Charging a Heat Pump at Start up or in the Winter Time! What you need to Know!

  Рет қаралды 232,616

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

This is how to charge a new R-410A heat pump system in the middle of winter. An overview of the superheat process is explained and examined to see if you can use it to charge since the liquid is going through a piston in heat pump mode. Refrigerant weights per lineal foot of lineset are discussed for liquid and vapor sizes.
Tool List- www.amazon.com...
Support- / acservicetech
Our Inverter Mini Split Resources:
Mini Split Book on Our Website- www.acservicet...
Mini Split Paperback on Amazon- amzn.to/3ytHJSs
Mini Split Paperback on TruTech Tools- www.trutechtoo...
Mini Split E-Book on Google- play.google.co...
Mini Split E-Book on Apple- books.apple.co...
Our Single Speed and Two Speed Air Conditioning Resources:
My Paperback and E-Book: www.acservicet...
My Paperback: www.amazon.com...
Read the book reviews on Amazon!
Check out our new Articles at www.acservicet...
Support the Channel by purchasing tools through Tru Tech Tools!
Use this link www.trutechtoo...
Save 8% at checkout using code "acservicetech"
Supervision is needed by a licensed HVAC Tech while doing this as Experience and Apprenticeship garners Wisdom and Safety.
All of the ACSERVICETECH Playlists- / @acservicetechchannel
If you want to support the ACSERVICETECH Channel and receive more HVAC content, check out www.Patreon.com/acservicetech
ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com.
You can enter Amazon through this amzn.to/2aenwTq
The above link happens to be the Gauge Set that I use in my refrigerant videos but you can search from there.
Here is a link to the UEI DL389 Multimeter used in the video amzn.to/2xAdaJf
Here is the link to the Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka
Here is a link for the Supco Magnet Jumpers amzn.to/2gS4h6z
Here is a link to Refrigerant hoses with valves used in the videos amzn.to/2aBumVI
Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos amzn.to/2aenwTq
Here is a link to the Digital Refrigerant Scale used in the video
amzn.to/2b9oXYl
Here is a link to the Imperial 535-C Kwik Charge Vaporizer for Charging Refrigerant- amzn.to/2oge0u9
Here is a link to the thermostat 3/32 screwdriver -- amzn.to/2hxt7uK
Here is a link to the C&D core removal tool amzn.to/2bFpobQ
Here is a link to the JB 6 CFM Vacuum Pump amzn.to/2nqbvo8
Here is a link to the JB Platinum 5 CFM Vacuum Pump with Valve
amzn.to/2mGKcSh
Here is a link to 1 gallon of JB Vacuum Pump Oil amzn.to/2mGrlXy
Here is a link to the Supco Vacuum Micron Gauge amzn.to/2bH98bO
Here is a link to the 1/4" by 1/4" female coupler from Supco - amzn.to/2kFrbU9
Here is a link to the Hilmor 4 port Aluminum Manifold Gauge Set-
amzn.to/2m4QLik
Here is a link to the Supco core removal tool amzn.to/2brEJco
Here is a link the Nitrogen Regulator amzn.to/2bXdR5f
Here is a link to the Nitrogen Flow Meter amzn.to/2brvoBg
Here is a link to the General Tools digital Psychrometer
amzn.to/2cSHsi1
Here is a link to the Amprobe Digital Psychrometer amzn.to/2d7cGkW
Here is a link to the Fieldpiece SDP2 Digital Psychrometer- amzn.to/2nniMVR
Here is the UEI Digital Manometer used in the videos amzn.to/2c1XkiT
Here is the link for the Ratcheting Service Wrench amzn.to/2dGV4Nh
Here is a link to the Appion G5 Twin Recovery Pump amzn.to/2dGSEyr
Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
Here is a link to the air acetylene torch setup- amzn.to/2aQalsb
Here is a link to the Malco Snap Lock Punch amzn.to/2cY53Ag
Here is a link to the Wiss 3 Pack Tin Snips amzn.to/2bHWhWO
Here is a link to the Wiss 5 Blade Crimper amzn.to/2bwTlsW
Here is a link to the Wiss Hand Seamers amzn.to/2dRk83v
Here is the link for the Hitachi Lithium Ion Drill and Flashlight kit amzn.to/2dzNgkL
Here is the link for the Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V
Here is the link for the Hilmor 12" folding tool amzn.to/2d9VTPR
Here is the link for the Malco 3" Blade Combination Snips amzn.to/2dz7Ejc
Thank You,
ACSERVICETECH

Пікірлер: 65
