Wiring safety relay Pilz PNOZ and emergency stop button.

  Рет қаралды 212,030

AboutElectricity

AboutElectricity

Күн бұрын

Пікірлер: 81
@AboutElectricity
@AboutElectricity 2 жыл бұрын
Was this video useful? Want to download this file and suppport this channel ? Why not buy me coffee :) www.buymeacoffee.com/Aboutelctricity
@mortenlund1418
@mortenlund1418 4 жыл бұрын
Very informative and easy understandable video. Thanks a lot. :)
@dasmi32
@dasmi32 3 жыл бұрын
Or we can use 23-24 for K2. I think it's better option :)
@ryanjohnson3606
@ryanjohnson3606 4 жыл бұрын
Hello AboutElectricity, I've got a question. I notice that you don't have the E-Stop button wired into any 24V in the video. Why is that? I'm assuming, that whenever channel 1 and 2 are happy and you hit your reset, it sees both channels are closed then and that allows the relay to latch? An answer would be awesome! Maybe I'm just confusing 24v e-stop daisy chained circuits to the pilz, which I'm not entirely sure what all the differences are yet. Also, what are the 13 and 14 terminals for? From my understanding it looks like it keeps power latched onto the coil for the contactor(s), for whenever the circuit isn't tripped.
@AboutElectricity
@AboutElectricity 4 жыл бұрын
1.yes.You only wire 24V to power the relay and e-stop button to the monitoring channels. During reset if booth are closed then the relay turn on the safety outputs 13-14.If for some reasons we will lose one channel the safety relay will de-energize safety outputs.
@ryanjohnson3606
@ryanjohnson3606 4 жыл бұрын
@@AboutElectricity Thanks for such a quick response! I believe I understand it pretty clearly now. This helped a lot for troubleshooting ideas for work. Thank you!
@GettinChrixy
@GettinChrixy Жыл бұрын
@ryanjohnson3606 The unit itself sends a 24 through the e-stop from S11 and S21 and monitors that it receives the signal on S12 and S22. When it loses the 24 signal (when you push the E-stop) it will then open the contacts for the circuit it is controlling. This is then reset when the e-stop is pulled out (can see the signal again) and when it gets a pulse signal from the reset (terminal S33 to S34) Hopefully I explained that clearly.
@oithetresen609
@oithetresen609 4 жыл бұрын
Thanks. You helped me a lot.
@antoniogaleana7672
@antoniogaleana7672 Жыл бұрын
Excelente explicación
@marijaismail8397
@marijaismail8397 3 жыл бұрын
Best video for saftey relay
@numberjuan5837
@numberjuan5837 4 жыл бұрын
This is great thanks!
@jeffjeff8562
@jeffjeff8562 2 жыл бұрын
Normally you wouldn't put the reset circuit through the n.c. contacts on the relays. You would just wire the n.o. reset button on the S33 to S34 terminals. The n.c. contacts on the relays are then free to use as feedback to the input card on the plc or simply an indicator light.
@radoslawczyzewski
@radoslawczyzewski 2 жыл бұрын
Depending on the performance level you want to achieve. Check ISO 13849 standard for details.
@MohammadArman-mv8wn
@MohammadArman-mv8wn 3 жыл бұрын
Outstanding... thanks
@mohammadkaheel973
@mohammadkaheel973 16 күн бұрын
Merci
@gercekler
@gercekler 2 жыл бұрын
Thanks for sharing master
@baudoinbenjamin8975
@baudoinbenjamin8975 3 жыл бұрын
Hello Aboutelectricity Will it be the same if you wire channel by channel; like fro s11 through E-stop to S21 and from S12 through E-Stop to S22?
@AboutElectricity
@AboutElectricity 3 жыл бұрын
No. Terminals S11 - S12 is one channel and s12 - s21 is the second channel.
@powell2762
@powell2762 3 жыл бұрын
Hi, couldn't the reset bypass the contractors and just go 33 to reset then straight back into 34. Or is this done to make sure a short hasnt developed on the contacts themselves. Thanks
@jeffjeff8562
@jeffjeff8562 2 жыл бұрын
Normally you wouldn't put the reset circuit through the n.c. contacts on the relays. You would just wire the n.o. reset button on the S33 to S34 terminals. The n.c. contacts on the relays are then free to use as feedback to the input card on the plc or simply an indicator light.
