Voltage Drop Problem | Long Distance Cable | Voltage Drop Calculation | Cable Size Selection Formula

  Рет қаралды 23,109

Shishiram Engineering Services

Shishiram Engineering Services

Күн бұрын

Voltage Drop Problem | Long Distance Cable | Voltage Drop Calculation | Cable Size Selection Formula
Please like and follow
Facebook Link : / shishiram-engineering-...
Instagram Link :
/ shishirameng
For more details visit our website
shishirameng.com/
Our blog
shishirameng.c...
How to Select Cable for House Wiring | How to Calculate Wire Size | Wire Full Details Malayalam 100%
• How to Select Cable fo...
In this video, I have explained in malayalam What will be the effect of long cables ?
When the length of the cable increases, cable resistance also increases with length. So Load due to this resistance also increases, this load will create a voltage drop in the line. I.e. a percentage of voltage is lost in the line itself and if the cable is too long then the equipment connected will be having a voltage issue.
what is the maximum length of the cable recommended for using as per manufacturer's manual rated current ?
We use standard cable size as per the manufacturer manual maximum up to 75 meters only. If the length is more than 75 meters then the voltage drop in the line is to be considered and Permissible voltage drop in the cable should be below 3% of the rated voltage. If the Voltage drop is more than 3% of the rated voltage the next higher size cable needs to be used.
How Does Using the Next Higher Size Cable Helps When There Is More Voltage Drop?
When we use the next higher size cable, the cross-section area of conductor increases and resistivity decreases with the cross-section area. So load across the cable decreases with that and voltage drop decreases.
Voltage Drop Calculation
Voltage drop VD= ( Milli Volt X Ampere load X Length of cable)/1000
Percentage Voltage Drop for Single Phase = (VD X100)/240
Percentage Voltage Drop for 3 Phase = (VD X100)/415
Maximum percentage voltage drop should be below 3 %
Cable selection: 5 KW single phase pump 150 meter alway from Power supply.
For Single Phase P= VI X Pf
For 1KW or 1000 Watt , Current I = 1000 / ( 240X 0.85 ) = 5 A (Approx.)
So for 5 KW, current I = 25 A (Approx.)
As per chart for 25 A, single we need 4mm AYFY cable and
voltage drop / A / m =18.2 mV
Voltage Drop = (milli volt X Ampere X Length)/1000
= (18.2 X 25 X 150)/1000)= 68.25 V
For single phase Percentage Drop = (VD X100)/240
= (68.25 X 100)/240 =28.43 %
I.e. Volatge at load end = 240-68.25 = 171.75 V
Higher cable size of 35 mm AYFY cable and
voltage drop / A / m = 2.1 mV
Voltage Drop = (milli volt X Ampere X Length)/1000
= (2.1 X 25 X 150)/1000)= 7.875V
For single phase Percentage Drop = (VD X100)/240
= (7.875 X 100)/240 =3.28 %
I.e. Volatge at load end = 240-7.815 = 232.125 V
Higher cable size of 50 mm AYFY cable and voltage drop / A / m = 1.6 mV
Voltage Drop = (milli volt X Ampere X Length)/1000
= (16 X 25 X 150)/1000)= 6 V
For single phase Percentage Drop = (VD X100)/240
= (6X 100)/240 = 2.5 %
I.e. Volatge at load end = 240-6 = 234 V
#electricaltutorial #housewiring #electricalclass # bestelectricalkerala #electricalmalayalam
Some of Our other Videos-
5 Reasons For High Voltage Problem In House | Double Voltage Due to Neutral Problems | Voltage Issue
• 5 Reasons For High Vol...
Why 1.5 V to 3 V Voltage Between Neutral & Earth | Electrical Neutral | Neutral Leakage Problems
• Why 1.5 V to 3 V Volta...
3 Phase Main Switch Connection Malayalam | 3 Phase Main Switch | KWh Meter 3 Phase | 3 Phase Wiring
• 3 Phase Main Switch Co...
HRC Fuse | High Breaking Capacity Fuse | High Rupture Capacity Fuse | HRC Fuse Working In Malayalam
• HRC Fuse | High Breaki...
Switch Disconnector Fuse | SDF | Difference Between SFU and SDF | L&T SDF | 3 Phase SDF Malayalam
• Switch Disconnector Fu...
