Brand new evaporator coil with a restriction?

  Рет қаралды 10,501

Ulises Palacios

Ulises Palacios

Күн бұрын

Пікірлер: 55
@dizziedallas
@dizziedallas 7 жыл бұрын
Thank you for taking the time to make the video and showing the problem.
@OcRefrig
@OcRefrig 7 жыл бұрын
👍👍
@OcRefrig
@OcRefrig 7 жыл бұрын
Wow, Great video Ulises !!! U the Man ulises ! I Been doing this 36 Years and have never seen this until now.
@JuanMendoza-sp5vt
@JuanMendoza-sp5vt 5 жыл бұрын
Quick question I have a heat pump and the evaporator coil is completely frozen and the suction line valve outside has barely any pressure have u had that happened?
@raulmoreno3108
@raulmoreno3108 4 жыл бұрын
Hi ulises, I'm Raul, from hermosillo, mexico. HVAC & R technitian, I never seen something like that, thank you for you videos. Grettinngs
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Gracias.
@davidharmon8745
@davidharmon8745 3 жыл бұрын
Love watching your videos. Have a save new years.God Bless
@UlisesPalacios
@UlisesPalacios 3 жыл бұрын
Likewise. I appreciate it.
@tonynewswanger5759
@tonynewswanger5759 4 жыл бұрын
Nice video, I’m having a similar issue on a 2 week old Goodman. I’m going to back and test it the way you did, thanks!
@polishtheturdmickelson5473
@polishtheturdmickelson5473 7 жыл бұрын
Nice find Ulises, in hind sight when you pressure tested it out on the floor. It seem to pressurize really fast, because you were only pressurizing 1/2 of the coil. 4 pm on a Friday made coil. I hope you get the labor covered.
@OcRefrig
@OcRefrig 7 жыл бұрын
Yea, they Definately owe him many hours for labor. For sure thier fault. I hope he sends them a bill for at least a days labor.
@fighkb
@fighkb 5 жыл бұрын
👍🏻thank you for sharing, good catch
@theairconditioningguy
@theairconditioningguy 7 жыл бұрын
Wow! Guess I'll have to check them from now on. What brand was it?
@jonhvac
@jonhvac 7 жыл бұрын
Wow! Put you through so much unnecessary heart ache. At least you cought the 2nd one...third one is a charm😂 What brand coil?
@NorCal-refrigeration
@NorCal-refrigeration 7 жыл бұрын
What a mess. Quality control? Lol
@justin0957
@justin0957 7 жыл бұрын
If it fits it ships!
@joeshearer1247
@joeshearer1247 4 жыл бұрын
I know this is three years old now but it popped up in my feed and I believe the two u bends at top of apex should be rotated 90 degrees
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Yup. That’s correct Joe. Can you believe they gave me two coils like that. Fool me once shame on me lol. I definitely checked the second one.
@texasstarniles5
@texasstarniles5 7 жыл бұрын
What a Great Video Ulises Some Manufactures use the customers as there Research and Development !!
@savagetampa4112
@savagetampa4112 4 жыл бұрын
Damn 390 psi of nitrogen? What’s the tonnage, 4/5 ton unit? You ain’t scared about fittings, LP/HP switches blowing or leaking after the pressure test.
@savagetampa4112
@savagetampa4112 4 жыл бұрын
Will say that you actually are doing better than most techs and not just doing nothing. Or using a digital leak detector. I’d assume you’re using soapy bubbles tho with nitrogen
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Savage Tampa yeah it was probably a little too much. Usually I’ll go to 150 max. Unless it’s a vrf system. They recommend 600 psi nitrogen test.
@ebaum1000
@ebaum1000 5 жыл бұрын
I have had a lot of issues with brand new Lennox systems. Especially on commercial. Never seen this before so it’s just the icing on the cake. I avoid Lennox at all costs. The equipment is not the problem it’s the quality control. They have warranty and compatibility issues on top of that. We installed 12 rtu’s on one building literally 4 of them had issues. 2 were electrical and the other 2 were out of refrigerant due to joints not being brazed all the way, all Lennox. Yet it Says they were pressure tested. Total joke and waist of time.
@HVACRSurvival
@HVACRSurvival 6 жыл бұрын
WoW, what brand is that? That's a first for me, glad you shared it, I'll keep that in mind for later.
@UlisesPalacios
@UlisesPalacios 6 жыл бұрын
Lennox. Always triple check lol
@HVACRSurvival
@HVACRSurvival 6 жыл бұрын
I used to work for a Lennox Premier dealer.... why does this not surprise me LOL
@ebaum1000
@ebaum1000 5 жыл бұрын
Lennox? Stay away.
@ConservTab-sv3kx
@ConservTab-sv3kx 6 жыл бұрын
this would happen to me on my first day with a new company
