@mortenlund14184 жыл бұрын
Very informative and easy understandable video. Thanks a lot. :)
@dasmi323 жыл бұрын
Or we can use 23-24 for K2. I think it's better option :)
@ryanjohnson36064 жыл бұрын
Hello AboutElectricity, I've got a question. I notice that you don't have the E-Stop button wired into any 24V in the video. Why is that? I'm assuming, that whenever channel 1 and 2 are happy and you hit your reset, it sees both channels are closed then and that allows the relay to latch? An answer would be awesome! Maybe I'm just confusing 24v e-stop daisy chained circuits to the pilz, which I'm not entirely sure what all the differences are yet. Also, what are the 13 and 14 terminals for? From my understanding it looks like it keeps power latched onto the coil for the contactor(s), for whenever the circuit isn't tripped.
@AboutElectricity4 жыл бұрын
1.yes.You only wire 24V to power the relay and e-stop button to the monitoring channels. During reset if booth are closed then the relay turn on the safety outputs 13-14.If for some reasons we will lose one channel the safety relay will de-energize safety outputs.
@ryanjohnson36064 жыл бұрын
@@AboutElectricity Thanks for such a quick response! I believe I understand it pretty clearly now. This helped a lot for troubleshooting ideas for work. Thank you!
@GettinChrixy Жыл бұрын
@ryanjohnson3606 The unit itself sends a 24 through the e-stop from S11 and S21 and monitors that it receives the signal on S12 and S22. When it loses the 24 signal (when you push the E-stop) it will then open the contacts for the circuit it is controlling. This is then reset when the e-stop is pulled out (can see the signal again) and when it gets a pulse signal from the reset (terminal S33 to S34) Hopefully I explained that clearly.
@oithetresen6094 жыл бұрын
Thanks. You helped me a lot.
@antoniogaleana7672 Жыл бұрын
Excelente explicación
@marijaismail83973 жыл бұрын
Best video for saftey relay
@numberjuan58374 жыл бұрын
This is great thanks!
@jeffjeff85622 жыл бұрын
Normally you wouldn't put the reset circuit through the n.c. contacts on the relays. You would just wire the n.o. reset button on the S33 to S34 terminals. The n.c. contacts on the relays are then free to use as feedback to the input card on the plc or simply an indicator light.
@radoslawczyzewski2 жыл бұрын
Depending on the performance level you want to achieve. Check ISO 13849 standard for details.
@MohammadArman-mv8wn3 жыл бұрын
Outstanding... thanks
@mohammadkaheel97316 күн бұрын
Merci
@gercekler2 жыл бұрын
Thanks for sharing master
@baudoinbenjamin89753 жыл бұрын
Hello Aboutelectricity Will it be the same if you wire channel by channel; like fro s11 through E-stop to S21 and from S12 through E-Stop to S22?
@AboutElectricity3 жыл бұрын
No. Terminals S11 - S12 is one channel and s12 - s21 is the second channel.
@powell27623 жыл бұрын
Hi, couldn't the reset bypass the contractors and just go 33 to reset then straight back into 34. Or is this done to make sure a short hasnt developed on the contacts themselves. Thanks
@jeffjeff85622 жыл бұрын
Normally you wouldn't put the reset circuit through the n.c. contacts on the relays. You would just wire the n.o. reset button on the S33 to S34 terminals. The n.c. contacts on the relays are then free to use as feedback to the input card on the plc or simply an indicator light.
@sabiriwayuser14 жыл бұрын
Good presentation 👍 make more videos related to safety relay like Allen Bradley gsr di safety relay 440r-d22r2
@juliocesardealmeida21673 жыл бұрын
I agree with you!
@manhhungbui37364 жыл бұрын
Thanks for your video. It's very helpful. But can you help me to explain how does the reset contact work? Thanks a lot.
@AboutElectricity4 жыл бұрын
Simple.Whenever you e-stop the machine to energize the safety relay back again you will need to press reset button.
@juliocesardealmeida21673 жыл бұрын
@@AboutElectricity great!
