Charging R-410A Refrigerant Into An Air Conditioner Using Wireless Probes!

  Рет қаралды 44,536

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер
@deanmartin1966
@deanmartin1966 5 ай бұрын
I'm sure I've said it before, but thanks for all the great free information you and all the other great teachers provide. Such a wealth of knowledge. I'm 58 and I absolutely hated high school. Until I got into the trades. Then surprisingly I became an "A" student. I seriously love the trades and think its a great alternative to a four year college. My grand daughter is 15 and wants to become a welder. She makes me proud. Once again, thanks. Phil
@Tomkayanja
@Tomkayanja 4 ай бұрын
Thank for the video, the effort and time you put in make the world a better place to leave in.
@edwardlouie
@edwardlouie 5 ай бұрын
I like using core depressors so I don't need to spin on/off quickly.
@Meenomack
@Meenomack 4 ай бұрын
This guy is a bad dude ! Always on point !
@kevinpearce3281
@kevinpearce3281 4 ай бұрын
I bought those probes. I don’t have the manometers yet tho. Some day I’ll get what I need to do my job properly.
@deanmartin1966
@deanmartin1966 5 ай бұрын
Excellent video Craig. I do love my fieldpeace probes.
@pongobongo2295
@pongobongo2295 5 ай бұрын
Use Appion charging tees. This is my go to charge set up. Also, get a third probe and map to outdoor air temp.
@electrolatif
@electrolatif 5 ай бұрын
The best aircon video in KZbin ❤
@yannkitson116
@yannkitson116 5 ай бұрын
Great video, I have Testo probes and a slightly different app but it is all the same in the end :)
@paulrmfd
@paulrmfd 5 ай бұрын
absolutely instructional keep up the good work
@kastenusa
@kastenusa 5 ай бұрын
Can you please make a video on where to connect probs on package unit correctly. Thank you!
@cryptkeyper
@cryptkeyper 5 ай бұрын
I second this
@kinstonboy1
@kinstonboy1 3 ай бұрын
Supply & return duck lol​@@cryptkeyper
@povoljan13
@povoljan13 5 ай бұрын
The charging hose has air when you hooked it up to the tee. The small space after the shutoff valve is dead air space. Needs a better setup maybe?
@pbrewton
@pbrewton 3 ай бұрын
@acservicetechchannel Craig, correction to your statement: 75F as our *outdoor* dry bulb... 😊 8:47
@mohdrifi1930
@mohdrifi1930 5 ай бұрын
Excellent! You need to do this method to ac split unit also! Appreciate your effort teacher! ❤️❤️❤️❤️
@cryptkeyper
@cryptkeyper 5 ай бұрын
This is a ac split unit
@jericosha2842
@jericosha2842 5 ай бұрын
This doesn't work on mini split ductless if that's what you mean
@ludylopez3327
@ludylopez3327 4 ай бұрын
😮It's advisable to charge luguid in suction side.
@NickNameNemo
@NickNameNemo 5 ай бұрын
If system has leakage (r410a) and still remains some amount of refrigerant, let’s say 70-80% of total, should I recover all refrigerant from system and charge it with new or just add needed amount?
@pitaeata8493
@pitaeata8493 5 ай бұрын
need tips and tricks to determine if a system has a piston or txv. Sometimes on UNCASED coils it is impossible to remove the front of the field made cover to get a look.
@sir.cannabis1173
@sir.cannabis1173 5 ай бұрын
I'm thinking one could tell by how fast the numbers move. Craig mentioned it might take 15 minutes for pressures to equalize with a fixed.
@mackenziegray2090
@mackenziegray2090 5 ай бұрын
If you see a threaded union outside the case, chances are you got a piston.
@turnedearthdesign8678
@turnedearthdesign8678 5 ай бұрын
Also check the chart on the condenser. It usually (but not always) tells you what the pressure of one of the lines should be which should match up to the metering device used
@craigmarshall40
@craigmarshall40 4 ай бұрын
Great video thank you for spending the time
@Domopartner
@Domopartner 3 ай бұрын
great explanation thanks
@AndyHoltOutdoorUniversity
@AndyHoltOutdoorUniversity 5 ай бұрын
Nice job, Craig!
