Hello sir, How to connect low voltage sensor to plc please reply the sensor output also low voltage.? What must be the voltage for connecting to plc x pins?
@ACCautomation4 жыл бұрын
Hi Thaskar, In order to connect low voltage sensors to the PLC, an interposing relay is usually used. This can be mechanical or solid-state. Low voltage is usually referred to less than 5 VDC. accautomation.ca/wiring-interposing-relays/ This post should help you out. Regards, Garry
@thaskarthaskaran14254 жыл бұрын
@@ACCautomation Thank you . How much min voltage required does 12 v enough
@thaskarthaskaran14254 жыл бұрын
Actually the thing is I want to connect the raspberry pi output which is 3v to plc . Can it be done by boosting the voltage.?
@ACCautomation4 жыл бұрын
@@thaskarthaskaran1425 You would have to look at the specifications of the input of the PLC that you are using. This would be listed as a minimum voltage level. Regards, Garry
@ACCautomation4 жыл бұрын
@@thaskarthaskaran1425 To interface with a PLC you would either get a relay output board for your raspberry pi or get an interposing relay. www.automationdirect.com/adc/shopping/catalog/relays_-z-_timers/solid_state_relays/socket_mount_relays,_4a_(ad-70s2_series)/ad-70s2-04b This link will show a solid-state relay that has an input of 3-30 VDC input. 8-12mA draw for the input. I hope this helps you out. Regards, Garry
@kinsleyjolicoeur65163 жыл бұрын
can i connect a vfd to this PLC to adjust the speed of a 3 phase motor please sir answer
@ACCautomation3 жыл бұрын
Hi Kinsley, Yes, you can connect to a variable frequency drive and control the speed. Usually, you will have local or remote modes on the VFD. The local mode can control the VFD through digital and analog signals on the PLC. Remote control would usually involve a communication protocol like Modbus TCP, Modbus RTU, Ethernet IP, etc. Here is a video showing Modbus RTU communication to control a 3 phase motor. kzbin.info/www/bejne/aYvTd6SCZpdjZqs Regards, Garry
@kinsleyjolicoeur65163 жыл бұрын
Man thanks you so so so must you just save me..
@kinsleyjolicoeur65163 жыл бұрын
how can i program proximity sensor to click plc than to a vfd of 20 hp please answer sir.The ladder language can you please help me sir
@ACCautomation3 жыл бұрын
Hi Kinsley Jolicoeur, You are missing a lot of information from your question. - How are you communicating with the VFD? - What VFD are you using: Model / Options? - What proximity sensor are you using? Make / Model - What is the sequence of operation of the proximity sensor in relation to the VFD? Here is a link to the five steps for program development. accautomation.ca/five-steps-to-plc-program-development/ It will help you in explaining what you are trying to achieve. Thanks, Garry
@kinsleyjolicoeur65163 жыл бұрын
@@ACCautomation Ok thanks..will back to you later.You're helping me a lot Sir..