Air Compressor keeps tripping out circuit breaker.. how to fix this problem

  Рет қаралды 13,493

Micks Mowers The Mower Man

Micks Mowers The Mower Man

Күн бұрын

Hi and welcome to Micks Mowers
In this Video I have a new Air Compressor that keeps tripping out the circuit breaker.. in this how to fix video I will show you what the problem is and how to fix it.
Micks Mowers Merchandise UK Store below
micksmowersthe...
Micks Mowers Merchandise USA Store below
micks-mowers-u...
Here is my channel wish list if you would like to show some support in purchasing some tools or spare parts, it is gratefully appreciated www.amazon.co....
TOOLS I USE -
Oil Extraction pump amzn.to/2UBApDI
Fan Blade Bulb amzn.to/39BLI4a
Blade removel tool amzn.to/3nxBVQj
Micro Drill Bits amzn.to/36Jpv0R
Carb Cleaning Files amzn.to/3lH8ESx
Hex Shank Extension Drill Bits Bar Set 1/4" 3/8" 1/2" amzn.to/3oFKHx9
Dewalt DCF887M1- Impact Driver, amzn.to/3oEVcjZ
Lawnmower Rotary Blade Balancer amzn.to/3e6UOWN
Rode WIGO Wireless GO Wireless Microphone amzn.to/2JlRlIN
Neewer 176 LED Light amzn.to/2HaubnJ
Universal Style, Mower Deck clamp for blades amzn.to/31PKygE
Briggs & Stratton Diaphragm and Gasket set amzn.to/3kF8Y3H
GT SONIC 3L Ultrasonic Cleaner amzn.to/2TDdVy9
VEVOR 3L Ultrasonic Cleaner amzn.to/2Gb3PBJ
Stainless Steel Strainer for carb jets in a cleaner amzn.to/3e6CxJ2
Please follow me for more channel updates
Instagram www.instagram....
Twitter mi...
Banjo Hop by Audionautix is licensed under a Creative Commons Attribution license (creativecommon...)
Artist: audionautix.com/
Disclaimer: My Videos are for information only- i am not a professional or repair shop im just someone in a shed enjoying a hobby- If you choose to try one of the suggestions made in my videos, you do so at your own risk. No information contained in this video shall create any express or implied warranty or guarantee of any kind. Any injury, damage or loss that may result from the improper use of tools, equipment or information contained in this video is the sole responsibility of the viewer and not Micks Mowers The Mower Man.THE SIGNS IN THE BACKGROUND ARE FOR DISPLAY PURPOSES ONLY.I HAVE NO AFFILIATION WITH THEM AND I CONFIRM I AM NOT A MAIN DEALER OF SAID COMPANIES I HAVE PERMISSION TO USE THEM

Пікірлер: 55
@themowerman
@themowerman 11 ай бұрын
Here is my channel wish list if you would like to show some support in purchasing some tools or spare parts, it is gratefully appreciated www.amazon.co.uk/hz/wishlist/ls/13BO7QKGAZZV2/ref=nav_wishlist_lists_2?_encoding=UTF8&type=wishlist
@bofor3948
@bofor3948 11 ай бұрын
Hi Mick, unless you were adding to an existing load on the breaker i.e. lights, cooling fans, tools etc. and you exceeded the breaker rating, this should not have happened. If it was only the compressor switched on, then this could be caused by what is known as inrush current. High reactance loads like big transformers, motors and capacative (condensor) loads will pull higher current for milliseconds at startup. You have found a solution but SGS should be notified. If that compressor is rated at 13A and expected to run on domestic mains they should modify the equipment by adding an inrush current limiter device. Your sparks has added a similar device to your supply board, but the equipment should run at the notified rated current without tripping existing circuits. If you had that compressor in your van and you were mobile doing repairs, you wouldn't expect customers to have uprated mains RCD's
@themowerman
@themowerman 11 ай бұрын
That's a good point...