@mariabenabdelouhab14534 жыл бұрын
Thank you
@adeyanjusamson30864 жыл бұрын
How can i clear fault and reset alarm on PNOZ s4.1? When power, In1, In2, Out are not coming on
@AboutElectricity4 жыл бұрын
Check voltages on booth inputs.How to troubleshoot safety relay here kzbin.info/www/bejne/hmSomnaPapyAoKc
@nghia2224 жыл бұрын
If we dont use in S11 and S21, How about the needed signals for S12 and S22 (0V or 24V)?
@Sakaryali713 жыл бұрын
Thank you wonderfull
@CarlosGonzalez-et3ok3 жыл бұрын
amazing information! Tnks
@sajadsarami28913 жыл бұрын
Thanks.
@juliocesardealmeida21673 жыл бұрын
So good! Congrats!!!!!
@tzukaza_Gaming3 ай бұрын
Hello, I have a question. Can I use the pnoz without a contactor and just connect it to the Siemens Logo? If so, which contact would that be?
@yattaman714 жыл бұрын
Can i connect feedback circuit to two relays in series instead of contactors ? why would just not connect NO contact reset between s34 and s34?
@AboutElectricity4 жыл бұрын
1.I have seen many machines and they have always been fitted with contactors.It is because those contactors are switching main circuit where current is higher and might exceed rated load of the relay contacts. 2. If your application does not require feedback circuit then yes, you can wire only NO contact between s33 and s34 as manual start.
@yattaman714 жыл бұрын
@@AboutElectricity Thank you for quick reply. I am working on low voltage 24vdc circuit, outputs are pneumatic sv 24vdc dump valve 24vdc buzzer 24vdc ect., inputs are sensors that are 24vdc. I think in low voltage circuits i can use small 24vdc relays with safety relay 24vdc? correct me if i am wrong.. Another question is that in small machines based on PLC with maximum 8 inputs and outputs - push buttons, proxy sensors, solenoid valves, buzzers, dump valves all operating on 24vdc - i would need to implement safety circuit - means e-stop and safety relay, there is no guards that would require interlocks or light curtains.. all i need to drop air from the pneumatic system and trigger buzzer at the event of emergency machine stop (e-stop depressed) 1.) would be necessary to disable inputs 24vdc? 2.) would be necessary to disable outputs 24vdc? 3.) would be just connecting pneumatic dump valve and buzzer to safety relay with 24vdc relays in series? Regards, D.
@AboutElectricity4 жыл бұрын
@@yattaman71 I would still use contactors instead of relays.I would wire safety relay with emergency stop like here kzbin.info/www/bejne/iYrOioR5m7WJhqs When E-stop depressed two contactors will drop out disconnecting power supply to the valves.On top of that,use one set of contact and wire it to the plc and plc program should deenergize all outputs.But you have to chceck if it works.
@yattaman714 жыл бұрын
@@AboutElectricity Hi, Thanks for help on this matter. Would you be able to explain how to connect remote pneumatic dump valve 3/2 24vdc. to the safety relay ?
@adisharr4 жыл бұрын
The purpose of using aux contacts on contactors is to prevent a safety circuit reset in case of a contact weld in one of the contactors. You would also use a safety rated contactor that's built differently than a standard model.
@iletisimatakan3 жыл бұрын
Hello, can you tell me which program are you using?
@JBCFAUTOMATION4 жыл бұрын
Hi AboutElectricity Can you create Video about Wiring safety relay XPS-AC5121 of Schneider Electric
@Jarito19033 жыл бұрын
nice
@chemssoubourada14578 ай бұрын
thank u i like this kind of videos
@attilapataki9533 жыл бұрын
Hi Dear. I am wondering if you could help me with my project. I am rebuilding an old cnc milling machine with new components , but keeping old safety relay . It is an Omron.
@curryhouse13774 жыл бұрын
Weldone
@AboutElectricity4 жыл бұрын
Thanks.
@curryhouse13774 жыл бұрын
@@AboutElectricity You r a great man...Are you from India?
@AboutElectricity4 жыл бұрын
@@curryhouse1377 No mate. From UK.
@emersoncunha6184 Жыл бұрын
Só faltou numerar a contatores, não sei se usou contato aberto ou fechado.
@mohammadtayyab92764 жыл бұрын
Kon c aap me ye graphics bnaye hen???
