Testing if an HVACR Compressor is Shorted to Ground, Open, or Overload Tripped!

  Рет қаралды 767,443

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
-Join our updates list for an email strictly from us for new videos, articles, products and website features! www.acservicetech.com Mini Split Book on Our Website- www.acservicetech.com/mini-split-book Mini Split Book on Amazon- amzn.to/3ytHJSs Mini Split Book on TruTech Tools- www.trutechtools.com/BooksGuides Mini Split E-Book on Google- play.google.com/store/books/details?id=HN-iEAAAQBAJ Mini Split E-Book on Apple- books.apple.com/us/book/id6445178399
@paulpeter2869
@paulpeter2869 4 жыл бұрын
Hi Craig! Love your videos! AMANA furnace with a B1 code (module not communicating with blower motor) emerson aa25650l variable speed. Meter reading from R-W is 0.04V at the control board and the rest of Tstat wires are 27V. Do you know what could be the problem? Thanks very much!
@paulpeter2869
@paulpeter2869 4 жыл бұрын
The motor is working fine as per ohms test at the 3 pin connector
@dayjavu2586
@dayjavu2586 4 жыл бұрын
Do you have a video on low, medium and high temp compressor difference?
@pehvac9198
@pehvac9198 2 жыл бұрын
Thanks for all the amazing knowledge boss
@abelmouzount8817
@abelmouzount8817 2 жыл бұрын
Hi I just had A unit where we put all new wiring box / outlet then change the capacitor but end up with no running fan after ordering a motor fan condencer got it changed the fan started working but the house isn't sending a cool air in the house ?? So I'm afraid there's a problem with a bad compressor or just cuz of the hot weather that I need to hose it down with water then cool it off then try it works? I wish I could get some guidance from anyone here that faces similar problems? Thank you
@newstart49
@newstart49 2 жыл бұрын
Great video!! Suggestions and beyond ; 1. If the IOL is stuck open and it shouldn't be (Cold compressor etc), try hitting it with a 2x4 to unstick it temporarily until the repair/replacement can me made. Sometimes a sudden shock will get it to close. Sounds unprofessional, but if you get it going for the weekend, you're a hero! 2. After turning off the power to the outdoor unit, push the contactor fully in- to make sure the power is off and to bleed the capacitors at the same time so you don't get bit. Check as well with the meter to make sure power is off. 3. If nothing is running outside and it should be, don't be fooled. A bad duel capacitor can cause the compressor and the motor both to overheat and shut down. 4. Plastic forceps come in handy for quick connecting a temp wire or meter to another wire or capacitor for testing. 5. Always test a grounded compressor at the compressor itself, the wiring to the compressor may be shorted to ground (Made that mistake one cold day covered in snow- but only once) lol 6. A float drain switch in the main drain can flicker the low voltage on and off quickly causing chatter at the outdoor contactor and also cause the scroll compressor to run backwards resulting in a no cooling situation and a noisy compressor complaint. Install a time delay relay in the circuit and set it for one minute minimum. 7. Always verify your meter is working by testing it on live voltage first! Assuming the power is off because you don't read voltage just might mean your meter just quit working. I've enjoyed HVAC work for over 48 years and I still love it!
@j.bennett2485
@j.bennett2485 3 жыл бұрын
Hands down the best teacher and KZbin channel on here. For someone who likes troubleshooting and fixing their own equipment these videos are incredible.
@rolandotillit2867
@rolandotillit2867 2 жыл бұрын
When the shaft seal is puking out oil and refrigerant, the compressor sounds like a bunch of marbles when you try to run it, and there's metal paste in the discharge line, I assumed it meant the compressor was shot, good thing this video exists to make me reconsider.
@joseorta9928
@joseorta9928 Жыл бұрын
Great explanation...Im a minisplit tech in Apodaca Mexico...in yr videos I learn alot...