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Our Inverter Mini Split Resources: Mini Split Book on Our Website- www.acservicetech.com/mini-split-book Mini Split Paperback on Amazon- amzn.to/3ytHJSs Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGuides?aff=8 Mini Split E-Book on Google- play.google.com/store/books/details?id=HN-iEAAAQBAJ Mini Split E-Book on Apple- books.apple.com/us/book/id6445178399 Our Single Speed and Two Speed Air Conditioning Resources: My Paperback and E-Book: www.acservicetech.com/the-book My Paperback: www.amazon.com/shop/acservicetech Read the book reviews on Amazon! Check out our new Articles at www.acservicetech.com/articles Support the Channel by purchasing tools through Tru Tech Tools! Use this link www.trutechtools.com/?Aff=8 Save 8% at checkout using code "acservicetech" Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Linked Below) Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos- amzn.to/2aenwTq Here is a link to Refrigerant hoses with valves used in the videos- amzn.to/2aBumVI Here is a link to the UEI DL389 Multimeter used in the videos- amzn.to/2xAdaJf Here is a link to the Imperial 535-C Kwik Charge Vaporizer for Charging Refrigerant- amzn.to/2wFHtBW Here is the link to the Fieldpiece ST4 Dual Temp Meter- amzn.to/2wc1ME3 Here is a link to the Digital Refrigerant Scale used in the videos- amzn.to/2b9oXYl Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn Other tool links can be found in the video description section. ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon. Check out other videos on the HVACR topics of interest at- kzbin.info/door/OZR-1IqsAer9wzlvFgb4mAplaylists?view_as=public If you want to support the ACSERVICETECH Channel and receive more HVAC content, check out www.Patreon.com/acservicetech
@Garfield_Campbell
@Garfield_Campbell Жыл бұрын
Brother, thank you for this video. People don't understand how much science is behind all this. Hats off.
@mrd4292
@mrd4292 Ай бұрын
You are so good teaching AC . I am so graceful.. Tks
@jimbola77
@jimbola77 7 жыл бұрын
I'm very impressed with your work acservicetech!!!! I drive OTR I watch your work over and over I wish I had your knowledge, OTR is very tiring! and I love working with my hand's! thank you so much for sharing! people I know won't share they act like it is rocket science! but when I show what I have learned over the year's from you they are stunned.
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Well thank you very much Jimbola77. I always appreciate your comments, that's cool about their response!
@Brnstrmr
@Brnstrmr 3 жыл бұрын
This isn't how to charge in the winter. It's how much to add when changing line lengths.
@fishlifeknives7429
@fishlifeknives7429 Жыл бұрын
He said basically you can't do it. If you were listening
@Wibob636
@Wibob636 3 ай бұрын
@@fishlifeknives7429yea well it wasn’t basic enough.
@fishlifeknives7429
@fishlifeknives7429 3 ай бұрын
@@Wibob636 lol
@jimbola77
@jimbola77 8 жыл бұрын
excellent presentation!!!!
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
+jimbola77 Thanks!
@matthewedwardsnyder
@matthewedwardsnyder 2 жыл бұрын
Should we be adding the refrigerant in liquid or vapor state during the winter time and should we be adding it in to the discharge line or into the true suction line?
@matthewedwardsnyder
@matthewedwardsnyder 2 жыл бұрын
My understanding is that the heat pump it in winter everything is backwards so my assumption is we should be charging the system with Vapor into the discharge line because we are charging into the condenser which is now the evaporator because it’s winter
@davidashcom6087
@davidashcom6087 3 жыл бұрын
Sir you cannot check the superheat of that unit like that. Your probe must be on an actual suction line. The pipe you are attached to has no refrigerant flowing through it, it is for checking pressure only.
@tyl8ter
@tyl8ter 3 жыл бұрын
do you mean coming off the compressor?
@schpanker
@schpanker 4 жыл бұрын
I see that you are connected to the common port. Is it possible to charge the system through the common port in cooling mode? I'm thinking of using stubby gauges instead of hoses to save refrigerant when checking the system and would like to hook up the charging hose to the common port when needed.
