14yr Old 5 Ton Ruud Iced Up || Customer Prefers To Repair If Possible … Let’s Check It Out..

  Рет қаралды 10,388

Subcool HVAC

Subcool HVAC

Күн бұрын

Пікірлер: 73
@welrod94
@welrod94 3 ай бұрын
I didnt watch the video just because I dont find it interesting when you have worked on and replaced god only knows how many units but I did wanna say unless they are stupid rich they are always gonna wanna repair over replacing the unit. I mean I'm the type of guy if my compressor blows up I wanna buy a new compressor than a entire unit😂 **even tho I didnt watch the comment will still help with the algorithm
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks for not watching but commenting 😎
@ccthepope
@ccthepope 3 ай бұрын
You are one of the very few HVAC guys that knows how to run a clean torch tip! Also sounds like the gas pressures are correct also, I am an aircraft mechanic that had to weld with Oxy-Ac,
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks CC, you learn to hear what the flame should sound like if you use it enough. Not much heat needed on this one 🔥👍
@alabamahvacprofessional2946
@alabamahvacprofessional2946 3 ай бұрын
Just watched the video, and want to say thanks for repairing the problem. I have 37 years of experience in the field, and most guys these days only want to replace the entire system.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks Alabama HVAC!
@forthefunofit3230
@forthefunofit3230 2 ай бұрын
500 as opposed to 5 grand!!!! of course we want REPAIR!
@stephenjenner484
@stephenjenner484 3 ай бұрын
Only a good tech can make a repair. Any hack can take good equipment and through it in the junk . Those Rheem,Rudd, Weather Kings were good equipment .
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
The previous company only wanted to replace 😎
@williamgildea8348
@williamgildea8348 2 ай бұрын
Too many white shirt companies never would have attempted to do this repair. There all about the up sale. Nice repair
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Agreed, Most customers would rather repair if it makes $ sense. Thanks for the comment 👍
@Ericbakereb1
@Ericbakereb1 3 ай бұрын
Some guys can really perform art with a mixed torch. Good job bud.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks Eric 🔥
@thesilentonevictor
@thesilentonevictor 3 ай бұрын
Great craftsmanship tech
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks Victor!! 😎
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Been busy....just catching up on videos.....keep it bro...I enjoy the content and the channel
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
The Heat is On 🔥 Thanks Jason 😎
@joeyf504327
@joeyf504327 2 ай бұрын
Nice job
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Thanks!
@nicolasmuniz9452
@nicolasmuniz9452 3 ай бұрын
Looks like the H/F vacuum pump works great.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
I’m using it where I can to keep testing 👍
@OIC-es6pi
@OIC-es6pi 3 ай бұрын
Nice work.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks!
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks!
@stevencossaboon3237
@stevencossaboon3237 3 ай бұрын
Nice work Subcool.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks brother 👍
@zekenzy6486
@zekenzy6486 3 ай бұрын
Great video. Thank you for sharing. Have a nice weekend
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thank you! You too!
@MarcelHVAC
@MarcelHVAC 3 ай бұрын
Great job, what was the smoke coming from the condensor? Dirty condensor or was it oil from then refrignant lines burning? Like your oldschool scale, i bet it will survive you!
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
It was a combination of leak detector liquid boiling off and may have been residual oil on the coil from the initial leak. Yep, the scale will outlast me 👍
@topher8634
@topher8634 3 ай бұрын
When those aluminum coils started coming out, all the manufacturers claimed they couldn't leak.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
A lot of claims were made when r410a was introduced as the new standard, here we go again with A2L 👀
@topher8634
@topher8634 3 ай бұрын
@@subcoolHVAC give it 10 years and it'll be contributing to something as well
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
@@topher8634Agreed 100%
@RobertTuck-vo8cw
@RobertTuck-vo8cw 3 ай бұрын
Good job. I would bet that the evaporator coil has never been cleaned or even looked at. Also with that number of suspicious spots, the coil will leak in another place.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
The evaporator was pretty clean, usually they rust on the end sheets. I’ve repaired many of these condensers like that. It’s the same spot most of the time . It’s best years are behind it for sure. 👍
@SFBay69
@SFBay69 3 ай бұрын
@@subcoolHVAC Crazy how rusty these evap coils can be. Is there any correlation between strict filter maintenance and leaks in evap coils?
@kamranjutt9040
@kamranjutt9040 3 ай бұрын
Good work👍 but if the leakage is close to metal part of condenser. It is better to carefully melt the surroundings of metal part touching copper u and then solder copper part No callback no complains . I work as an hvac technicion in kuwait .
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