@mridulsharma29704 жыл бұрын
Fritzing
@politics1024 жыл бұрын
Shouldn't one contactor come from 13,14 the other from 23,24. You have spent all this money an have a single contact failure in the pilz bringing it all down.
@radoslawczyzewski2 жыл бұрын
This is what led me to this video. Each single contact in safety relay is made in fact from two relays connected in series - is it sufficient to satisfy category 3/4 circuit?
@assemismail66614 жыл бұрын
How to connect this relay with electro-mechanical switch
@gagandeepsharma36133 жыл бұрын
Allen-Bradley SensaGuard 440N- Z21US2HN9 kase chek krte hai kharab hai ja shi hai
@mehdisafari-mg6wg4 жыл бұрын
I use pliz pnoz x3 After couples years when I want to reset it never reset need to switch of power and then reset
@AboutElectricity4 жыл бұрын
Well, you have to check feedback circuit. It looks to me that some of the normally closed contact is not really closed ( and it should be).Check how many NC contacts you have in the feedback circuit then take a multimeter and check the voltage before and after each contact.
@AboutElectricity4 жыл бұрын
I agree with you on "milion dollar business".Every electrical part that has word "safety" in it cost a fortune :)
@mehdisafari-mg6wg4 жыл бұрын
@@AboutElectricity I use it to check for emergency loop I am sure that all push button and NC keys are OK I use all inputs for emergency in different places(one machine) AND different machine(press machine,glaze line, wrap carton, ball mill with a 1 MW electromotor ,....... in tile company desined by SACMI) It has no problems at the beginning of use, but it does have problems over time and needs to be turned off once to reset
@1357938254 жыл бұрын
can you do FX5U-32ME/ES mitsubishi
@shaqeelquraishi24074 жыл бұрын
Singal phace control wiring par videos banao
@omurolmez0 Жыл бұрын
Please someone give me an explain or something to read about benefit of using automatic reset safety device over making same circuit without using a safety device.
@AboutElectricity Жыл бұрын
Nowadays, in every machine in the factory where safety is taken seriously, only safety relays are used.
@AboutElectricity Жыл бұрын
Type in google "machine safety categories explained".
@Joan-lw8zu4 жыл бұрын
Porque esran en serie k1 y k2??
@othaomay83012 жыл бұрын
Cốc cốc, xin A một góc, thanks Bán rẻ cho AE RELAY: OMRON H3Y-2 TIMER 24D RELAY: RXM 24VDC Scheneider Control speed: JSCC Model SF06E 6W/220V. Động cơ: JSCC:80YT25GV22 / 220VAC CONTACTOR: TENGEN-TGC1-3210-KOI 220V/AC CONTACTOR: CHiNT-NC1-32Z-Ui 690V - lth 50A Nguồn TỔ ONG: 24V/5A RELAY: IDC RJ25-CL-D24 Để lại cho AE nha.
@leonardochieng72207 ай бұрын
Can I get an explanation of how voltage regulator work
@suriyat87732 жыл бұрын
ราคาเท่าไหร่ ครับ สนใจซื้อ
@chrisperry67462 жыл бұрын
The safety relay will not give enough power to activate a contactor.
@AboutElectricity2 жыл бұрын
What makes you think so ?
@chrisperry67462 жыл бұрын
@@AboutElectricity I've wired these up before. You need a separate 24v supply. For the contacts.
@AboutElectricity2 жыл бұрын
@@chrisperry6746 I work with them every day. It has nothing to do with safety relay. It is up to your power supply. We use 5A or 10A power supply and they power whole machine ie. a couple of safety relays,valves and many, many relays and contactors.
@chrisperry67462 жыл бұрын
@@AboutElectricity Sorry I should of been more clearer. The current going through the two channels. Won't be enough to power a contact.
@AboutElectricity2 жыл бұрын
@@chrisperry6746 I still disagree with you. Pilz pnoz technical details says that safety contacts at 24VDc have got Imax = 6 A. Is your contactor coil taking more than 6A ?
@rehouma4 жыл бұрын
Attention le câblage est faux !!!! la bobine de K2 (A- A2) entre 24 et 0V. ne pas oublier de relier +24V à 23.