@NoWayCraig
@NoWayCraig Жыл бұрын
If you get OL between any terminals, common to run, run to start, start to common, you’ll get OL on your meter. That’s means the winding is open. It’s possible to just have one of the 3 open, 2 of 3 open or all 3 open. If the compressor is severely overheated the windings will be open until the internal overload resets. You can cool the compressor off with cold water or ice. A lot of times you’ll hear the internal overload reset, it’s a mechanical “click” noise. If you check any terminal to ground (any terminal to copper ref line works best) you’ll get continuity or a “beep.” If you get a beep on any that compressor is dead. On a 3 phase compressor all resistance (ohms) from terminal to terminal are EQUAL. On a single phase compressor common to run and common to start=start to run….run to start is the LARGEST RESISTANCE VALUE, common to run is the LOWEST RESISTANCE VALUE.
@huskyng6981
@huskyng6981 Жыл бұрын
Hi Craig my situation is same like you mentioned Compressor, , Start - to run 2.9k ohm, and common - to start =OL, and common - to run = OL OPEN, And I haven't turn on ac for days even crazy hot weather too, is there anyway I can fix it??? And I also check , common - to ground green =OL, Run - to ground 39k ohm + and meter ohm keep on increasing, and Start - to ground 39k ohm+ meter keep increasing???is there way to fix or I have to replace a 5 months brandnew compressor?? Thank you for your help and your time
@EarthaNell
@EarthaNell 7 ай бұрын
The contact is pulled in, but the compressor nor fan start. Got readings for compressor wires and terminals, but one wire from condenser fan had no reading. Will dead fan motor prohibit compressor from starting? 1996 Goodman 3 phase condenser unit.
@muneycorn6310
@muneycorn6310 2 жыл бұрын
Love your videos Mr Craig ...You and Mr Brian (kalos) are great teachers.Invaluable to those of us learning online.
@abnergarcia6252
@abnergarcia6252 4 жыл бұрын
Great vídeo! I would love to see a video where you troubleshoot a compressor with bad or weak valves.
@harpoon_bakery162
@harpoon_bakery162 4 жыл бұрын
Thanks for keeping parts that went bad. That helps tremendously to lock on a visual.
@soheil7673
@soheil7673 4 жыл бұрын
This tutorial very useful. But that's part of compressor checking. That's electrical checking only. What if the compressor is seized. Or weak. One of the best solutions checking mechanical functionality would. Be pump down the unit to see if it pumps down correctly or not. On the other hand all inverter units have same winding resistance as the inverter controls the load of compressor by increasing and decreasing the Amp and volt rather than winding. Big like to all your efforts during last couple of years. Appreciable
@MiguelRamirez-ld7sy
@MiguelRamirez-ld7sy 6 ай бұрын
I've been messing with a Honda generator and it's gen Head. I kinda, sorta see some similarities between the two. Then again the extent of my voltage meter experience is the continuity setting on my volt meter. Great channel by the way.
@jesusadrianbarraza3061
@jesusadrianbarraza3061 4 жыл бұрын
The best chanel for hvac hands down!!!
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thank you for your support!!!!
@josepalacios627
@josepalacios627 4 жыл бұрын
Im working on a unit rn with compressor windings that are good but it doesn't start. I tried that grounding test and that's what it was. Im so grateful you made this video lol
@apprenticephil649
@apprenticephil649 4 жыл бұрын
Love the video but perhaps showing how a compressor analyzer or start kit can help diagnose a bad compressor would be informative as well.
@sewerat11
@sewerat11 3 жыл бұрын
What ohm setting do you recommend
@Reefertech
@Reefertech 4 жыл бұрын
So basically if the compressor is off on overload it would read OL between windings? And if it’s shorted to ground you would get continuity(tone) from the shorted winding to ground ?
@specialK_hvac
@specialK_hvac 4 жыл бұрын
If you measure ohms between run and start but not common and run and common and start that's am internal overload that is opened
@officerkrupke4966
@officerkrupke4966 2 жыл бұрын
You would read continuity to ground on all windings since they are all connected
@davidstofanak3222
@davidstofanak3222 2 жыл бұрын
We just had our compressor fail after 2 years of service. Its a mr cool universal heat pump DIY install. We had an authorized MR Cool tech come out and diagnose it and covered its replacement but I'm worried maybe we wrong during the install. The Tech was super impressed with our work and said everything looks great but I'm worried. The compressor sits on ground level outside the house and the AHU is in the basement maybe 4-5' drop in grade. When we installed the line set we didn't install any oil return bends just kept it as straight as possible hanging them basement ceiling. Having a hard time researching oil return bends not a lot of quality information on it. I'm just worried if we replace the outside unit we would potentially be in the same spot in 2 years if we install it the same way. BTW your videos are awesome!!