Fuse & Main Switch Connection Malayalam | KSEB Energy Meter Connection | Safe Fuse Replacement |Fuse
• Fuse & Main Switch Con...
Query to solved in this video
voltage drop calculation in malayalam
voltage drop calculation
voltage drop calculation in long distance cable
voltage drop across cables
voltage drop calculation single phase
how to calculate voltage drop in cable
voltage drop physics malayalam
voltage drop over distance
For more details visit our website
shishirameng.com/
Amrut Shishir M
Electrical Consultant, Chartered Engineer
Kannur, Kerala
email us: info@shishirameng.com
Contact us: +91 8606472279
#voltagedropcalculation #howtosizeelectricalcables #cablesizingcalculation #voltagedropforfeedercircuitcalculation #howtocalculatesizeofcable #cablesizecalculationinmalayalam #cablesizecalculation #shishiramengineeringservices #amrutshishir #electricalengineeringservices #electricalconsultantkannur #electricalconsultantkerala #electricalmalayalam #electricalkerala

Пікірлер: 87
@dreamelectricals3020
@dreamelectricals3020 2 жыл бұрын
വളരെ ഉപകാരപ്രദം ........ എന്റെ വലിയ ഒരു പ്രശ്നം നിസാരവൽക്കരിച്ചതിന്
@shishiram
@shishiram 2 жыл бұрын
thank you...
@anilkumargl3797
@anilkumargl3797 3 жыл бұрын
താങ്കളുടെ വീഡിയോസ് എല്ലാം സൂപ്പർ ആണ്, വിദഗ്ധനായ ഒരു പ്രൊഫസറുടെ ക്ലാസ്സ്‌ പോലെ, 👍👍👍
@jaseemjaseemm1582
@jaseemjaseemm1582 7 ай бұрын
It is very very informative for designers 👏👏👏thankyou so much,keep going ,we are expecting more videos like this from you 🤝🤝🤝
@shishiram
@shishiram 7 ай бұрын
check our online course for such videos shishirameng.com/courses/
@noushadch9624
@noushadch9624 4 жыл бұрын
ഡിസി വയറിങ്ങിനെ കുറിച്ചും അതിലെ വോൾടേജ് ഡ്രോപിനെ കുറിച്ചും ഒരു ടെക്നിക്കൽ വീഡിയോ ചെയ്യാമോ?
@mustafamohsin6439
@mustafamohsin6439 3 жыл бұрын
Thank you sir. After watching your tutorials, I benefited
@faziludeenm7071
@faziludeenm7071 4 жыл бұрын
very useful and good class
@kamalakshiammaap
@kamalakshiammaap 4 ай бұрын
Can u please tell me the correct length extended cord for a black and decker grass cutter 350 watt machine and it's built-in cord having 16A 240 v 2p
@pradipanp
@pradipanp 4 жыл бұрын
വളരെ ഉപകാരപ്രദമായ വീഡിയോ, ഇതുസംബന്ധിച്ചു ഇന്നലെ fB home design ഗ്രൂപ്പിൽ ഒരു പോസ്റ്റ് കണ്ടിരുന്നു. വന്യ മൃഗങ്ങളെ തുരത്തുവാൻ വേണ്ടിയുള്ള ഇലക്ട്രിക്കൽ ഫിൻ ലൈനിന്റെ പ്രവർത്തന രീതി വിശദീകരിച്ചുകൊണ്ടുള്ള വീഡിയോ ചെയ്യാമോ
@shishiram
@shishiram 4 жыл бұрын
Ok...i will explain in a video Stay subscribed with bell button pressed to all... If you liked the video, like and share to friends and family...
@pradipanp
@pradipanp 4 жыл бұрын
@@shishiram sure
@afsalpn9353
@afsalpn9353 4 жыл бұрын
Thanks voltage drop എന്ന് കേട്ടിട്ടുണ്ട് എന്ന് അല്ലാതെ ഇത് ഇത്ര പ്രശ്‌നം ഉണ്ടാകും എന്ന് ഇന്നാണ് അറിയുന്നത് thanks thank you very much
@shishiram
@shishiram 4 жыл бұрын
Welcome... Stay subscribed with bell button pressed.. If you find our video interesting , please like and share this video to friends and family...