@sabiriwayuser1
@sabiriwayuser1 4 жыл бұрын
Good presentation 👍 make more videos related to safety relay like Allen Bradley gsr di safety relay 440r-d22r2
@juliocesardealmeida2167
@juliocesardealmeida2167 3 жыл бұрын
I agree with you!
@manhhungbui3736
@manhhungbui3736 4 жыл бұрын
Thanks for your video. It's very helpful. But can you help me to explain how does the reset contact work? Thanks a lot.
@AboutElectricity
@AboutElectricity 4 жыл бұрын
Simple.Whenever you e-stop the machine to energize the safety relay back again you will need to press reset button.
@juliocesardealmeida2167
@juliocesardealmeida2167 3 жыл бұрын
@@AboutElectricity great!
@mariabenabdelouhab1453
@mariabenabdelouhab1453 4 жыл бұрын
Thank you
@adeyanjusamson3086
@adeyanjusamson3086 4 жыл бұрын
How can i clear fault and reset alarm on PNOZ s4.1? When power, In1, In2, Out are not coming on
@AboutElectricity
@AboutElectricity 4 жыл бұрын
Check voltages on booth inputs.How to troubleshoot safety relay here kzbin.info/www/bejne/hmSomnaPapyAoKc
@nghia222
@nghia222 4 жыл бұрын
If we dont use in S11 and S21, How about the needed signals for S12 and S22 (0V or 24V)?
@Sakaryali71
@Sakaryali71 3 жыл бұрын
Thank you wonderfull
@CarlosGonzalez-et3ok
@CarlosGonzalez-et3ok 3 жыл бұрын
amazing information! Tnks
@sajadsarami2891
@sajadsarami2891 3 жыл бұрын
Thanks.
@juliocesardealmeida2167
@juliocesardealmeida2167 3 жыл бұрын
So good! Congrats!!!!!
@tzukaza_Gaming
@tzukaza_Gaming 3 ай бұрын
Hello, I have a question. Can I use the pnoz without a contactor and just connect it to the Siemens Logo? If so, which contact would that be?
@yattaman71
@yattaman71 4 жыл бұрын
Can i connect feedback circuit to two relays in series instead of contactors ? why would just not connect NO contact reset between s34 and s34?
@AboutElectricity
@AboutElectricity 4 жыл бұрын
1.I have seen many machines and they have always been fitted with contactors.It is because those contactors are switching main circuit where current is higher and might exceed rated load of the relay contacts. 2. If your application does not require feedback circuit then yes, you can wire only NO contact between s33 and s34 as manual start.
@yattaman71
@yattaman71 4 жыл бұрын
@@AboutElectricity Thank you for quick reply. I am working on low voltage 24vdc circuit, outputs are pneumatic sv 24vdc dump valve 24vdc buzzer 24vdc ect., inputs are sensors that are 24vdc. I think in low voltage circuits i can use small 24vdc relays with safety relay 24vdc? correct me if i am wrong.. Another question is that in small machines based on PLC with maximum 8 inputs and outputs - push buttons, proxy sensors, solenoid valves, buzzers, dump valves all operating on 24vdc - i would need to implement safety circuit - means e-stop and safety relay, there is no guards that would require interlocks or light curtains.. all i need to drop air from the pneumatic system and trigger buzzer at the event of emergency machine stop (e-stop depressed) 1.) would be necessary to disable inputs 24vdc? 2.) would be necessary to disable outputs 24vdc? 3.) would be just connecting pneumatic dump valve and buzzer to safety relay with 24vdc relays in series? Regards, D.
@AboutElectricity
@AboutElectricity 4 жыл бұрын
@@yattaman71 I would still use contactors instead of relays.I would wire safety relay with emergency stop like here kzbin.info/www/bejne/iYrOioR5m7WJhqs When E-stop depressed two contactors will drop out disconnecting power supply to the valves.On top of that,use one set of contact and wire it to the plc and plc program should deenergize all outputs.But you have to chceck if it works.
@yattaman71
@yattaman71 4 жыл бұрын
@@AboutElectricity Hi, Thanks for help on this matter. Would you be able to explain how to connect remote pneumatic dump valve 3/2 24vdc. to the safety relay ?
@adisharr
@adisharr 4 жыл бұрын
The purpose of using aux contacts on contactors is to prevent a safety circuit reset in case of a contact weld in one of the contactors. You would also use a safety rated contactor that's built differently than a standard model.