@richgallagher4160
@richgallagher4160 3 жыл бұрын
So how do you check the charge on a heat pump in winter
@pedrocastano6410
@pedrocastano6410 2 жыл бұрын
Nobody knows
@heatncool
@heatncool 5 жыл бұрын
Replaced evaporator coil. After nitrogen leak test and pulling vaccum to around 500 microns. I charged it up according to nameplate. 11 lb 4 oz. Added 5 oz extra for long lines. It is split heat pump. I checked delta t on cooling. 18. On heating it took a while to heat up but got to 17 in 7 minutes or so. It went smoothly and I said my goodbyes to the customer and that id be out in 5 minutes. When I get back it's still running on heat and pressure are 500 or tetard on low and 400 on high. (Reverse refrigerant flow ) my heart sank at first. But I see i needed to use the true suction port on heating instead of the liquid line? Although sometimes I checked before it read the same? Also ambient was 65
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
After when you charge in the exact amount needed, you can check the charge like normal with subcooling (if equipment has a txv) if you use a charging jacket or another way to reduce airflow across the condensor if it is below 70 degrees outside. You would target the saturated temp of the condensor to 95 before checking the charge. I want to do a video on that soon, thanks
@jimmyung3212
@jimmyung3212 7 жыл бұрын
Great inform thank you!!!
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Thank you!
@vukknezevic4258
@vukknezevic4258 2 жыл бұрын
I have this in my place,i have hot water in the sink but only mild in the tub? Help me! Thanks
@phillipjoy8191
@phillipjoy8191 7 жыл бұрын
In heat mode could you hook the high side gauge to the liquid line instead of the discharge line? Great videos
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
The liquid line in heat mode won't give you much if that is where the piston is so it will be a low pressure liquid before phase changing and superheating. It depends if the piston is before or after. We usually are on the large vapor line and true suction for heat mode. Thanks
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Check this one out and note where the piston often is in answer to your question, thanks- kzbin.info/www/bejne/haSViICHrayGrdU
@mark.r8900
@mark.r8900 3 жыл бұрын
So in cooling mode, red hose to liquid line and blue hose to suction line as usual. But in heat mode now red hose to 3/4 line where does blue hose go? In both modes your low side always need to be higher than 32F correct? Thanks.
@waltherherrera67
@waltherherrera67 9 ай бұрын
Excelente
@larsonhomeinspection9932
@larsonhomeinspection9932 4 жыл бұрын
How often do you have to adjust the TXV or adjust the charge based on superheat on a new installation?
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
We shouldn't have to go and adjust an ac system TXV if it was correctly set originally. Most TXV's for AC don't even have an adjustment stem on the bottom. If there is high superheat and low vapor pressure, coupled with normal to high subcooling then that would indicate a liquid line restriction such as a TXV. It could also be a strainer screen or the filter drier. I go into detail explaining troubleshooting scenarios as well as charging procedures in my book which is available at the website, www.acservicetech.com thanks!
@seanmcdermott416
@seanmcdermott416 6 жыл бұрын
Would you consider doing a lesson on the 30 + rule when using the PT Chart when measuring head pressure on a low SEER unit ? I've heard of it before but never had to apply it in the field yet . Thanks again BroOski
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
I would not advise applying it. It will get you close and some older factory reps were teaching it for a while. Just maintain using superheat and subcooling to get exact amounts for efficiency and compressor safety. I may do a video on that for next summer. Maybe you can remind me when we get closer. I try to stick with the season we are in as much as possible, thanks Sean!
@caru3257
@caru3257 6 жыл бұрын
Newer unit have that number lowered.
@waynemiles7027
@waynemiles7027 7 жыл бұрын
What are some rule of thumbs when servicing old heat pumps in winter mode to check the charge? Pressures should be? Indoor temp. Split? Anything would be helpful, thanks.
@IshockO
@IshockO 7 жыл бұрын
Wayne Miles I got the same questions :(
@MrOhiousa
@MrOhiousa 7 жыл бұрын
My understanding is that since the outdoor unit is the evaporator in the heating mode, and the txv controls the superheat, and most of the manufactures design the txv for 10 to 15 degrees of superheat, if you are in that range. you are in good shape, temperature split between 20 to 30 is good in the indoor coil, of course airflow is very important. i will not worry too much about pressure. since pressure and temperature follow each other that number is going to be dependant on indoor and outdoor temperature
@caru3257
@caru3257 6 жыл бұрын
Read the literature that came with the unit. Most of the times, instructions to charge in heat mode are outlined.
@junkyardjedi7706
@junkyardjedi7706 4 жыл бұрын
If the temp indoors is above 70 you can check the sub cool in a/c mode if you restrict the air flow at the condensor. He made a video on how to do this.
