I bought 2 Anern 8.2kW inverters, they cannot charge more than 56.4v from the network. The user of settings does not obey. Why?
@ottopasztor4614 Жыл бұрын
If you set the AGM battery (factory default) in menu 05, it does not allow you to change the charging current in menu 26: 56.4V. Can only be changed if FLd (flooded) or USE (self-defined) is set.
@samodelkin2 Жыл бұрын
@@ottopasztor4614 in menu 5 I set the use mode, set menu 26 to 58.6v, the inverter does not want to charge more than 56.4v from the network. Only when the sun is connected then charges further.
@ottopasztor4614 Жыл бұрын
@@samodelkin2 How many volts does it charge when in solar mode?
@samodelkin2 Жыл бұрын
@@ottopasztor4614 when the solar panels are connected, the inverter charges up to 58.6 volts, it charges clearly from the solar panels as I set it. From the network does not want to only charge more than 56.4v. I have 4 such inverters and everything is the same from the network, they do not charge above 56.4v.
@ottopasztor4614 Жыл бұрын
@@samodelkin2 Interesting! I will see how the inverter charges the battery. (AGM)