@davidcarlisle3384
@davidcarlisle3384 11 ай бұрын
Good advice about the startup current spike. Also, if you need air farther away,it is better to get a longer hose than to use an extension cord. 😊
@themowerman
@themowerman 11 ай бұрын
Good advice mate
@alandykes2519
@alandykes2519 11 ай бұрын
Great to see you have got it all up and running now Mick 👍👍👍👍
@markcreeney-if7rr
@markcreeney-if7rr 11 ай бұрын
I used to be an electrician in a previous life. I put my garage on a ring main as providing your incoming cable is big enough you can get away with 32 amp breaker. If your incoming cable is say 2.5 mm and a distance from the house I would be a little wary of using 32 amp. I would do what you have done and put the compressor on a separate 20amp breaker but make it a close as possible to the consumer unit so only a short cable run. Never keen on a 20 breaker on the end of a run of sockets even if in theory it is ok. For me as long as you have the correct breaker protecting your underground cable to your outbuilding you won’t go far wrong as it will protect everything. But good video as many people will think they have a faulty compressor. Also got my grey cells working and brought back memories when I was on the tools.
@themowerman
@themowerman 11 ай бұрын
Thanks for watching.. yes I'm got to add a stocket just for the compressor.. the others are on a ring main...
@wrxs1781
@wrxs1781 11 ай бұрын
Good video Mick, and glad to see the compressor issue resolved. Not familiar with the UK electrical code but, we size the breaker to the wire gage and also the wire run distance, longer the run the larger the wire gage, they have line loss charts on line.
@ianharvey868
@ianharvey868 11 ай бұрын
It's the same here in the UK, we use a physical size not like a gauge rating, so we would use 1.5mm(sq) cable for lights and 10mm(sq) cable for showers etc. We also take in consideration if the wire is also embedded in insulation or in conduit vs open air over the length for thickness and protection rating
@Turningwrenches85
@Turningwrenches85 10 ай бұрын
Glad it was able to be fix there mick with the bigger Amp to allow the initial startup
@themowerman
@themowerman 10 ай бұрын
It's running great...
@liljoeii6091
@liljoeii6091 11 ай бұрын
Yeah, do the same thing you did. I got a better breaker in there. An it don't pop the breakers anymore. Thank you for the video
@themowerman
@themowerman 11 ай бұрын
Fantastic...
@fixitorstripitGardenmachines
@fixitorstripitGardenmachines 11 ай бұрын
I don't have that problem with my baby air compresor. Interesting video and very helpfull for people who upgrade.
@themowerman
@themowerman 11 ай бұрын
Thanks mate
@GuysPlayingWithTools
@GuysPlayingWithTools 11 ай бұрын
I have slow blow circuit breakers on mine, works like a charm. 🙂
@derrasenmaher9730
@derrasenmaher9730 11 ай бұрын
Nice and it just purrs away 👍🏻 Great Setup Mick
@themowerman
@themowerman 11 ай бұрын
Thanks mate
@stevoj8959
@stevoj8959 11 ай бұрын
That is a nice compressor. At 14 CFM you could run a spry gun with that. I can see why you will need at least 20 amps to run it. On a cold day it may need more. Nice set up Mick. Stevo
@HobbyMotorDK
@HobbyMotorDK 11 ай бұрын
Funny - I had the same issue with my hydraulic, remote comtrolled, totally awesome, in floor lift table 🙂
@dnrsmallenginerepair
@dnrsmallenginerepair 11 ай бұрын
Good fix my friend
@Dstromb232
@Dstromb232 11 ай бұрын
I use a surge protection Eliminate Surges, Spikes. Some compressors depending the size when at first start it uses its full amps to power up then drops off .
@petefroud5308
@petefroud5308 11 ай бұрын
Good job better safe than sorry.