@iletisimatakan
@iletisimatakan 3 жыл бұрын
Hello, can you tell me which program are you using?
@JBCFAUTOMATION
@JBCFAUTOMATION 4 жыл бұрын
Hi AboutElectricity Can you create Video about Wiring safety relay XPS-AC5121 of Schneider Electric
@Jarito1903
@Jarito1903 3 жыл бұрын
nice
@chemssoubourada1457
@chemssoubourada1457 8 ай бұрын
thank u i like this kind of videos
@attilapataki953
@attilapataki953 3 жыл бұрын
Hi Dear. I am wondering if you could help me with my project. I am rebuilding an old cnc milling machine with new components , but keeping old safety relay . It is an Omron.
@curryhouse1377
@curryhouse1377 4 жыл бұрын
Weldone
@AboutElectricity
@AboutElectricity 4 жыл бұрын
Thanks.
@curryhouse1377
@curryhouse1377 4 жыл бұрын
@@AboutElectricity You r a great man...Are you from India?
@AboutElectricity
@AboutElectricity 4 жыл бұрын
@@curryhouse1377 No mate. From UK.
@emersoncunha6184
@emersoncunha6184 Жыл бұрын
Só faltou numerar a contatores, não sei se usou contato aberto ou fechado.
@mohammadtayyab9276
@mohammadtayyab9276 4 жыл бұрын
Kon c aap me ye graphics bnaye hen???
@mridulsharma2970
@mridulsharma2970 4 жыл бұрын
Fritzing
@politics102
@politics102 4 жыл бұрын
Shouldn't one contactor come from 13,14 the other from 23,24. You have spent all this money an have a single contact failure in the pilz bringing it all down.
@radoslawczyzewski
@radoslawczyzewski 2 жыл бұрын
This is what led me to this video. Each single contact in safety relay is made in fact from two relays connected in series - is it sufficient to satisfy category 3/4 circuit?
@assemismail6661
@assemismail6661 4 жыл бұрын
How to connect this relay with electro-mechanical switch
@gagandeepsharma3613
@gagandeepsharma3613 3 жыл бұрын
Allen-Bradley SensaGuard 440N- Z21US2HN9 kase chek krte hai kharab hai ja shi hai
@mehdisafari-mg6wg
@mehdisafari-mg6wg 4 жыл бұрын
I use pliz pnoz x3 After couples years when I want to reset it never reset need to switch of power and then reset
@AboutElectricity
@AboutElectricity 4 жыл бұрын
Well, you have to check feedback circuit. It looks to me that some of the normally closed contact is not really closed ( and it should be).Check how many NC contacts you have in the feedback circuit then take a multimeter and check the voltage before and after each contact.
@AboutElectricity
@AboutElectricity 4 жыл бұрын
I agree with you on "milion dollar business".Every electrical part that has word "safety" in it cost a fortune :)
@mehdisafari-mg6wg
@mehdisafari-mg6wg 4 жыл бұрын
@@AboutElectricity I use it to check for emergency loop I am sure that all push button and NC keys are OK I use all inputs for emergency in different places(one machine) AND different machine(press machine,glaze line, wrap carton, ball mill with a 1 MW electromotor ,....... in tile company desined by SACMI) It has no problems at the beginning of use, but it does have problems over time and needs to be turned off once to reset
@135793825
@135793825 4 жыл бұрын
can you do FX5U-32ME/ES mitsubishi
@shaqeelquraishi2407
@shaqeelquraishi2407 4 жыл бұрын
Singal phace control wiring par videos banao
@omurolmez0
@omurolmez0 Жыл бұрын
Please someone give me an explain or something to read about benefit of using automatic reset safety device over making same circuit without using a safety device.
@AboutElectricity
@AboutElectricity Жыл бұрын
Nowadays, in every machine in the factory where safety is taken seriously, only safety relays are used.
@AboutElectricity
@AboutElectricity Жыл бұрын
Type in google "machine safety categories explained".
@Joan-lw8zu
@Joan-lw8zu 4 жыл бұрын
Porque esran en serie k1 y k2??
