Love that you used one meter to measure voltage and another to measure amps simultaneously. I always recommend that techs have at least two meters at all times!
@acservicetechchannel3 жыл бұрын
Good call!
@HCheatNcool3 жыл бұрын
This type of stuff helps me out more than anything as a new technician. Helping me think about weird things that could happen and beat in my head the operating principles of the unit and the electricity
@bill9443 жыл бұрын
Sound information here! Isolation of components and equipment is essential in many cases for proper troubleshooting. Nicely done. This particular problem is also missed when technicians are checking voltage at a single pole contactor. The voltage will backfeed through the unit. Between ground and each leg of power you'll get 120V but if you measure between each incoming leg at the contactor you get 0V.
@MrChipBryant3 жыл бұрын
Very good information. Thank you for your many contributions to our industry!
@acservicetechchannel3 жыл бұрын
Thanks for watching!
@andresbarragan85952 ай бұрын
FROM CHICAGO EXELENT VIDEO THANK YOU SO MUCH
@jameswasher39383 жыл бұрын
Just wondering where that white wire turned red. Did you find the white wire in the air handlers disconnect?
@LRBennettInc3 жыл бұрын
Using red electrical tape wrapped on the white wire is a designation of power and should always be done regardless of the obvious 2 pole breaker. But i do like your observation of increasing that breaker if the wire is correct. The panel breaker does tend to be the issue on most of our voltage issues to the unit but rarely when it's oversized correctly and can only be done when you have a fused disconnect or breaker at the AH. AH breaker is the important one. The OHM to ground is good stuff. Thanks for the video these really help passing around good information.
@deanmartin19663 жыл бұрын
Great info thanks for sharing your knowledge
@acservicetechchannel3 жыл бұрын
Glad it was helpful!
@kingjames7929 Жыл бұрын
I'm having a same issue but I do have 120 to each leg to ground. So I'm confused at this point, can you help me out?
@Eddy633 жыл бұрын
Great info Craig ...
@acservicetechchannel3 жыл бұрын
Glad you enjoyed it
@michaelchiang65953 жыл бұрын
I appreciate you and your videos. So helpful. I’ve been out of the treads for a while and I’ve been looking for a way to refresh my memory and I have to tell ya that your videos are perfect. Thanks you so much.
@acservicetechchannel3 жыл бұрын
That is really awesome to hear Michael!
@CoolerQ3 жыл бұрын
It would be really interesting to see the inside of the failed breaker if you still have it. Or send it to someone like bigclive to tear down.
@morganexoticmastiffllc14033 жыл бұрын
Thanks 🙏🏾 needed to know that. I will like an share!!!
@Ted_E_Bear3 жыл бұрын
Information is great. !!
@acservicetechchannel3 жыл бұрын
Glad you think so!
@BagelBoard2 жыл бұрын
I love your videos. My problem is that my air handler goes on, but then shuts off after 5-10 mins. Then it comes on again but shuts off again. What do you think is the issue ?
@jerrygolden17572 жыл бұрын
What type of breaker is that in that unit? I have been looking for some like that, but havent found any yet. where can i order some?
@oscarcastellanos92703 жыл бұрын
Where do I get a replacement breaker since mine went bad? Mine is identical to the one on this video but Lowes and Home Depot don't seem to carry it?
@DavidHernandez-gt9bo3 жыл бұрын
Good videos !!! Great troubleshooting skills .
@acservicetechchannel3 жыл бұрын
Glad you enjoyed it
@AlbertHariaz-np8uk Жыл бұрын
What kind of cable can I use for an air controller without a control board?
@rolandovargas51493 жыл бұрын
4:12 the white wire has to be marked with a black or red mark to identify it as a hot wire el cable blanco tiene que marcarse con una marca negra o rojo para identificarlo como un alambre calient
@edypanama72213 жыл бұрын
Thank you Good video 👍
@acservicetechchannel3 жыл бұрын
Glad you enjoyed it
@zekenzy64863 жыл бұрын
Great Video. Have A nice Weekend. Thank you for sharing ^_^
@acservicetechchannel3 жыл бұрын
Thank you! You too!