@themowerman
@themowerman 11 ай бұрын
Yes mate
@ianharvey868
@ianharvey868 11 ай бұрын
Could be a few things, what I don't get is the fuse in the 13a plug didn't blow first as that is less than the 16a mcb/rcd, this to me means its probably a faulty mcb/rcd in reaction time, most are a "c16 b" so it's a bit slower and should trip around 50a at a few microseconds and as the video says the varient " C" is even slower. What concern me in this video he says his cables are rated for 20a, so the mcb in the house should be a 16a to protect the cable going to the shed, this is because the mcb/rcd/fuse won't blow at 16a but around 1.3times that (20.8amp) is where it will trip, if he has a 20amp fuse or mcb in the house that will trip/open circuit at 26amps, so his 32amp mcb/rcd in the shed is technically "no protection" at that actual point, however if the mcb/rcd in the house is a 32amp then that's a problem, as this won't trip until like 40amps which as he said his cable is only rated for 20amps, this can make that long cable a large resistive wire heating up and may cause a fire before a direct short-circuit happens then tripping the mcb/rcd. I'm no qualified electrician but fuses, mcb, rcd, rcbo's etc are designed to protect the wires not the equipment, I have something called common sense when doing research. So that being said what in my opinion should have been done is exchanged the "c16b" for a "c16c or d" this protection for short circuit of upto 20amps at his shed keeping his wires going to the house safe too
@johne8379
@johne8379 9 ай бұрын
Now you’ve had the air compressor for awhile. How are you getting on with it?
@themowerman
@themowerman 9 ай бұрын
It's perfect...
@Johnny16781
@Johnny16781 11 ай бұрын
Good one again Mick
@themowerman
@themowerman 11 ай бұрын
Thanks mate
@ashleystringer7531
@ashleystringer7531 11 ай бұрын
First of all it doesn't matter whether your sockets are connected A16 amp breaker that will not work all sockets are 13 amp but if that compressor says runs off 13 amp it should run off 13 amp if not it's fake advertisement I've had this problem before with my compressors you will need a 16 amp surpply and a breaker are they 16 amp Plug any compressor what's over 50 l will need a 16 amp supply my name is Ashley I like your channel as .
@knighthawk86855
@knighthawk86855 11 ай бұрын
I wired all my compressors with a dedicated circuit, hard wired in thier own box. they all have a their own wire, and in house circut breaker 30amp....and I never run more then one at a time.
@dallasgarner1990
@dallasgarner1990 11 ай бұрын
It would be best to put a socket right next to your compressor mick.
@themowerman
@themowerman 11 ай бұрын
Yeah I think I will do that ...
@motorcoachtech7615
@motorcoachtech7615 11 ай бұрын
Mick, Is the voltage in the shed 240v?
@themowerman
@themowerman 11 ай бұрын
Yes mate
@MrGWN7
@MrGWN7 11 ай бұрын
Capacitor can be weak, even new. The breaker in the panel can be weak. Have someone test the draw on both. Replace what is needed.
@matthewharmer1656
@matthewharmer1656 11 ай бұрын
Just change the b type to c type rcds??
@matthewharmer1656
@matthewharmer1656 11 ай бұрын
C type have a better trip curve designed for motors with a high in rush of current.
@robertmailhos8159
@robertmailhos8159 11 ай бұрын
How 2 amps are causing the breaker to trip 😮
@themowerman
@themowerman 11 ай бұрын
It's the first start up.. pushing it over 16amps...
@robertmailhos8159
@robertmailhos8159 11 ай бұрын
@@themowerman that is the truth about that matter thing is different types of electric motors require different amps at start up depending on the horsepower of the motor
@KensSmallEngineRepair
@KensSmallEngineRepair 11 ай бұрын
Sparky? I thought that meant something else!!
@themowerman
@themowerman 11 ай бұрын
Like what ken.. please explain 🤔
@paulacabbo466
@paulacabbo466 4 ай бұрын
Sorry I couldn't watch this inordinately long video for a simple fix
@themowerman
@themowerman 4 ай бұрын
Ok but thanks for the comment
@johnobiro5202
@johnobiro5202 11 ай бұрын
Shocking that Mick. You can plug your Jack Hammer in now. 👍🔧
@themowerman
@themowerman 11 ай бұрын
Lol will do mate
@outkast187
@outkast187 6 ай бұрын
Holy hell, get to the point. No need for a 13 minute video for a 13 second explanation.