You realize the end sheet melts at a higher temp than the copper, trying to melt that would destroy the copper. Thanks for the comment though👍
@kamranjutt9040
@kamranjutt9040 3 ай бұрын
@@subcoolHVAC I have done it bro It needs super skills But any way your work is outstanding 👍
@TrustedHVACR
@TrustedHVACR 3 ай бұрын
I would be challenged to do that without burning a hole through the copper … any suggestions?
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Yep, clean the u-bend with sand cloth, small light flame and keep it moving with brazing melting over it. I use Stay-silv 6% . Had to stop the nitro because it was popping holes, but got it to close. You can do it. 👍
@davidnull5590
@davidnull5590 3 ай бұрын
Thanks for the video, it was interesting. Was there a huge difference in price between a repair and replacement? thanks,
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks David, would’ve cost at least 6x the $ to replace , ultimately it’s customer decision 👍
@Paul-IE-Repairs
@Paul-IE-Repairs 3 ай бұрын
ive seen several systems installed without a dryer, when the lineset is less than 10ft long. i dont think that is the case in this situation. did someone put a hard start on a scroll compressor smh....
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
They provide a drier with those units, none was put in when the evaporator was replaced either 🤔.
@stevem1081
@stevem1081 3 ай бұрын
They may save money now, but the unit being that old, they will be paying a lot more in the long run due to it being less efficient and more leaks are likely to show up again before long.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Ultimately customers decision
@mrsmith5114
@mrsmith5114 3 ай бұрын
Wish you posted the prices.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Replacement would’ve cost 6-7 times as much if that helps
@mrsmith5114
@mrsmith5114 3 ай бұрын
@@subcoolHVAC It does :) Thanks for the response. Donno why I watch all these repair stuff, but always interested in the prices. Best of luck!
@nicolasmuniz9452
@nicolasmuniz9452 3 ай бұрын
Hopefully no fan, capacitor or compressor goes out in the near future they might blame it on you, usually no good deed goes unpunished, I've done a a couple of less expensive jobs to help a customer out and BAM! they call back that their water heater, on other side of house does not work a day after I repaired the a/c, this really happened to me, just told them to go kick rocks.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
I did replace the capacitor, no guarantees when in situations like this. The owner is aware of the condition
@DabblelyDiddly
@DabblelyDiddly 3 ай бұрын
funny, most window units still use copper. besides the midea 5k
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
👍
@bjbuchanan7326
@bjbuchanan7326 2 ай бұрын
What was the cost of fixing the unit?
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
About 1/5 the cost to replace
@divine4fi244
@divine4fi244 3 ай бұрын
They dont make them capacitors like they used to 😅
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Definitely not !
@jwotham96
@jwotham96 3 ай бұрын
Forgot the video, but what is your opinion on the compressor jackets? My unit has one and I still need to clean it.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Sound blanket? Not a fan… not sure what that has to do with cleaning?
@jwotham96
@jwotham96 3 ай бұрын
@@subcoolHVAC didn’t think about it for sound reduction. I asked so when I go in to clean I could address it at the same time if it had a negative effect. Thanks
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Gotcha, clean it sure or toss it 👍
@markcotter2355
@markcotter2355 3 ай бұрын
15 pounds of refrigerant good golly.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Yep 241 oz. Factory charged
@MindzEnt
@MindzEnt 3 ай бұрын
All depends on how much you charged them, if you go around making leak repairs for 500 bucks of course the owners will go with repairs.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Where did you get $500 ?
@wayneguy6043
@wayneguy6043 3 ай бұрын
Who wants to to put in a new 5 ton every 10-15 years for $18k
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
You could spend that much but not for a comparable replacement to this one . Thanks for watching!
2Yr Old Goodman AC Just Stopped cooling… Aluminum Coil Repair
16:53
Офицер, я всё объясню
01:00
История одного вокалиста
Рет қаралды 5 МЛН
哈莉奎因怎么变骷髅了#小丑 #shorts
00:19
好人小丑
Рет қаралды 55 МЛН
Which One Is The Best - From Small To Giant #katebrush #shorts
00:17
Customer Fired Other Company! Can I Figure This No Cooling Out?
18:25
Jeff’s HVAC Adventures
Рет қаралды 480 М.
HVAC Contractors Practically Make Their Living On These
11:26
The DIY HVAC Guy
Рет қаралды 1,4 МЛН
Refrigerant line repair after customer accidentally cuts it
4:47
HVAC Legend
Рет қаралды 1,3 М.
18 Year Old HVAC Technician
12:48
Ewok
Рет қаралды 109 М.
Problems Hiding In Plain Sight! #hvacguy #hvaclife
39:21
HVAC GUY
Рет қаралды 62 М.
"Flammable" Refrigerant Facts for Residential HVAC
1:02:01
HVAC School
Рет қаралды 113 М.
Tossed to the Curb - Neglected Push String Trimmer
1:40:19
James Condon
Рет қаралды 821 М.
Condenser Pump And Motor Install With Some York YMC2 Surging Issues
12:55
Офицер, я всё объясню
01:00
История одного вокалиста
Рет қаралды 5 МЛН