Carrier CLO (Current or Compressor Lock Out Board) explained.

  Рет қаралды 36,737

SLC TECH

SLC TECH

Күн бұрын

Пікірлер: 47
@destronger5313
@destronger5313 4 ай бұрын
Great video. On some of the (older?) carrier units these are in, the larger Carlyle compressors have a internal protector in 24v series with the LP, HP, FP.
@megabadass30
@megabadass30 5 жыл бұрын
Thank you, this video is great, and the diagram being drawn out is absolutely amazing, so helpful
@rkinnett
@rkinnett Жыл бұрын
This made my day. Thanks for your very clear explanation.
@elcrazy8017
@elcrazy8017 8 жыл бұрын
Thanks a lot SLC tech for clarifying things for me. Never knew how it actually worked. Great teacher!
@arthouston7361
@arthouston7361 6 жыл бұрын
Hi, SLC. TB here. The most frequent cause of the CLO locking out the compressor is when the LP switch opens during a low ambient startup on units without a working economizer. Carrier had a timer kit that could be installed to bridge the LP switch until pressures could rise enough that the LP would stay closed. We found we could make our own bypass. Of course, I have found the compressor conductor removed from the sensing loop and terminals 2 and 3 jumpered together by others... which is not the right approach to that issue. When they place that jumper, they lose the protection the safeties provide, including the HP switch and the freeze stat. The purpose of the board is to not allow the contactor to ride on the safeties, opening and closing repeatedly when there is a problem. This way, the tech can know that an issue exists, and then investigate the issue, and the contactor can have a much longer lifespan, along with the compressor. That's a very good explanation of the way it works, too.
@slctech3432
@slctech3432 6 жыл бұрын
Thanks TB. Hope all is well with you, loving my new gig in the private industrial side of things.
@russellkelley2737
@russellkelley2737 7 ай бұрын
Thanks for sharing this information it really helped me understand what is happening to the unit I am working on
@wannis100
@wannis100 Жыл бұрын
Hello SLC Tech Yesterday I was working on one of the Carrier Horizontal units with a Current Sensing Board. It was my first time troubleshooting one of these boards. I suspected it had something to do with the amp draw because my compressor was drawing too much amp and it was shutting down on LRA Locl Rotor Amp. When I removed the common wire on the board and contactor will energize try to start the compressor but it will fail on LRA. Thank you for clarifying. Great educational video.
@darwinjames2000
@darwinjames2000 6 жыл бұрын
Finally, found what I was looking for. Thank you! Just to understand the way the climate control board works on a condenser.
@gillcorona9615
@gillcorona9615 5 ай бұрын
Great explanation 👌
@3dgar91
@3dgar91 6 жыл бұрын
Great explanation! I ran into 1 today not knowing what it was. Now I do. Thanks!
@matth502
@matth502 2 жыл бұрын
Holy crap I just had a issue with this today and I’m not a carrier tech but this board through me a loop , didn’t know exactly what the board does but now I think I know what’s wrong
@mikemalone6103
@mikemalone6103 11 ай бұрын
great explanation / concept
@EyesofIllusion
@EyesofIllusion 4 жыл бұрын
Thank you for explaining. It now makes sense to me now🙏
@MrRene1968
@MrRene1968 2 жыл бұрын
Thank you sooo much. My air con does not recover after power outages, until I manually reset the thermostat, sometimes I have to turn off the breaker.
@ralphruiz1066
@ralphruiz1066 2 жыл бұрын
Thank you for explaining this.
@samho9318
@samho9318 7 жыл бұрын
Thank you, thank you.....SLC TECH😀😀😀😀. I had been searching for this circuitry and explanation for a while. I was so happy to came across your channel and VOILA!!!! there she is hehehe. The best ClO explanation of what it does and how it operates. BTW , Thanks for the wiring diagram. God bless you and your family.
@fighkb
@fighkb 5 жыл бұрын
Great video, very illustrated 👏👍🏻
@Anihmal