@themowerman
@themowerman 6 ай бұрын
Did you watch it all.. ?
@themowerman
@themowerman 11 ай бұрын
Micks Mowers Merchandise UK Store below micksmowersthemowerman.myspreadshop.co.uk/men?q=D1 Micks Mowers Merchandise USA Store below micks-mowers-usa.myspreadshop.com/all
@jimlepeu577
@jimlepeu577 11 ай бұрын
Personally I wudda put in a 30a breaker to ensure I was giving it a margin. Better too much than too little or bare enuf - not much difference in the price.
@themowerman
@themowerman 11 ай бұрын
Like I said.. I'm not a professional.. however my electrician is...
@michaelbarkham6064
@michaelbarkham6064 11 ай бұрын
Please nobody take this guys advice. How do you know the current carrying capacity of the cable is rated for 30a?? Leave it to the experts 😉
@themowerman
@themowerman 11 ай бұрын
TOOLS I USE - Oil Extraction pump amzn.to/2UBApDI Fan Blade Bulb amzn.to/39BLI4a Blade removel tool amzn.to/3nxBVQj Micro Drill Bits amzn.to/36Jpv0R Carb Cleaning Files amzn.to/3lH8ESx Hex Shank Extension Drill Bits Bar Set 1/4" 3/8" 1/2" amzn.to/3oFKHx9 Dewalt DCF887M1- Impact Driver, amzn.to/3oEVcjZ Lawnmower Rotary Blade Balancer amzn.to/3e6UOWN Rode WIGO Wireless GO Wireless Microphone amzn.to/2JlRlIN Neewer 176 LED Light amzn.to/2HaubnJ Universal Style, Mower Deck clamp for blades amzn.to/31PKygE Briggs & Stratton Diaphragm and Gasket set amzn.to/3kF8Y3H GT SONIC 3L Ultrasonic Cleaner amzn.to/2TDdVy9 VEVOR 3L Ultrasonic Cleaner amzn.to/2Gb3PBJ Stainless Steel Strainer for carb jets in a cleaner amzn.to/3e6CxJ2
Why Does My Air Conditioner Breaker Keep Tripping?
14:21
Taddy Digest
Рет қаралды 12 М.
Air Conditioner Keeps Tripping Breaker... Stop Resetting it!
25:37
HVACR Survival
Рет қаралды 32 М.
Yum 😋 cotton candy 🍭
00:18
Nadir Show
Рет қаралды 7 МЛН
WORLD'S SHORTEST WOMAN
00:58
Stokes Twins
Рет қаралды 210 МЛН
Joker can't swim!#joker #shorts
00:46
Untitled Joker
Рет қаралды 40 МЛН
3 Reasons Your Circuit Breaker Keeps Tripping
4:19
Arnold Electric Services
Рет қаралды 366 М.
AC Keeps Tripping Breaker and The 10 Most Common Reasons Why
12:45
Word of Advice TV
Рет қаралды 541 М.
What is a Lost Neutral? Lost Neutrals demonstrated.
12:21
Morgan Inspection Services
Рет қаралды 19 М.
Pool Pump Tripping breaker and troubleshoot
4:41
Lance Dammeyer
Рет қаралды 72 М.
Why does my Compressor trip my circuit breaker? FIXED?
14:17
Paisteboy
Рет қаралды 25 М.
Capacitor and Hard Start Myths Busted
28:41
HVAC School
Рет қаралды 228 М.
Troubleshooting Craftsman Air Compressor 30 Gallon 6HP| Tripping Breakers
15:15
Air compressor pressure switch fail and fix. Kobalt/Lowe's
19:19
Jo Daddy's Workshop
Рет қаралды 111 М.
Yum 😋 cotton candy 🍭
00:18
Nadir Show
Рет қаралды 7 МЛН