@justinhughes452
@justinhughes452 5 ай бұрын
What was the recommended amount of refrigerant on the name plate? How much was in system at the start and what was the total amount at the rnd of this demonstration?
@x-got2bkidiny-justlikeabov787
@x-got2bkidiny-justlikeabov787 4 ай бұрын
Awesome explanation but … the label on the unit says indoor TXV with 10 deg F sub cooling. You say it has a fixed orifice so you’re using the superheat method - am I a missing something here?
@acservicetechchannel
@acservicetechchannel 4 ай бұрын
Yes so the outdoor unit will always tell you the subcooling if a txv is used. However, as you can see through that plexiglass at the indoor unit, there is a piston there and not a txv. Single stage outdoor units can be installed with any combination of indoor units and metering device, thanks! To learn more check out our books at acservicetech.com !
@iamtheedrummer1
@iamtheedrummer1 4 ай бұрын
Yeah I caught that
@gingerstrand6153
@gingerstrand6153 5 ай бұрын
Great video, thank you!!
@arthurrabon9349
@arthurrabon9349 5 ай бұрын
multi zone split unit question. if you have 3 zones and 1 zone is having troubles meeting set temp. how does system respond.
@carlossaenz4075
@carlossaenz4075 2 ай бұрын
Can I down load the calculation app ? And so what do need to do
@SocratesDionisius
@SocratesDionisius 3 ай бұрын
What if we add r32 to r410 system. Let say we add 30% r32 into it?
@jorgemanzano7232
@jorgemanzano7232 5 ай бұрын
Well explained! Thank you very much 😊
@zahedaminullah6934
@zahedaminullah6934 5 ай бұрын
Great video man!
@TheWathever516
@TheWathever516 5 ай бұрын
Great video!
@kennethlobo4420
@kennethlobo4420 5 ай бұрын
Well explained ❤
@repairitdontwreckit4257
@repairitdontwreckit4257 5 ай бұрын
Thanks. Nice job.
@manueldacosta6539
@manueldacosta6539 5 ай бұрын
Excellent video as always, thank you.
@monstaro19
@monstaro19 5 ай бұрын
We need a way to use this in cars its 106 in Florida
@lorunner1213
@lorunner1213 5 ай бұрын
Craig. Does the outdoor Dry bulb temp matter if being read from the sunny side of the condenser vs the shady side?
@edwardlouie
@edwardlouie 5 ай бұрын
This method doesn't always work with inverter variable speed equipment that change the superheat target based on various logics.
@HVAC_Tips_Tricks_Calcs
@HVAC_Tips_Tricks_Calcs 5 ай бұрын
Inverters usually don’t have fixed orifices.
@JoeSullivan-k6c
@JoeSullivan-k6c 5 ай бұрын
? What is the link for the brass tees to purchase sir. Thank You.
@JuanJuarez-en5xn
@JuanJuarez-en5xn 5 ай бұрын
Can you make a video on RTU’S?
@mackenziegray2090
@mackenziegray2090 5 ай бұрын
It's the samething. What part confuses you?
@butlerstouchHVAC
@butlerstouchHVAC 5 ай бұрын
great vid
@JuanJuarez-en5xn
@JuanJuarez-en5xn 5 ай бұрын
Where can I buy those T’s that go on your probes do you have a link to them ?
@jimwhite9483
@jimwhite9483 5 ай бұрын
How hard would it be for Fieldpiece to add a wireless input for ODDB in the app or on the SMAN 380V?
@turnedearthdesign8678
@turnedearthdesign8678 5 ай бұрын
You can link one of their psychrometer probes to the outdoor dry bulb
@jroberts3428
@jroberts3428 4 ай бұрын
I've been flooding alot of compressors 😳
@markniles3013
@markniles3013 4 ай бұрын
We all do. Sometimes when your busy. Lol
@APHVAC0913
@APHVAC0913 5 ай бұрын
Great video 👌🏽
@wpl11972
@wpl11972 5 ай бұрын
I just use my valve core removal tool as my tee.