@Anihmal 9 ай бұрын
Thank you for this video, by any chance are you familiar with the blue control boards with the CLO moles plug intertwined with the main board itself? And if the CLO trips would the condenser fan motor stay running without the compressor?
@firozrajhati3554
@firozrajhati3554 3 жыл бұрын
Amazing video I understand every thing about this lock out Realy in only 8:45 mint thanks
@guddumishra5655
@guddumishra5655 3 жыл бұрын
Very good example sir thanks
@mohammedalobaidi9981
@mohammedalobaidi9981 Жыл бұрын
Thank you so much
@josephdalton802
@josephdalton802 7 жыл бұрын
Great video very informative need more on wiring
@apr9286
@apr9286 Жыл бұрын
TY , For this. So if I measure 24 volts at terminal X that means the board is in Lockout due to a low current at the compressor? Other than that X terminal should not read any Voltage in normal operation operation.
@michaelcostello6991
@michaelcostello6991 6 жыл бұрын
Great explanation. Thank you
@rajaawaisshahzad43
@rajaawaisshahzad43 2 жыл бұрын
Yor explain it really amazing thanu kindly make a video like this on pc board of trane package
@omarsharif2666
@omarsharif2666 6 жыл бұрын
Thanks sir good information and nice explanation sir i have one question plz show me high amp auto cutoff circuit board so we can protect compressor from high current plz sir
@syedbasheer8210
@syedbasheer8210 3 жыл бұрын
Thanks .its helps alot🤩
@GKRAJAN
@GKRAJAN 7 жыл бұрын
Good message sir thanks
@صادقعلی-ق9س3ه
@صادقعلی-ق9س3ه Жыл бұрын
Good ✔👍
@prithwishdey6708
@prithwishdey6708 4 жыл бұрын
Sir please one video make on Emerson ICM-220 lock out relay Waring cannection.
@captainnemo3549
@captainnemo3549 6 жыл бұрын
Thanks, had that issue today
@shahrukhqureshi5621
@shahrukhqureshi5621 5 жыл бұрын
Good job sir
@elcrazy8017
@elcrazy8017 8 жыл бұрын
Also very good diagram
@michaelcostello6991
@michaelcostello6991 6 жыл бұрын
Now i know how it works what is its main purpose of the CLO . To detect any fault that stops current in winding and require a power cycle to reset ??
@samho9318
@samho9318 7 жыл бұрын
One more thing to add: can I temporarily eliminate this board once I determined it defective ? New board take a week @ the supply house. Thank you. Sir
@arthouston7361
@arthouston7361 6 жыл бұрын
It is actually pretty rare for the board to fail. It can happen, but I encourage techs to exhaust all other avenues, first.
@jude2242
@jude2242 7 жыл бұрын
THANKS !!
@marcelobustos3915
@marcelobustos3915 3 жыл бұрын
Alguien me puede traducir al español está explicación?? Gracias
@rb3263
@rb3263 5 жыл бұрын
What if it's a 2 stage and both have clo, they are in series. If second stage drops off then itll trigger the clo right?
@rb3263
@rb3263 5 жыл бұрын
Nevermind, if the y de-energizes and energizes itll reset that board like you stated.
@stevengeis146
@stevengeis146 7 жыл бұрын
great
@sumeshac110
@sumeshac110 3 жыл бұрын
Sir voice not clear
@nascimento8083
@nascimento8083 3 жыл бұрын
OK
@braintumor943
@braintumor943 Жыл бұрын
Dude, you didn’t mention that it won’t start up if it senses current when not calling, not so needed with this but the older ones people try to jump out
The lockout relay circuit
6:45
grayfurnaceman
Рет қаралды 71 М.
Players vs Pitch 🤯
00:26
LE FOOT EN VIDÉO
Рет қаралды 126 МЛН
When u fight over the armrest
00:41
Adam W
Рет қаралды 26 МЛН
КОГДА К БАТЕ ПРИШЕЛ ДРУГ😂#shorts
00:59
BATEK_OFFICIAL
Рет қаралды 8 МЛН
HVAC Relay Training-  Bypass Timer
4:00
Zack’s in the Shop
Рет қаралды 77 М.
Economizer Troubleshooting
8:53
David Harty
Рет қаралды 58 М.
The Sequence of Operation for a Defrost Heat Pump Board
9:30
SuperCool Slide Rule
Рет қаралды 225 М.
Testing if an HVACR Compressor is Shorted to Ground, Open, or Overload Tripped!
11:06
Economizer Troubleshooting Carrier RTU
9:28
David Harty
Рет қаралды 52 М.
York Simplicity PC Software and Boards Tutorial PART 1
6:19
SLC TECH
Рет қаралды 12 М.
Economizers: Fundamentals (1 of 4)
8:38
Tec Tube
Рет қаралды 100 М.