@chabdulnazer5130
@chabdulnazer5130 8 ай бұрын
Sir veettil ninnum 160mtr distace und kinar njan eath cable use cheyyanam
@vysakhvenugopal4817
@vysakhvenugopal4817 4 жыл бұрын
Please make video on UPS efficiency and minimum load to be provided for cost effective & what happen if we load after 80% of ups any instant impact.
@mirshadvk6924
@mirshadvk6924 4 жыл бұрын
Oru rumile le circuitil nunn loop cheyd ade roomile heaterilum, ac kum, ellengil kurarach power supplyilek loop cheydu. Ennal total power nokiyal mcb yul ulkollanavym engil voltage problem undavumo
@kannanr6454
@kannanr6454 4 жыл бұрын
Very helpful class sir thank u
@sunilraj2914
@sunilraj2914 9 ай бұрын
1.5 hp motor 150meter undu Ethu type wire use cheyyam
@mazinalhabsi7802
@mazinalhabsi7802 4 жыл бұрын
Useful 👍
@diyaazaghloul756
@diyaazaghloul756 4 жыл бұрын
Amazing video thank you
@rajappanvv1849
@rajappanvv1849 2 жыл бұрын
High voltage distribution : used because to reduce power loss ; when voltage. increased the Ampre reduce as per Jules law
@blessyvarghese2376
@blessyvarghese2376 4 жыл бұрын
Well said sir..... By using highvoltage we can reduce the cable size without voltage drop,so it is more ecconomical
@shishiram
@shishiram 4 жыл бұрын
good... ... Stay subscribe with bell button pressed. If you liked the video, Like and share to family and friends..
@shahulmj7487
@shahulmj7487 2 жыл бұрын
Energy meter to first floor vare oru bulb Kathikumbol voltage drop engane kanakakam
@shishiram
@shishiram 2 жыл бұрын
No need to calculate voltage drop if distance is less than 75meters
@shahulmj7487
@shahulmj7487 2 жыл бұрын
Thanks your valuable advais
@shahulmj7487
@shahulmj7487 2 жыл бұрын
Floating nuetral oru vidio cheyyamo sir
@abdusameerpullichola1394
@abdusameerpullichola1394 2 жыл бұрын
2 runs,3 runs cable selection yenkanea anu bro? Eg: 3 Run 3c x300 mm2 cable for Long distance how to select?
@babythomas2902
@babythomas2902 10 ай бұрын
120 അടി ദൂരത്തിൽ 1HP മോട്ടോർ സ്ഥാപിച്ചു. ഇതിലേക്ക് അലുമിനിയം Cable അതായത് Single Phase Weather proof Cable കൊടുത്തിരിക്കുന്നു. ഇവിടെ കൂടുതൽ drop ഉണ്ടാകുമോ?
@jyothishkumarkumar8809
@jyothishkumarkumar8809 4 жыл бұрын
Thanks
@shishiram
@shishiram 4 жыл бұрын
Welcome... Stay subscribe with bell button pressed. If you liked the video, Like and share to family and friends..
@ചെരാതുകൾ
@ചെരാതുകൾ 3 жыл бұрын
Sir ,earth wire size enganey calculate cheyyam
@mailstomails10
@mailstomails10 2 жыл бұрын
When the motor is in ON condition, if you measure the voltage at the source end and compare it with the motor terminal end, will there be any difference?
@shafikp6766
@shafikp6766 4 жыл бұрын
Surge Protection Device (SPD) oru video cheyyumo pls
@shishiram
@shishiram 4 жыл бұрын
Sure... Im planning one... Stay subscribed with bell button pressed to all... If you liked the video, like and share to friends and family...