@emidiolopez1409
@emidiolopez1409 5 ай бұрын
So you remove the schrader valve to do SH or SC? Or what kind of removal tool do you use that has a press tool built in? Because the Appion that I use don’t have the press tool so I can’t take any risk of losing 5+ pounds of refrigerant by removing the schraders lol
@HVAC_Tips_Tricks_Calcs
@HVAC_Tips_Tricks_Calcs 5 ай бұрын
@@emidiolopez1409if your loosing 5 lbs with a core removal tool you’re using it wrong. How much refrigerant are you going to lose I’d the schrader doesn’t seal?
@emidiolopez1409
@emidiolopez1409 5 ай бұрын
@@HVAC_Tips_Tricks_Calcs Ive never said I’m losing 5 pounds by using the schrader removal tool. I said that’s just stupid if you have to remove the schrader valves every time you have to check the pressures on an AC, NO way I’m taking risks in losing factory refrigerant if something doesn’t goes bad with the removal tool.
@davidlopan6649
@davidlopan6649 5 ай бұрын
I can see myself pulling the pressure probes off the T and accidentally letting out all the refrigerant. lol definately would put a valve core on that for me.
@lorunner1213
@lorunner1213 5 ай бұрын
I use apion tee’s. They are low loss with schraders on both male ends of the tee. So doesn’t matter if you pull just the probe off. Or the tee with the probe.
@davidlopan6649
@davidlopan6649 5 ай бұрын
@@lorunner1213 Yeah I love appion tools. Just purchased their recovery machine. I didn't get probes yet probably next year.
@JuanJuarez-en5xn
@JuanJuarez-en5xn 5 ай бұрын
Where did you bought those T’s ?
@lorunner1213
@lorunner1213 5 ай бұрын
@@JuanJuarez-en5xnJohnstone Supply
@mtbbiker6401
@mtbbiker6401 5 ай бұрын
I don't understand how taking a low pressure (vapor line) reading at the condenser translates to the pressure in the evaporator. Why is it not industry standard to take low pressure (vapor line) reading at the evaporator?
@8799crosby
@8799crosby 5 ай бұрын
There is no ports at the evap .
@mtbbiker6401
@mtbbiker6401 5 ай бұрын
@@8799crosby So we are measuring total super heat temp using thermometer near the service port at the condenser (outdoor unit for heat pump) and measuring the pressure at the same service port to measure the temperature at the evaporator (indoor unit for heat pump). We measure pressure to convert to temperature. If we are measuring the temp and the pressure at the same spot, why don't the temp readings match? I'm trying to understand the physics behind this. Does it have to do due with saturation temp, sensible heat, latent heat?
@EricJohnson-dr5wb
@EricJohnson-dr5wb 5 ай бұрын
@@mtbbiker6401good question. The pressure on the low side is essentially the same in the evaporator as it is at the low side service port. The vast majority of the cooling is due to the liquid to vapor phase change in the evaporator coil. The additional heating of the 100% vapor is the superheat. You want there to be some superheat to prevent liquid refrigerant from entering and damaging the compressor.
@957543
@957543 4 ай бұрын
Because you want to be able to be in one spot
@globecomputers1
@globecomputers1 5 ай бұрын
Great video! Like always! Question can you provide a link for those AC test caps? I need to buy a set.
@HVAC_Tips_Tricks_Calcs
@HVAC_Tips_Tricks_Calcs 5 ай бұрын
Just take two spare caps and drill a hole in them.
@HVAC_Tips_Tricks_Calcs
@HVAC_Tips_Tricks_Calcs 5 ай бұрын
Although I’m sure sponsored, nice to see someone make a video that didn’t say you had to use MQ and True Flow or you’re a hack.
@tomaszpoznanski7584
@tomaszpoznanski7584 5 ай бұрын
Iam a contractor and would like to do a course/training for a/c contractor. Can you recommend any in NY/NJ/PA area? Any schols?
