Tanvir Bhai K liye Dil Se dua Allah Apko Aur Kamyab kare Bahot helpful hain apke videos
@TanweerAhmed Жыл бұрын
JazakaAllah
@mdshadman7596 Жыл бұрын
Amazing explanation in very easy way…. Thanks a lot
@TanweerAhmed Жыл бұрын
JazakaAllah
@shahidansari9139 Жыл бұрын
Very informative video. Pls continue as a series for cleanroom having different classes.
@TanweerAhmed Жыл бұрын
Thank you
@mohammedriyaz223 Жыл бұрын
Amazing topic sir ,,,,,
@TanweerAhmed Жыл бұрын
Thank you
@muhammadfarazkhansu0096 Жыл бұрын
Really appreciate your help ❤️
@TanweerAhmed Жыл бұрын
My pleasure 😊, Jazaka'Allah
@thepurposeofmyexistence2511 Жыл бұрын
Nice video sir , but can we have video on sizing of expansion tank and chemical dosing unit , for chilled water system , i mean can y explain in one layout chilled water syatem such that where we will connect make water line , where we connect Expansion tank line , chemical doing line , air seperator line in chilled water system , and explain how to we start doing commissioning of this system from where we 1st inject water to the system , and do we do hydrostatic test , on what pressure ,, I will be glad sir if y explian it
@thepurposeofmyexistence2511 Жыл бұрын
Also dear sir , asper nfpa 92 for smoke management system , when is the criteria to install smoke extraction system in the building , I mean is there any specific ht of building or area that building should have this system.
@TanweerAhmed Жыл бұрын
Ok noted
@TanweerAhmed Жыл бұрын
I will work on these topics, time by time
@thepurposeofmyexistence2511 Жыл бұрын
@@TanweerAhmed thank y sir , جزاك اللة خير
@saiyedali8329 Жыл бұрын
Assalamualaikum sir ji CooldStorage ki details video se hame jankari dijiye please
@TanweerAhmed Жыл бұрын
W.salam, ok noted
@Sohail_SKS Жыл бұрын
Superb sir Ji
@TanweerAhmed Жыл бұрын
Jazaka'Allah
@jamsheerali7229 Жыл бұрын
Thanks for this video, if this toilet is part of commercial or industrial building, how much cfm supply cooling need to provide?
@TanweerAhmed Жыл бұрын
Welcome
@jamsheerali7229 Жыл бұрын
Sir .. please need ur answer? Can v give supply air to toilet as per ashrae
@faridkhan-mf5xg Жыл бұрын
❤Mashallah sir thank you
@TanweerAhmed Жыл бұрын
JazakaAllah
@faridkhan-mf5xg Жыл бұрын
@@TanweerAhmed sir ap se request ki plumbing standard pe ik detail vedio banwo
@SaifAli-is9hb Жыл бұрын
Ser ji ye ventilation ki duct design kitne velocity or kitne friction loss per karege aur grill and exhaust diffuser ko design krne k liye kitni velocity per lete h
@TanweerAhmed Жыл бұрын
Watch my duct designing videos
@nizamuddinz439211 ай бұрын
Thanks for sharing information, there is a porto cabin trailer of size 12 mtr x 4mtr. In this 6wc and 12 shower, 7 lavatory. Wc and shower are separate and each has cubical partition, partition wall not touch with ceiling. In this case should i need to calculate 70cfm per wc and open area by 1cfm/ft. How about shower area exhaust per fixture or cfm/ft? Also this space is air conditioned by mini split unit.
@TanweerAhmed11 ай бұрын
Review the ASHRAE standard's table for all different locations
@nizamuddinz4392 Жыл бұрын
could you pls make video on, how to select the duct gauges /THICKNESS FOR - SAD, RAD, FAD, EAD? ON WHAT BASIS WE NEED TO SELECT,
@TanweerAhmed Жыл бұрын
Insha'Allah
@pakistanimanitehadinsaaf.4478 Жыл бұрын
Good Job …
@TanweerAhmed Жыл бұрын
Thank you
@nawabkamran5541 Жыл бұрын
Sir plumbing mein invert level calculation bylaye please
@TanweerAhmed Жыл бұрын
Invert is lower level of pipe or manhole
@mdshahidhussain569811 ай бұрын
Very helpful ❤
@TanweerAhmed11 ай бұрын
JazakaAllah
@taqirkan7712 Жыл бұрын
Assalam O Allikum Tanveer Bhai...how can we calculate cfm for janitorial area/changing rooms associated with the washrooms? Thanks
@TanweerAhmed Жыл бұрын
W.Salam, As per ASHREA 62.1 Janitor closets, trash rooms, recycling is Exhaust Rate 1 cfm/ft2 and further review standard
@engr.aamirhanif961 Жыл бұрын
Thanks for your videos. It’s really helping me brother. I would like to ask “where can i get ASHAREA standards book for these ventilation systems”?
@TanweerAhmed Жыл бұрын
Share email or join my Telegram group "HVAC|MEP Engineering"
@nizamuddinz4392 Жыл бұрын
MAKE VIDEO ON COLD STORAGE DESIGN - FREEZER, CHILLER
@TanweerAhmed Жыл бұрын
I have no experience about it
@nizamuddinz439211 ай бұрын
How to calculate heat load in washing area (WC, Shower, Lavatory)
@TanweerAhmed11 ай бұрын
Do you want to air conditioning in Toilet?
@nizamuddinz439211 ай бұрын
Yes, it's US Army Project.
@TanweerAhmed11 ай бұрын
Heat load calculation is same process as you calculate in other areas
@akkivlogs3321 Жыл бұрын
Basement sump calculation
@TanweerAhmed Жыл бұрын
Ok noted
@sarowarkabir974 Жыл бұрын
Make kitchen room ventilation design
@TanweerAhmed Жыл бұрын
Ok noted
@vijaybajaj401 Жыл бұрын
Tanveer I always prefer to give fresh air Nd exhaust fans in top end offices yes ACH m taking 12 for exhaust and keeping toilet always under negetive pressure our NBC is very very clear about this
@TanweerAhmed Жыл бұрын
🆗 👍
@nizamuddinz439211 ай бұрын
Thanks for sharing information, there is a porto cabin trailer of size 12 mtr x 4mtr. In this 6wc and 12 shower, 7 lavatory. Wc and shower are separate and each has cubical partition, partition wall not touch with ceiling. In this case should i need to calculate 70cfm per wc and open area by 1cfm/ft. How about shower area exhaust per fixture or cfm/ft? Also this space is air conditioned by mini split unit.
@TanweerAhmed11 ай бұрын
Check the table in ASHRAE standard for further details