@othaomay8301
@othaomay8301 2 жыл бұрын
Cốc cốc, xin A một góc, thanks Bán rẻ cho AE RELAY: OMRON H3Y-2 TIMER 24D RELAY: RXM 24VDC Scheneider Control speed: JSCC Model SF06E 6W/220V. Động cơ: JSCC:80YT25GV22 / 220VAC CONTACTOR: TENGEN-TGC1-3210-KOI 220V/AC CONTACTOR: CHiNT-NC1-32Z-Ui 690V - lth 50A Nguồn TỔ ONG: 24V/5A RELAY: IDC RJ25-CL-D24 Để lại cho AE nha.
@leonardochieng7220
@leonardochieng7220 7 ай бұрын
Can I get an explanation of how voltage regulator work
@suriyat8773
@suriyat8773 2 жыл бұрын
ราคาเท่าไหร่ ครับ สนใจซื้อ
@chrisperry6746
@chrisperry6746 2 жыл бұрын
The safety relay will not give enough power to activate a contactor.
@AboutElectricity
@AboutElectricity 2 жыл бұрын
What makes you think so ?
@chrisperry6746
@chrisperry6746 2 жыл бұрын
@@AboutElectricity I've wired these up before. You need a separate 24v supply. For the contacts.
@AboutElectricity
@AboutElectricity 2 жыл бұрын
@@chrisperry6746 I work with them every day. It has nothing to do with safety relay. It is up to your power supply. We use 5A or 10A power supply and they power whole machine ie. a couple of safety relays,valves and many, many relays and contactors.
@chrisperry6746
@chrisperry6746 2 жыл бұрын
@@AboutElectricity Sorry I should of been more clearer. The current going through the two channels. Won't be enough to power a contact.
@AboutElectricity
@AboutElectricity 2 жыл бұрын
@@chrisperry6746 I still disagree with you. Pilz pnoz technical details says that safety contacts at 24VDc have got Imax = 6 A. Is your contactor coil taking more than 6A ?
@rehouma
@rehouma 4 жыл бұрын
Attention le câblage est faux !!!! la bobine de K2 (A- A2) entre 24 et 0V. ne pas oublier de relier +24V à 23.
@gagandeepsharma3613
@gagandeepsharma3613 3 жыл бұрын
Manual lin send kro
@fernandofernandez4810
@fernandofernandez4810 3 жыл бұрын
No se ve
@suriyat8773
@suriyat8773 2 жыл бұрын
Thank you
@yavuzaydin4111
@yavuzaydin4111 2 жыл бұрын
Thank you
How to wire the timer, relay and 14 pin relay base.
4:20
AboutElectricity
Рет қаралды 25 М.
What is Safety Relay PILZ ? Easy Explained | pnoz X2 X3 X4
5:59
PLC Programming Tutorials Tips and Tricks
Рет қаралды 138 М.
When Cucumbers Meet PVC Pipe The Results Are Wild! 🤭
00:44
Crafty Buddy
Рет қаралды 60 МЛН
How to Fight a Gross Man 😡
00:19
Alan Chikin Chow
Рет қаралды 18 МЛН
The Ultimate Sausage Prank! Watch Their Reactions 😂🌭 #Unexpected
00:17
La La Life Shorts
Рет қаралды 8 МЛН
Муж внезапно вернулся домой @Oscar_elteacher
00:43
История одного вокалиста
Рет қаралды 7 МЛН
How To Wire Pilz Safety Relay. Step by Step Guide For Beginners
9:33
AboutElectricity
Рет қаралды 19 М.
Schmersal Protect SRB-E: Multi functional safety relay modules
5:10
Schmersal UK & Ireland
Рет қаралды 44 М.
Troubleshooting safety relay Pilz PNOZ  with emergency button.
4:55
AboutElectricity
Рет қаралды 71 М.
CNC Electronics - E-STOP Mockup (Home shop CNC Build Log - Ep17)
12:16
How to wire  Sick UE48 safety relay.E-stop and light curtains.
6:31
AboutElectricity
Рет қаралды 60 М.
ИГРОВОЙ ПК от ИЛОНА МАСКА, Распаковка
32:50
😱Складных смартфонов больше не будет
0:46
ÉЖИ АКСЁНОВ
Рет қаралды 446 М.
Никогда так не делайте #сборка #пк #pcbuild
0:17
XDOT PC - Игровые ПК
Рет қаралды 1,7 МЛН
Introducing the "VitaWear SmartBand," a next-generation wearable gadget🎉
0:16
Vrashika Rajput Official
Рет қаралды 19 МЛН