@pana5075
@pana5075 5 ай бұрын
Espero este video en español
@vonboldler5219
@vonboldler5219 5 ай бұрын
Hi mike!
@noname-cw5or
@noname-cw5or 4 ай бұрын
I thought this was a joke at first
@mikev.1034
@mikev.1034 5 ай бұрын
👍👍
@Mok-l5i
@Mok-l5i 5 ай бұрын
🙏🙏🙏🙏
@martinguzman4323
@martinguzman4323 5 ай бұрын
👍👍👍👍👍👍👍👍👍👍👍👍👍
@var8492
@var8492 5 ай бұрын
What if my liquid pressures are at 390 and suction 174 with a 11 t/s !??
@hazendismukesjr.8319
@hazendismukesjr.8319 5 ай бұрын
😂why didn't you use a charging orifice
@YankeesFan74
@YankeesFan74 5 ай бұрын
sadly most techs will hook up and immediately say it's good or needs refrigerant because companies are so focused on getting techs in and out as fast as possible. Most expect a complete diagnosis to be complete in 30 min max preferably less.
@TheRealDegen100
@TheRealDegen100 5 ай бұрын
Preferably way less but every call is different. Only calls that really take time is determination of why a part failed.
@kevinpearce3281
@kevinpearce3281 5 ай бұрын
Why can’t you put the r410a into the liquid side if it’s coming in as a liquid
@davidgochenour7072
@davidgochenour7072 5 ай бұрын
It would push refrigerant into your bottle
@camilo8cheryl
@camilo8cheryl 5 ай бұрын
High pressure
@FreonChugger
@FreonChugger 5 ай бұрын
The liquid side is at a high pressure while the system is running. Connecting the refrigerant jug to the suction line, which is a lower pressure, will suck the refrigerant into the system.
@wyattdekay7763
@wyattdekay7763 5 ай бұрын
Usually to much pressure
@boongoon92
@boongoon92 5 ай бұрын
It's leaving as a liquid
@snwsk8
@snwsk8 5 ай бұрын
Great tips as always, thank you
Checking the R-410A Refrigerant Charge! What to Watch Out For!
42:39
AC Service Tech LLC
Рет қаралды 98 М.
Air Conditioner Troubleshooting! Connecting, Measuring, Fixing, Disconnecting!
21:05
人是不能做到吗?#火影忍者 #家人  #佐助
00:20
火影忍者一家
Рет қаралды 20 МЛН
She made herself an ear of corn from his marmalade candies🌽🌽🌽
00:38
Valja & Maxim Family
Рет қаралды 18 МЛН
When you have a very capricious child 😂😘👍
00:16
Like Asiya
Рет қаралды 18 МЛН
Каха и дочка
00:28
К-Media
Рет қаралды 3,4 МЛН
HVAC 119 Charging with Wireless Probes
12:54
Love2HVAC with Ty Branaman
Рет қаралды 45 М.
Digital HVAC Gauges or Wireless Probes | Which should YOU buy??
17:00
Charging R-410A Refrigerant into an Air Conditioner! Pressures, Temps, Tips!
27:56
AC Service Tech LLC
Рет қаралды 1,5 МЛН
What A Rookie MISTAKE!! | HVAC Life
9:35
Quality HVACR
Рет қаралды 209 М.
How To Use AC Gauges
26:34
Benjamin Sahlstrom
Рет қаралды 1,2 МЛН
Explaining Superheat and Subcooling to Your Apprentice!
14:14
AC Service Tech LLC
Рет қаралды 644 М.
40 VACUUM PROCEDURE TIPS for HVAC Techs! Avoid Frustration and Save Time!
27:12
HVAC Tool Review | Fieldpiece SM480V
13:07
HVAC Tech Tips
Рет қаралды 57 М.
HVAC Silver Soldering vs Brazing vs Brazing While Flowing Nitrogen!
18:42
AC Service Tech LLC
Рет қаралды 109 М.
人是不能做到吗?#火影忍者 #家人  #佐助
00:20
火影忍者一家
Рет қаралды 20 МЛН