@MiguelPerez-jf3tf3 жыл бұрын
I have a question on how do I add a heat pump to the system , removing the heat strip because its not heating enough for the client and were happier when they had a heat pump before
@tristanwilson25602 жыл бұрын
Have you had a problem with having 120v on both legs to ground but when you measure from L1 to L2 you only get around 50v? It’s stumping me
@Achabab3 жыл бұрын
great jobs 👍
@acservicetechchannel3 жыл бұрын
Thanks for the visit
@800blake3 жыл бұрын
Had a similar problem recently was at a job with a leg out coming into the condenser disconnect and something that had me scratching my head, on the leg with 120 across the line and load side of the open disconnect I was only getting a bit over half the voltage drop of like 75 volts but the output side still had 0 volts to ground like I'd expect with a full voltage drop super weird.
@dalebrenchley33113 жыл бұрын
So confused. My handler worked perfectly and suddenly won’t power on. My dog knocked the drain pipe that includes the shut-off float next to it. The float wire may have got tugged. I’ve turned breakers on n off and same with outside unit. Any ideas spring to mind?
@CHOMAHOMA3 жыл бұрын
Thank you for your video. I appreciate it. One question, what do you think is the best way to study the sequence of operation of a particular unit?
@bill9443 жыл бұрын
I've found that the manufacturers' installation manual is best. This will eliminate, what are typically minor, differences between different manufacturers and different models and will inform you of jumper or dip switch settings that can change the operational characteristics of the equipment. Also, important to know what thermostat is being used and the specific installer settings that have been programmed such as "comfort" settings vs. "normal" settings.
@CHOMAHOMA3 жыл бұрын
@@bill944 Thank you.
@rosscourtney99133 жыл бұрын
It can be red or black in my area. I can't remember but I believe their may be a third color also it can be. Obviously talking about the power wire color but nice vid!!! I've ran into the same issue with an od unit but was something in the disconnect ultimately if I remember right.
@grecomsiri15323 жыл бұрын
Beautiful
@acservicetechchannel3 жыл бұрын
Thank you
@donnierobertson30883 жыл бұрын
Nice video
@acservicetechchannel3 жыл бұрын
Very nice
@brianb57793 жыл бұрын
Thanks for the info, def learned something.
@acservicetechchannel3 жыл бұрын
Glad it was helpful!
@ericgateway Жыл бұрын
can you please help the way forward. Machine came on correctly. but the only problem is not blowing the bottle
@clevc1123 жыл бұрын
Could the homeowners replace their own breaker to save money on an electrician if they know It's the issue? I replace mine and I'm not a licensed electrician.
@OcRefrig3 жыл бұрын
Good video ! in California we are allowed to install a Breaker and pull power to our Hvacr equiptment. To everyone else Check Your state for Local Laws. White Wires in an electrical panel should NEVER be used as a Power Wire attached to a breaker. White wires should only be used as a Neutral wire & should ONLY BE attached to a Neutral bar. Green wires Should ONLY be used as Ground wires. Colored wires are used for Power & attached to breakers. Follow these rules and everyone WILL be a lot safer.
@michaelcostello69913 жыл бұрын
Thanks
@anthonylumar59843 жыл бұрын
Wat if it's a terminal block? I read 240v coming to the unit but not through the terminal. 🤷🏾♂️
@jeffreyhill39608 ай бұрын
Some ware in the feed circuit the wire goes from white to red, obviously a splice somewhere….hmmmmm.
@ericgateway Жыл бұрын
I have a problem. the bottle is not blowing
@fredrejouis30182 ай бұрын
Well I have a issue air handler fuse keep blown up on me
@Bluecollarrebel3 жыл бұрын
🔥🔥🔥🔥🔥
@1martinontherocks3 жыл бұрын
thats stupid not to allowed an hvac guy to change a breaker, ill change the whole panel if i have to.
@OcRefrig3 жыл бұрын
in California we are allowed to install a Breaker and pull power to our Hvacr equiptment. Check Your state for Local Laws.
@Froggability3 жыл бұрын
An hvac tech who isn't a licensed electrician? I feel sorry for these guys unable to do the whole job
@clevc1123 жыл бұрын
@James Kepley you should become a doctor too in case someone gets hurt where you are working.
@rickychavez14733 жыл бұрын
👍👍👍
@eliezerrivera87643 жыл бұрын
Well the guy with the meter at the main braker doesn't have at list gloves on his hands for protection
@adamcraig15683 жыл бұрын
No one cares
@ericgateway Жыл бұрын
it's a brane new machine
@scottieholland64864 ай бұрын
So if no amps are coming on when breaker is on does that mean it's bad?