@premprasad5857
@premprasad5857 3 жыл бұрын
Thanks sir 🙏
@ajithkprabhakar1
@ajithkprabhakar1 4 жыл бұрын
We can use 3 phase supply and cable of 16 square mm to reduce the cost
@adharshga9806
@adharshga9806 3 жыл бұрын
Long distance transmissionil distance koodumbo cable resistance koodum.. So I^2 R loss koodunnu. So step up transformer vech high voltage il transmit cheyyunnu
@shishiram
@shishiram 3 жыл бұрын
This actually we are using in industry... for submersible to pump oil from oil rig... watch this video... more more information.... kzbin.info/www/bejne/qXyaioFurad-rck
@faziludeenm7071
@faziludeenm7071 4 жыл бұрын
detailed information about mega tester
@jaisonkuriakose5683
@jaisonkuriakose5683 2 жыл бұрын
Normally Single phase mechines current കൂടുതൽ withdraw ചെയ്യും അതുകൊണ്ട് വോൾട്ടേജ് കുറയാൻ സാധ്യത ഉണ്ട്....
@samasafiyasafiya9973
@samasafiyasafiya9973 4 жыл бұрын
Good
@shishiram
@shishiram 4 жыл бұрын
Thanks... Stay subscribe and support...
@Ramzan-Vettoor
@Ramzan-Vettoor 4 жыл бұрын
2000 Wന്റെ ചാർജർ 16AM ഇലക്ട്രിക്ക് ആട്ടോയുടെ ചാർജർ കണക്ട്‌ ചെയ്യാൻ എത്ര MM ന്റെ വയർ ഉപയോഗിക്കണം
@MUHAMMAD-cz2fr
@MUHAMMAD-cz2fr 4 жыл бұрын
Induced voltage (intension) angane pariharikkam?
@shishiram
@shishiram 4 жыл бұрын
I will make a video on it...later on... Stay subscribed with bell button pressed.. If you find our video interesting , please like and share this video to friends and family...
@jihasvk8932
@jihasvk8932 4 жыл бұрын
Delta connection explain cheyamo, Delta connection circuit engane complete aavunnu?
@shishiram
@shishiram 4 жыл бұрын
Ok...i will explain in a video Stay subscribed with bell button pressed to all... If you liked the video, like and share to friends and family...
@renjithravi6065
@renjithravi6065 4 жыл бұрын
Super
@shishiram
@shishiram 4 жыл бұрын
Thanks...... Stay subscribe with bell button pressed. If you liked the video, Like and share to family and friends..
@asharafapk2073
@asharafapk2073 4 жыл бұрын
സർ വയറിന്റെ length calculate ചെയ്യുന്നതിൽ confusion വരുന്നുണ്ട് സാറി ന്റെ vedio യിൽ single phasil v drop calculate ചെയ്യുമ്പോൾ 150 meter അകലെ യുള്ള ലോഡിൽ phasum nuetralum lay ചെയ്യുന്നു so total distance 150*2=300meter അല്ലെ ഫോര്മുലയിൽ ചെയ്യേണ്ടത് Some Enginers ഇങ്ങനെ യാണ് ചെയ്യുന്നത് അത് you tubil തന്നെ കണ്ടിട്ടുണ്ട് അതുകൊണ്ടാണ് ചോദിക്കുന്നത് can u pls explain about it because being confused ur last vedio
@adharshga9806
@adharshga9806 3 жыл бұрын
Bro 2 core cable alle use cheyyane. 2 core aavumbol athil phase and neutral undallo. Pinne ath oru cable alle.. So 150m mathi..
@arunyeshodaran211
@arunyeshodaran211 3 жыл бұрын
What about 24Vdc case?
@afsalpn9353
@afsalpn9353 4 жыл бұрын
Sir എന്ത് കൊണ്ടാണ് ചെറിയ ലോഡ് ന് വലിയ കേബിൾ യൂസ് ചെയ്യാത്തത് ex നല്ല ഒരു cash ഉള്ള ആളാണ് ഹൗസിങ് owner എങ്കിലും ചെറിയ ലൈറ്റ് ലോഡ് (30w) പ്രവര്‍ത്തിക്കാന്‍ voltage drop വേണ്ട electric equipment nnum വയർ nnum നല്ല ലൈഫ് കിട്ടും എന്ന് കരുതി 4 mmsqm വയർ അല്ലെങ്കിൽ അതിൽ കൂടുതല്‍ കനം ഉള്ള wire ഉപയോഗിക്കുന്നില്ല cash ചെലവ് അല്ലാതെ technical error വല്ലതും ഉണ്ടോ pls reply me sir
@shishiram
@shishiram 4 жыл бұрын
No need to use big cables for small loads... just use as per standards... that is enough...