@acelookrenos611
@acelookrenos611 5 жыл бұрын
Hi Craig Iv got a quick question There is a mini split system r410a on heating mode the discharge line goes up 690 psig and actual temperature of 62 Celsius. There is no other valve to connect my hose to except vapor(discharge on heating) question is that 690psig isn't it a little higher than normal? What's wrong with unit then?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Hey Ace, it sounds high to me too. Is it possible it is overcharged? Did you check it in max cool and find a superheat of 0 to 5 degrees of superheat? Thanks!
@acelookrenos611
@acelookrenos611 5 жыл бұрын
@@acservicetechchannel The superheat was about 8 degree Celsius as we are in Australia and now it's winter time but not that much cold. Saturation about 5 degree Celsius Suction line temp about 15 16 Celsius After reversing it from heat to cool
@acelookrenos611
@acelookrenos611 5 жыл бұрын
By the way I mean 690 kpa not psi in my first message
@joshuameadows5574
@joshuameadows5574 7 жыл бұрын
You have the liquid line hose on the suction line because thats now your discharge line because your in heat mode. So in effect that now somewhat turns into you liquid line in cooling mode. Am i somewhat understanding it? Do you always hook up your guages like that in heat mode.
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Yes that is the way we hook up in heat mode. the red gauge is hooked to the discharge vapor but in cooling this would be low pressure vapor. The small liquid line will remain liquid but it is just the direction in which it is going. Check this refrigerant cycle with flow video --- kzbin.info/www/bejne/haSViICHrayGrdU --- I will be making one like this for while it is in heat mode as well
@joshuameadows5574
@joshuameadows5574 7 жыл бұрын
thanks man for all the help
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
No prob!
@joshuameadows5574
@joshuameadows5574 7 жыл бұрын
Hey ac service tech ive been watching a lot of your videos and i would like to thank you for all the time that you put into your videos it helps clarify a lot of the basics. Do you know when youll be making the video on the cycle in heat mode so i can watch out for it?
@israelquintanilla2784
@israelquintanilla2784 7 жыл бұрын
have you tried using the fieldpiece charging blanket ? would like to see a video how that works
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
I was thinking of making a video in low outdoor temps at some point. I just arrived home from installing a tankless combi boiler unit for the last 13 hours but at some point I would like to do a video like that. Thanks
@JohnstonPettigrew
@JohnstonPettigrew 5 жыл бұрын
alright!!!!
@drmikeosgood
@drmikeosgood Жыл бұрын
you miss the point of charging by sub cooling method!!
@es27co21
@es27co21 5 жыл бұрын
Would low Freon make the heat pump short cycle in heating mode ?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Only if the unit was shutting off the outdoor unit due to a low pressure switch in the vapor refrigerant line, thanks
@christopheblock8561
@christopheblock8561 7 жыл бұрын
Hey brother, great channel! Very professional and informative. In a situation where we are unsure of line set length can we use discharge temp on a TXV unit to determine charge pressures in wintertime? If so, do you have a video or recommended procedure?
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Unfortunately we cannot because of the varying amount of refrigerant in the accumulator and the varying temp outside. A different outdoor temp will lead to varying discharge gas heat which will lead to varying heat transfer on the evap coil even when we have a roughly constant 63-73 degree temp value inside the building that you are rejecting into. You are going to have to guess the distance if you don't know the best you can. Some companies have come out with the charging bag that you put over the out door unit but that won't be right on either. Cooling mode drains most of the accumulator. I recommend that heat pumps be checked for any leakage during fall so that if there is a leak it is a large one that needs to be fixed and then you can weigh back in. Of course it is harder if something is not serviced and then doesn't seem to heat in the winter. Start really paying attention to your supply minus return indoor conditioned air temps on different outdoor degree days at customers places so you can feel confident if another system is working properly depending on seer, cfm, coil life and then check it for exacts when it is 65-70 degrees outside in spring. I hope this helps a little bit!
@christopheblock8561
@christopheblock8561 7 жыл бұрын
Man you are one of the best (in every sense of the word) youtubers out there! Thanks for doing what you do.
