What you should determine is what the temperature reset source is and look at the low/high reset source setpoints. The reset source can be the VFD speed, the outside air temperature, or the space temperature. The low/high reset source setpoints are the values from the reset source that determines what the SAT setpoint will be between the setpoint and high reset setpoint. I recommend looking into getting a CommLink 5 with the IP/Ethernet module, or if your building has a BACnet BMS system, to wire it into the BACnet terminals on the controller.
@jasonjohnsonHVAC13 күн бұрын
USB LINK 2 and PRISIM2 software is a game changer. I have the handheld...but i stopped using once i started using my laptop.