@sujinsreedharan4915
@sujinsreedharan4915 4 жыл бұрын
Why Voltage drop/A/m is in mV and not in Ohm/m ie. Resistance /m
@shishiram
@shishiram 4 жыл бұрын
This is easier method of calculation....for me at least ...as I'm using this...
@rasakakv6872
@rasakakv6872 Жыл бұрын
I, 5wire using 75 meater up than 3
@gopalakrishnanjayaprakash6414
@gopalakrishnanjayaprakash6414 4 жыл бұрын
വോൾട്ടേജ് കൂട്ടി ആന്പിയർ കുറച്ചു കഴിഞ്ഞാൽ റസിസറ്റൻസ് കുറയ്ക്കും.അങ്ങനെ വോൾട്ടേജ് ഡ്രോപ്പ് കുറയ്ക്കാം,കണ്ടക്ടറിൻെറ ഏരിയാ ഓഫ് ക്രോസെക്ഷൻ കുറയ്ക്കാം,അതുവഴി എക്കൊണൊമിക് ഫീസിബിലിറ്റി ഉണ്ടാകും.
@afiafeef8841
@afiafeef8841 4 жыл бұрын
Ys thats it
@shishiram
@shishiram 4 жыл бұрын
Good..for full details and calculation... Stay subscribe with bell button pressed. If you liked the video, Like and share to family and friends..
@mohammedroshan347
@mohammedroshan347 4 жыл бұрын
വലിയ മോട്ടറിന്റെ ഒക്കെ സ്റ്റാർട്ടിങ് Ampire എങ്ങനെയാണ് Calculate ചെയ്യാ??
@realdevbro447
@realdevbro447 3 жыл бұрын
3 times rated amp.
@binurajvijayan
@binurajvijayan 4 жыл бұрын
എന്റെ വീട്ടിൽ ഉള്ള എല്ലാ LED ലൈറ്റുകളും ഓൺ ആയിരിക്കുബോൾ ബ്ലിങ്ക് ചെയ്യുന്നു എന്തായിരിക്കും കാരണo (20watt,14watt,9watt,0.5watt) ഒരു മാസത്തോളമായിട്ട് ഇങ്ങനാ
@pradipanp
@pradipanp 4 жыл бұрын
OFF ആയിട്ടിരിക്കുമ്പോൾ ആണോ?
@kunhumuhammedkunhumuhammed1661
@kunhumuhammedkunhumuhammed1661 2 жыл бұрын
@@pradipanp ശരിക്ക് നോക്കി വായിക്കൂ
@rasakakv6872
@rasakakv6872 Жыл бұрын
❤❤❤❤❤❤
@MrShaneemibnshereef
@MrShaneemibnshereef 4 жыл бұрын
For a load of 300 watts. Single phase . The length is 1500 meter. Can you please advise the cable size suitable for this run. Pvc insulated cable.
@shishiram
@shishiram 4 жыл бұрын
Brother... take some effort... try to do calculation yourself... if you have any doubt in calculation ask me .... I will help for sure...
@MrShaneemibnshereef
@MrShaneemibnshereef 4 жыл бұрын
@@shishiram VD=(Milli volt x Amp load x Length of cable) /1000 P=300 Watts A=300/(240x0.9)=1.4A Consider the wire size is 6mmsq where its Milli volt per ampere is 7.4 VD=(7.4x1.4x1500)/1000 =15.54 VD%= (15.54/240)x100=6.475% which is greater than 3%. So considering next stage of cable which is 10mmsq where its Milli volt per ampere is 4.3 VD=( 4.3x1.4x1500)/1000 =9.03 VD%=(9.03/240)x100=3.7 % which is nearer to 3 %. But not equal to 3 % So we consider the. Ext stage of cablw which is 16 mmsq. Where its Milli volt per ampere is 2.7 VD=( 2.7x1.4x1500)/1000 =5.67 VD%= (5.67/240)x100=2.3 %which is less than permissible voltage drop 3 %. So we will choose 16mm sq cable for the long run of 1500..meter length and the power 300 Watts.
@MrShaneemibnshereef
@MrShaneemibnshereef 4 жыл бұрын
Is this calculation OK??
