A step-by-step guide on how to size AHU cooling coil from sensible cooling load to calculating the AHU airflow, identifying the on/off coil conditions and finding the on/off coil enthalpy for coil load calculation.
Пікірлер: 16
@aircondlounge7 ай бұрын
Understanding cooling coil design helps us to not only size AHU appropriately but also have the skills to troubleshoot many air conditioning problems. Learn more in my Psychrometric Analysis Course: course.aircondlounge.com/psychrometric-analysis-course Cooling load calculation: course.aircondlounge.com/rts-cooling-load-calculation-course
@GalacticAdventures694 күн бұрын
My goodness dude, you saved my ass at work. Will be buying your courses as well. You the man!
@aircondlounge4 күн бұрын
Is it? How that happened. Anyway, thanks.
@sinunlinu15 күн бұрын
Awesome I m from India very good explanation.😊
@aircondlounge13 күн бұрын
Thanks
@vanzproject9378Ай бұрын
Im from indonesia , thanks sir you are amazing ,
@aircondloungeАй бұрын
It’s nice to meet you!
@sadeghnaderi412929 күн бұрын
@aircondlounge if your AHU is CAV you can add sensible heat to get total sensible heat. if AHU is VAV then you can nod add the max of each zone sensible heat together
@aircondlounge29 күн бұрын
For VAV AHU, you should apply a diversity factor to the total sensible heat you mean?
@sadeghnaderi412927 күн бұрын
@@aircondlounge you should calculate total sensible load of all zones hourly to find the worst scenario with highest load, not just add the load of each zones together. because they can not occur at the same time to add them together
@aircondlounge27 күн бұрын
For load calculation yes. However, if those zones are serve by one AHU, adding the max load at each zone at different hour will lead to oversizing because when one zone is at max load, it doesn’t necessarily means the other zones are at max load as well. So, sum up the load by the same hour and choose the highest one should be the optimal approach.
@sadeghnaderi412927 күн бұрын
@@aircondlounge yes thats what I mean. So you select the hour with highest load?
@aircondlounge27 күн бұрын
Because this video is about coil sizing, the sensible loads are just an example. In load calculation, I do calculate by hourly and pick the highest load hour.
@user-jw7gh5py3v5 ай бұрын
Where can i get the copy for psychometric chart same as what you use in the video?
@aircondlounge5 ай бұрын
It is extracted from the ASHRAE Handbook. You may try google it though.