Very good efforts and explain sir.... Understand very easy way...Thanks for your efforts
@swapnasumanpati65203 жыл бұрын
Great content sir. Thank you so much 👍🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏
@syedhassnainali29174 жыл бұрын
Thank you very much
@AjeetKumar-iq7fp2 жыл бұрын
Thank you sir share knowledge 🙏
@ManishSingh-og1kd4 жыл бұрын
Sir Please take care of your health right now. Be fully recovered and come back like a champion.
@inzmamhussain55634 жыл бұрын
Sir good to see you back.. I was waiting for your videos. Please provide 132 kv cb siemens drwaing in Pdf format.
@ranjansahu23624 жыл бұрын
So fabulous sir... Little confusion gas lock out condition...
@beingelectrical66414 жыл бұрын
K10 (density monitor multiplier) is meant for gas pressure supervision, which is guided/ controlled through B4 (gas density monitor). It allows/prohibits the breaker from operating as per the gas pressure status through its NO contact in closing & tripping circuit, and informs the user regarding gas pressure status through 2 no of alarms 1. Gas pressure low (1st stage)- NC of B4 2. Gas pressure lockout(2nd stage)- NC of K 10. K10 therefore is a dedicated supervision cum controlling component in respect of gas pressure status.
@ranjansahu23624 жыл бұрын
@@beingelectrical6641 yes sir got it ....
@AjeetKumar-iq7fp2 жыл бұрын
Thanks 😊 sir
@patakotisrinivas19183 жыл бұрын
Nice explanation..see that breaker drawing is visible clearly...it is not clearly visible...
@manishjanagal27554 жыл бұрын
Nice Explaination sir but if I am not wrong you forgot to mention lockout relay contacts in closing & tripping circuit.
@beingelectrical66414 жыл бұрын
That we have covered in the next video, detailed discussion of closing & tripping circuit.
@appliedelearning86513 жыл бұрын
Please make a video about relay Settings.
@ranjansahu23623 жыл бұрын
Sir one of our 33kv bay 195 and 295 relay C flag is drop... What might be the reason for this... We have checked tc 1 coil and tc2 coil it found healthy..
@sarojiniperumalla4 жыл бұрын
Sir can u please share the 132kv CHL Breaker drawing
@manasdey8272 Жыл бұрын
63GLX se Direct tripping kaise hote hai
@beingelectrical6641 Жыл бұрын
63GLX gas pressure normal ke case me pick up condition me rehta hai, which means ye ek supervision contactor ki tarah work karta hai.. agar iske through tripping dena hai to iske NC contact ka use Kiya jaa sakta hai.. but gas pressure low ke case me tripping karana safe option nahi hota
@rakeshghorpade49564 жыл бұрын
Sir please explan siemans spring chargeing control