(2) 13 ton Aaon's....multiple alarms.....simple problem causing all kinds of issues.

  Рет қаралды 1,011

Jason Johnson

Jason Johnson

4 ай бұрын

‪@EverythingHVACR‬ ‪@ReliableHVACR‬ ‪@KoolinwithKrauss‬ ‪@subcoolHVAC‬ ‪@HVACUncensored‬ ‪@HVACRSurvival‬ ‪@HughesManHVAC‬

Пікірлер: 17
@fshn76
@fshn76 4 ай бұрын
That’s was cool. Don’t deal with Aons but I have had similar this happens with Emerson E2 controller modules that are mounted o. RTUs for remote operations. As soon as you were showing the weird codes I thought bad connection. Good stuff JJ
@jasonjohnsonHVAC
@jasonjohnsonHVAC 4 ай бұрын
Thanks Bryan...the biggest issue was that when there is a module fault..Aaon controllers will default to factory program. These are using the E-Bus comms. Its very similar to other systems that daisy chain their comms. Thanks for the comment.
@Eddy63
@Eddy63 4 ай бұрын
Good find JJ ... Thx
@jasonjohnsonHVAC
@jasonjohnsonHVAC 4 ай бұрын
Thanks Eddy...appreciate you and your support
@NROhvac
@NROhvac 3 ай бұрын
Good find!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Thanks for watching and the comment
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
Well done Jason, Thanks for the education!!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 4 ай бұрын
Thanks broski....i appreciate your channel and knowledge as well....that last video of yours was awesome. Really enjoyed it
@EverythingHVACR
@EverythingHVACR 4 ай бұрын
Interesting stuff, thanks Jason!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 4 ай бұрын
Thanks Steve-o. Appreciate you bro.
@neilcvids2583
@neilcvids2583 4 ай бұрын
so you just remade those splices at the OA TnH ? correct? I have a handful of Aaon here on Long Island Sound, definately remembering to check , , ,
@jasonjohnsonHVAC
@jasonjohnsonHVAC 4 ай бұрын
Yes sir. Wasn't worried because they are using voltage and not resistance. I used a hygrometer to confirm what the sensor was reading vs what it really was. It was mighty close. So i know im not causing a false reading due to a voltage drop or additional resistance to the input. Thanks for the comment
@NestorDelgado-fr6pu
@NestorDelgado-fr6pu 22 күн бұрын
What was your clue,how did you figure out that conector/sensor was bad
@jasonjohnsonHVAC
@jasonjohnsonHVAC 21 күн бұрын
Because I was getting so many errors, especially for weird stuff. The whole thing works on a comm bus. Every module is daisy chained together. The fact all the modules were showing alarms, gave me an indication that it was something on the comm bus.
@Eighty8Fitter
@Eighty8Fitter Ай бұрын
Addison units are just as bad as Aaons. Id take a Trane with a Symbio controller any day over an Aaon!
@jasonjohnsonHVAC
@jasonjohnsonHVAC Ай бұрын
I really don't mind AAON units. Yes they can be a pain at times....but like anything....enough practice and bumping you head....it gets easier. Thanks for the comment
@3cats932
@3cats932 2 ай бұрын
I Hate AAON!!!!
How to Update the AAON Wattmaster RSMD Board
5:36
HVAC TV
Рет қаралды 438
Always be more smart #shorts
00:32
Jin and Hattie
Рет қаралды 47 МЛН
I Can't Believe We Did This...
00:38
Stokes Twins
Рет қаралды 81 МЛН
HVAC TROUBLESHOOTING | CONTROLS METHOD
16:53
D2D NY Real World HVAC Simplified
Рет қаралды 9 М.
Refrigeration - 5 ton chiller startup 407c.
3:21
Mike Refrigeration
Рет қаралды 553
AAON : Economizer and Actuator - JohnsonBarrow: Costco
3:28
Johnson Barrow - Costco
Рет қаралды 1,2 М.
AAON Package Unit Basic Troubleshooting.
25:42
Tech-Survival
Рет қаралды 9 М.
Little tour of the plant I was in this morning. Has a big AHU.
2:58