking Measure
Рет қаралды 3,8 М.
WHAT’S THAT?
00:27
Natan por Aí
Рет қаралды 13 МЛН
Heartwarming Unity at School Event #shorts
00:19
Fabiosa Stories
Рет қаралды 20 МЛН
Опасность фирменной зарядки Apple
00:57
SuperCrastan
Рет қаралды 6 МЛН
Amazing weight loss transformation !! 😱😱
00:24
Tibo InShape
Рет қаралды 56 МЛН
INTUAURA SplendorII
11:51
Jaytiss
Рет қаралды 29
Every Component of a Switch Mode Power Supply Explained
23:10
ElectrArc240
Рет қаралды 186 М.
Simpson 260 VOM Troubleshoot And Repair - Part 2
19:29
Erik's Electronics Workbench
Рет қаралды 1 М.
What is Ghost Voltage?
19:45
HVAC School
Рет қаралды 30 М.
Multimeters -  The Complete Guide
59:01
DroneBot Workshop
Рет қаралды 32 М.
How 3 Phase Transformers Work - why we need them
24:24
The Engineering Mindset
Рет қаралды 474 М.
Building an Adjustable High Voltage Supply
15:04
Advanced Tinkering
Рет қаралды 64 М.
Fiber Optic Splicing: Tips and Tricks for Beginners | ØY16
25:28
Cory Mac - ØY Electrical
Рет қаралды 101 М.
Ghost voltage, is it real?
9:27
Curious HVAC Guy
Рет қаралды 9 М.
Why So Many Capacitors? Understanding Their Differences and Uses!
25:20
Electronic Wizard
Рет қаралды 19 М.
Cheapest gaming phone? 🤭 #miniphone #smartphone #iphone #fy
0:19
Pockify™
Рет қаралды 4,3 МЛН
Как бесплатно замутить iphone 15 pro max
0:59
ЖЕЛЕЗНЫЙ КОРОЛЬ
Рет қаралды 5 МЛН
Это - iPhone 16 и вот что надо знать...
17:20
Overtake lab
Рет қаралды 128 М.
Телефон-електрошокер
0:43
RICARDO 2.0
Рет қаралды 1,3 МЛН
BEKMOBILDA Tecno Camon 30 smartfoni🔥🤩 #bekmobil
1:01
Bekmobil shorts
Рет қаралды 2,3 МЛН
Looks very comfortable. #leddisplay #ledscreen #ledwall #eagerled
0:19
LED Screen Factory-EagerLED
Рет қаралды 2,3 МЛН
Look, this is the 97th generation of the phone?
0:13
Edcers
Рет қаралды 6 МЛН