Follow up on Trane RTAE that blew 200amp AFD fuses from what appeared to be just a lizard shorting the phase… here’s the results #hvac #trane #hvacrepair #chiller
Пікірлер: 33
@BOBKB3NZX2 ай бұрын
I always enjoy getting to watch your work. Glad I found your channel
@subcoolHVAC2 ай бұрын
Awesome, Thank you! 👊
@spikester2 ай бұрын
Lucky that mr. lizard didn't take out the diode packs.
@subcoolHVAC2 ай бұрын
⚡️yep
@ericbaker56192 ай бұрын
Got her back in stealth mode. Was waiting for the sequel. Youre apprentice is gonna be awesome.
@subcoolHVAC2 ай бұрын
I like that Stealth Mode 👍 The apprentice is doing well, today is his 1yr anniversary in the trade 👊
@thesilentonevictor2 ай бұрын
Good work having her back online
@subcoolHVAC2 ай бұрын
Thanks SilentoneVictor 👊
@rodnnymarquez99242 ай бұрын
good work and excellent contribution
@subcoolHVAC2 ай бұрын
Thanks for watching 👍
@ccthepope2 ай бұрын
good show, damn good show!
@subcoolHVAC2 ай бұрын
😀 Thanks for the support 👍
@ddrl462 ай бұрын
Nice timing with the impact at 5:00 hah.
@subcoolHVAC2 ай бұрын
Thanks Dylan 👍
@KyleWithStyle7Ай бұрын
Nice work
@subcoolHVACАй бұрын
Thanks
@stevencossaboon32372 ай бұрын
Nice work Subcool.
@subcoolHVAC2 ай бұрын
Thanks Steven 👍
@jasonjohnsonHVAC2 ай бұрын
Nice little voltage drop when she fired up. Do yall have crappy power there. We definitely do and we have lots of issues when the buildings get power loss or a surge. Nicely done by yall. Another chiller running.
@subcoolHVAC2 ай бұрын
Ha, we do have our share of power issues especially when storms roll through. Thanks Jason !
@zekenzy64862 ай бұрын
Great Video. Good Job and Nice Work. Thank you for sharing. May I ask, what is the name fuse ?
@subcoolHVAC2 ай бұрын
Thanks, it’s VFD Semiconductor Fuse Type FWH-200B (200 amp)
@gantmj2 ай бұрын
I always use the German torque specs.
@subcoolHVAC2 ай бұрын
It’s not just for lug nuts 🤣👍
@JC-sc9rx2 ай бұрын
So chiller compressor resistance values between terminals should all be the same? New to trade, Thanks for video !
@subcoolHVAC2 ай бұрын
Good question, on 3 phase like this one Trane recommends 0.2 to 2.5 ohms DC resistance of windings be within 5-10% of each other. Thanks 👍
@Ag89q43G0HyA2 ай бұрын
Is that thing variable? i mean, could it handle little loads to high ones and not waste energy overworking like my window ac?
@subcoolHVAC2 ай бұрын
Yes its 150 Ton chiller with variable speed compressors
@CATA200342 ай бұрын
You know when a technician and not an engineer is making the measurements. You measured the input and you had less than an ohm, and after that you tested EACH one with high pot to GND.... WHY? If you have 1 ohm between each winding, and you tested first of them to GND and had 2200MEG.... for sure the other will be the same...as they had one ohm between them....
@subcoolHVAC2 ай бұрын
Good question GRC, because one good reading doesn’t mean something isn’t wrong. However, one bad reading guarantees something is wrong. Thanks for asking 👍
@inothome2 ай бұрын
Agreed, 100% correct after verifying winding resistance on a three wire motor, test one leg and you tested them all. But, it doesn't take much time to do the other two and the one time someone doesn't check all phases is the one time they didn't measure the winding resistance correct and there is a bad winding. So not losing anything by doing all three but a minute or so.
@Hwishebak2 ай бұрын
lol you perfectly encapsulated the lack of real life problem solving engineers are known for
@haldermand2 ай бұрын
Stick to your clipboard and computer programs. Let the big kids handle the work in the field - where the real problems are solved.