@shihabkattoorpetta8912
@shihabkattoorpetta8912 Жыл бұрын
1500 wats 200 meter awich cable alluminum 2core
@mubashirthottungal11
@mubashirthottungal11 2 жыл бұрын
വോൾടേജ് കുറവാണു ഫാൻ എല്ലാം സ്ലോ മെയിൻ ഓഫ്‌ ചെയ്ത് ഇൻവെർട്ടറില് നിന്ന് വർക്ക്‌ ചെയ്യുമ്പോൾ സ്പീഡ് ഉണ്ട് കാരണം എങ്ങനെ കണ്ട് പിടിക്കാം
@hari3658
@hari3658 2 жыл бұрын
main connection in voltage drop varunnath kond aanennu thonnunnu, pazhaya wiring aanenkil megger cheyth nokki cable insulation check cheyyunnath nannayrikkum
@gopalakrishnanc.p4415
@gopalakrishnanc.p4415 2 жыл бұрын
Voltage is increasing,samtime current decrease
@binutn5375
@binutn5375 4 жыл бұрын
100m lengthലുള്ള loadൽ2core cable ഉപയോഗിക്കുമ്പോൾ voltage drop 100m ആണോ200m ആണോ calculationനു വേണ്ടി ഉൾപ്പെടുത്തേണ്ടത്? Conductorന്റ നീളം 200mആണല്ലോ.
@shishiram
@shishiram 4 жыл бұрын
If your 2 core cable length is of 100 m then for calculation is for 100 m
@hafathk9773
@hafathk9773 4 жыл бұрын
Under water cable
@shishiram
@shishiram 4 жыл бұрын
OK... Flat cable used for submersible pump... For more details on cables watch this video... kzbin.info/www/bejne/eXikYn-dl5xkpNU Stay subscribed with bell button pressed.. If you find our video interesting , please like and share this video to friends and family...
@jamsheerchanath677
@jamsheerchanath677 4 жыл бұрын
ഡിസി വയറിങ് സിസ്റ്റം സ്‌പ്ലൈൻ
@usmanttml
@usmanttml 4 жыл бұрын
കാൽക്കുലേഷൻ മനസ്സിലാവുന്നില്ല
@shishiram
@shishiram 4 жыл бұрын
Sorry... please see once again....or check my facebook or insta page for all slides..
@sacred_hope
@sacred_hope Жыл бұрын
thanks
@mohamedsafwan6198
@mohamedsafwan6198 3 жыл бұрын
Thank you sir....
@sathyanhari4089
@sathyanhari4089 4 жыл бұрын
Super
@shishiram
@shishiram 4 жыл бұрын
Thanks ... Stay subscribe with bell button pressed. If you liked the video, Like and share to family and friends..
Everything you need to know to solve Voltage Drop Calculations!!
14:57
Craig Michaud- Electrical Instructor
Рет қаралды 246 М.
Арыстанның айқасы, Тәуіржанның шайқасы!
25:51
QosLike / ҚосЛайк / Косылайық
Рет қаралды 700 М.
“Don’t stop the chances.”
00:44
ISSEI / いっせい
Рет қаралды 62 МЛН
黑天使只对C罗有感觉#short #angel #clown
00:39
Super Beauty team
Рет қаралды 36 МЛН
How 3 Phase Power works: why 3 phases?
14:41
The Engineering Mindset
Рет қаралды 2,2 МЛН
Repairing Underground Power Cables Is Nearly Impossible
13:34
Practical Engineering
Рет қаралды 4,2 МЛН
120V 240V Electricity explained - Split phase 3 wire electrician
12:24
The Engineering Mindset
Рет қаралды 5 МЛН
Lighting Circuits Part 1
24:18
John Ward (jwflame)
Рет қаралды 1,5 МЛН
Ground Neutral and Hot wires explained - electrical engineering grounding ground fault
11:13
Cable sizing calculation|How to select cable size|Electrical Technology and Industrial Practice
22:27
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 167 М.
Low Voltage Switchgear : A Beginner’s Guide | TheElectricalGuy
13:56
Gaurav J - TheElectricalGuy
Рет қаралды 64 М.
Арыстанның айқасы, Тәуіржанның шайқасы!
25:51
QosLike / ҚосЛайк / Косылайық
Рет қаралды 700 М.