Pretty good watch here folks.. I'd love to see you go a little deeper into these infinity systems. I have a problem child that keeps showing up on my dispatch list lol
@hvacwithdrewman983 жыл бұрын
What’s the problem you’re having with that system
@fuzzyvision12193 жыл бұрын
@@hvacwithdrewman98 it won't stay in hi stage, it keeps coming up with a different reason to stay in low. First it said the hi pressure switch was open, This last time it said the high stage contactor was stuck but it doesn't even have one, I changed the board and model plug and reinstalled the system. It was running in hi when I left We shall see if it stays. The back story I got was that a company was out there to replace a leaking evaporator. Then soon after this all started and the next guy took his original t stat and gave him a different one but was supposed to bring it back and never did yadayadayada lol
@hvacwithdrewman983 жыл бұрын
@@fuzzyvision1219 sounds like the model plug is the problem. I haven't seen that issue yet... LOL.. I'm curious now so let me know if that took care of it
@fuzzyvision12193 жыл бұрын
He called again, its not faulting now it says it's running hi stage but the indoor temp in the evening says otherwise smh
@hvacwithdrewman983 жыл бұрын
@@fuzzyvision1219 that makes no sense.. you would think if anything it would be in the middle of the day that it wouldn’t keep up if there was a problem
@fastlife8662 жыл бұрын
I don't work on these much but the ecm fam motor wasn't coming on, I was testing the red and blue thinking it was 24v ac, then checked dc and was getting 0.5 so im going to replace board. Compressor kicks on and i have high voltage to the other 2 wires going to fan ecm.
@jasonnolasco56648 ай бұрын
Can the carrier condenser operate without the A&B communication? I had the furnace replaced with a different brand and they installed a new t-stat without communication. Now there’s no reading at the condenser on A&B
@hvacwithdrewman988 ай бұрын
Yes it can.. next to the ABCD plug there is a set of terminals to wire it up for no communication..
@yetom5035 ай бұрын
Carrier 2 stage ac problem
@marcotorres50804 жыл бұрын
I have one with a highstage lock out the compressor never runs but amps at 56 amps for like 4 seconds then cuts off it doesn't have a relay like the one in this video do you believe its the compressor
@bkluntz4 жыл бұрын
So when I get the code for a low contactor shorted, it means grounded compressor?
@hvacwithdrewman984 жыл бұрын
It will usually lead to the compressor... Look on the board, you will see I believe L1 and L2. If that gets power without a call for cooling it will that shorted contactor... One side of the contactor always has power going through it, if the windings short, it'll get picked up at the board