@jcbecker28
@jcbecker28 7 жыл бұрын
Lennox coils? I have never seen that issue before.
@joshua-the-seer8494
@joshua-the-seer8494 2 жыл бұрын
Might be oil-logged Evaporator coil... Read up on that.. I'm having similar issue.
@mrcrux213
@mrcrux213 3 жыл бұрын
one time I had one of the capillar tube restrict it .
@pincheburro956
@pincheburro956 6 жыл бұрын
Wow, nice find
@EightiesTV
@EightiesTV 5 жыл бұрын
Imagine how many of these were sent out wrong because one idiot on the assembly line thought it didn't matter what way they went on. One bad $16/hr worker can cost you $100,000 in damages in one day and have ZERO liability themselves.
@UlisesPalacios
@UlisesPalacios 5 жыл бұрын
EightiesTV yup. I had a meeting with a Lennox engineer and Luckily they only had 7 coils of that batch shipped out. It’s an older coil so not to many.
@heavydiesel
@heavydiesel 7 жыл бұрын
I bet they've but the u bends in the wrong place so theres no circuit to flow through.
@heavydiesel
@heavydiesel 7 жыл бұрын
Haha teach me to comment before end of vid!
@throttlebottle5906
@throttlebottle5906 7 жыл бұрын
could be or the small/cap tubes slipped back and one or all partial plugged with brazing, or they didn't blow out shavings and debris?
@UlisesPalacios
@UlisesPalacios 7 жыл бұрын
heavydiesel lol yes sir. They had a rep come look at the coil with me. They had a few that where wrong
@UlisesPalacios
@UlisesPalacios 7 жыл бұрын
throttle bottle I took it completely apart. I thought that was my problem at first.
@throttlebottle5906
@throttlebottle5906 7 жыл бұрын
yeah, I'm guilty of commenting before watching whole video LOL! and I figured QC would have caught such obvious flaws, then again, I recall the QC at every factory I worked at, Quality Control was and is the installers and worst yet consumers :))
@KungFuMaintenance
@KungFuMaintenance 7 жыл бұрын
Yikes! That stucks!!
@sjefoekel6058
@sjefoekel6058 7 жыл бұрын
Usualy the distributor is soldered shut wi t h flux
@notanewbie1718
@notanewbie1718 7 жыл бұрын
At least she's not a leaker! lol
@OcRefrig
@OcRefrig 7 жыл бұрын
Lol.
@throttlebottle5906
@throttlebottle5906 7 жыл бұрын
ohh, since you think/know it;s bad, put water through it backwards and see if any of the 4 cap/small tubes has no flow, that would show you which line was plugged anyway. or better yet a smoke machine if you have one :) and never-mind that, I didnt watch whole vide before flapping my gums :))) busted!!!!! but busy so lol...
@5822huron
@5822huron 6 жыл бұрын
Ubends! Factory defect
@aircooledtx
@aircooledtx 7 жыл бұрын
Wow,ate allot of time on their dime.Warranty 4 hours per coil.
@throttlebottle5906
@throttlebottle5906 7 жыл бұрын
probably nobody wanting to do the factory work for peanut pay, so they're using temp services and the folks are brain baked on drugs. drug testing does no good as they all clean up enough to pass initial testing, then go off the rails. I did lots of night shift temp service work for extra $$$ in the 90's and early 2k's, not a place one didn't want me back or try to hire me within the first two days, I always declined :) this seems to be the most likely scenario >_>
@fattboy42
@fattboy42 7 жыл бұрын
wow, nice find.
HVAC 106 Scenario Restriction and non-condensable
14:02
Love2HVAC with Ty Branaman
Рет қаралды 29 М.
HVAC Brazing In The Evaporator Coil, Filter Drier 🔥
12:37
AC Service Tech LLC
Рет қаралды 102 М.
Как мы играем в игры 😂
00:20
МЯТНАЯ ФАНТА
Рет қаралды 3,4 МЛН
Synyptas 4 | Жігіттер сынып қалды| 3 Bolim
19:27
How To Get Married:   #short
00:22
Jin and Hattie
Рет қаралды 29 МЛН
Evaporator 101
10:20
HVAC School
Рет қаралды 254 М.
What happens when a compressor tries to pump liquid
21:23
Ulises Palacios
Рет қаралды 25 М.
HVAC 089 fixed orifice piston closer look inside
6:03
Love2HVAC with Ty Branaman
Рет қаралды 48 М.
How To Properly Clean An AC Evaporator Coil & Save HUNDREDS!
15:33
The DIY HVAC Guy
Рет қаралды 1,3 МЛН
DO NOT buy an ac with Microchannel coils
18:36
Bbernhardsr
Рет қаралды 3,3 М.
troubleshooting sealed system
6:38
O Torres
Рет қаралды 14 М.
HVAC Scam Rip Off told customer furnace heat exchanger cracked
5:52
Anti DIY HVAC
Рет қаралды 297 М.
Why Does The Evaporator Coil Freeze (And How to Diagnose It)
8:31
HVAC School
Рет қаралды 563 М.
We convert 16 chainsaws into an engine for a car
11:50
Garage 54
Рет қаралды 209 М.
Как мы играем в игры 😂
00:20
МЯТНАЯ ФАНТА
Рет қаралды 3,4 МЛН