@daviddebord7236
@daviddebord7236 6 жыл бұрын
Greetings! I Literally ran in to this same problem (The Wailing Gerbil like noise), with one of my Customers: kzbin.info/www/bejne/oXywgYOiZZdmfLM With the exception of the Noise, there are no other Complaints. The unit is heating the home satisfactorily in the heat pump mode. The HP is a Goodman GSH130421E, with 20ft lineset & a "All Style" ASUM 42 Coil that Goodman & Lute Supply of Cinti., Ohio "Certified" as "Matching". I installed this system 7 years ago, & the only problems were the Compressor needing a "Hard-start kit" (2 years ago), & a TXV that failed in July 2017. The System ran, with no problems up to approx. Mid November, when the "Gerbil getting strangled" noise began to infrequently appear in the Cooling & Heating mode. I'm going back to the Job tomorrow, & intend to to Trouble-shoot the System, but now another "Unbelievable" situation has arose, ....For some reason Goodman Tech is telling me that Checking for Sub-cooling will not work!?!?!?! I asked "Tyler" what he was talking about, & he really couldn't give me an explanation (WTH????), & he wants me to call him from the Job site. I'm thinking that this "Wailing noise" is coming from the Internal Check valve of the TXV, & I was wondering if You have ever run across something like this? Also, can you think of any reason why, Checking Sub-cooling, in the heating Mode, of this Heat Pump will not work, as "Goodman Tech" is saying?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
That is correct that you need to check subcooling in cooling mode only because otherwise, you don't know how much refrigerant is in the accumulator. In cooling it is drained. If it is below 65 degrees then you would need to limit outdoor unit airflow with a charging jacket to check cooling. When the internal pressure relief is not sealing there will be higher than normal vapor pressure in cooling mode. Thanks David!
@CHOMAHOMA
@CHOMAHOMA 2 жыл бұрын
Good, but I am looking for a real example. Someone actually performing the process.
@SR-jz9wn
@SR-jz9wn 3 жыл бұрын
good information, but a total fail titling the context of the video. You neither charged nor started the heat pump. Down voted.
@mychoclabwinston
@mychoclabwinston 7 жыл бұрын
High side one on the wrong port,
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
This is in heat mode so the large vapor is the discharge gas. The liquid line is the subcooled liquid from the indoor coil.
@SuperSincere1
@SuperSincere1 5 жыл бұрын
@@acservicetechchannel you still wouldn't hook up the gauges like that. The red will still go on the liquid side and you would put thr blue on your true suction port
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Hey Curtis, I would still turn the unit on in cooling mode and charge any extra refrigerant into the vapor service port. This is because this will enter the accumulator before entering the compressor. If you charge any liquid into the true suction port, it will immediately enter the compressor. You have to be extremely slow if you charge any refrigerant into that port. R-22 since it is a single component refrigerant can be charged in as a gas into that port though, thanks!
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
If you want to support the ACSERVICETECH Channel and receive more HVAC Content, Correspond, or Collaborate on your endeavors- check out www.Patreon.com/acservicetech All of the ACSERVICETECH Playlists- kzbin.info/door/OZR-1IqsAer9wzlvFgb4mAplaylists?view_as=public Submit your email to the ACSERVICETECH email updates list at info@acservicetech.com
Charging R-410A Refrigerant into an Air Conditioner! Pressures, Temps, Tips!
27:56
AC Service Tech LLC
Рет қаралды 1,5 МЛН
Heat Pump Freezing Up in Apartment Building
23:19
Taddy Digest
Рет қаралды 8 М.
Minecraft Creeper Family is back! #minecraft #funny #memes
00:26
The CUTEST flower girl on YouTube (2019-2024)
00:10
Hungry FAM
Рет қаралды 51 МЛН
Or is Harriet Quinn good? #cosplay#joker #Harriet Quinn
00:20
佐助与鸣人
Рет қаралды 57 МЛН
АЗАРТНИК 4 |СЕЗОН 2 Серия
31:45
Inter Production
Рет қаралды 1 МЛН
Charging a Heat Pump in Heat Mode
6:14
HVAC School
Рет қаралды 87 М.
Charging an AC System Low on Refrigerant in Real Time! Part 1
9:47
AC Service Tech LLC
Рет қаралды 67 М.
How to check a charge in heating.. (R-410A Heat Pump)
5:08
HVAC Tech Tips
Рет қаралды 68 М.
Checking the R-410A Refrigerant Charge! What to Watch Out For!
42:39
AC Service Tech LLC
Рет қаралды 72 М.
Refrigerant Levels on a Heat Pump. Proper Subcool
2:51
HVAC Guide for Homeowners
Рет қаралды 2,9 М.
R-22 and R-410A Refrigerant Operating Pressures on Air Conditioning Units!
14:56
Should You Replace a Bad TXV with a Piston? & TXV Diagnosis!
21:53
AC Service Tech LLC
Рет қаралды 28 М.
The Sequence of Operation for a Defrost Heat Pump Board
9:30
SuperCool Slide Rule
Рет қаралды 224 М.
Minecraft Creeper Family is back! #minecraft #funny #memes
00:26