@monteglover4133
@monteglover4133 4 жыл бұрын
Not all failures are burnouts. There are 3 types of Compressor failures opens, shorts and burn outs. A standard VOM may not find a high impedance short to ground a merger maybe required. I’m a HVAC&R service tech with 40+ years of experience.
@monteglover4133
@monteglover4133 4 жыл бұрын
Generally shorts to ground are not a burnouts or have significant amounts of acid in the system. A burnout will generate acid from insignificant to severe and often create sludge if any doubt use an acid test kit. At a minimum a high capacity liquid line dryer should be installed when changing a compressor and the refrigerant should always be changed.
@eliogonzalez3038
@eliogonzalez3038 4 жыл бұрын
Thank you so much for your help 🙏 and it help me a lot God bless you
@miguelurbina3004
@miguelurbina3004 4 жыл бұрын
Yes definitely a megohmmeter is the right tool for this a vom is not capable of reading such values
@TheWpruden
@TheWpruden 2 жыл бұрын
Every hvac tech should have a megommeter to test for those high impedance shorts!!!
@monteglover4133
@monteglover4133 2 жыл бұрын
@@TheWpruden even the cheap ones, will work if it has a high voltage test mode
@mrman5374
@mrman5374 4 жыл бұрын
This guy is simply THE BEST!
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thank you for your support!
@mrman5374
@mrman5374 4 жыл бұрын
@@acservicetechchannel No really thank you for what you do! We live in a time where training is so poor, but you have helped me tremendously!
@JuanGarcia-qu8ms
@JuanGarcia-qu8ms 3 жыл бұрын
Thank you for your help, I have learned a lot with your videos, I have already started my own business, I really appreciate you help. Thank you.
@clifordmichel8981
@clifordmichel8981 2 жыл бұрын
Great video, Haiti represent
@carolineandjaimegonzalez9839
@carolineandjaimegonzalez9839 2 жыл бұрын
Smelling the refrigerant works too. Spraying just a little of bit of refrigerant in your hand and if its smell like burnout tells you that you have a burnout compressor as well. That's just another easy way to identify a burnout compressor.
@acrservicesmathewr7565
@acrservicesmathewr7565 2 жыл бұрын
The oil will also be black. Or darkened. It does have a terrible smell when it burns out or I have seen a ton of foam which indicates liquid migrating to the compressor oil and sludging it
@rodgraff1782
@rodgraff1782 Жыл бұрын
Also the wonderful smell of phosgene gas.
@tutata7228
@tutata7228 3 жыл бұрын
Excellent video, I'm not working on ac at the moment, but I still want to keep learning more and refreshing my memory 😊👍🏼
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
You can do it!
@tutata7228
@tutata7228 3 жыл бұрын
Thanks! 😊
@nihalahmadpasha7607
@nihalahmadpasha7607 3 жыл бұрын
Good for every technician thanks
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
So nice of you
@turbolag98
@turbolag98 4 жыл бұрын
Is it a failed compressor if the compressor is pulling double LRA even after installing a hard start kit but the windings have continuity? Compressor isn’t tripping the circuit breaker either
@specialK_hvac
@specialK_hvac 4 жыл бұрын
Yes that would be a failed compressor if it is mechanically locked up like that. Sometimes you can give it a bump and it will free up but that's a stop gap solution
@LloydAveryM
@LloydAveryM Жыл бұрын
This video was very thorough.
@vsjapan
@vsjapan 4 жыл бұрын
Great video. What is it that is causing the ac breaker trip frequently? Checked all the electrical of the condenser unit and all seems to be good. The capacitor is new the fan motor has no issues the contactor looks good. Could it be the compressor causing it? If so how to diagnose and fix? Thanks.
@thembones12
@thembones12 4 жыл бұрын
Check the circuit breaker itself...Make sure that ac breaker it not warming up or hot when you start/running the compressor, check the temp of the circuit breaker-using HVAC infrared thermometer...Also, With your HVAC clamp on ammeter, check the Starting Load Current SLA and Running Load Current RLA...
@vsjapan
@vsjapan 4 жыл бұрын
@@thembones12 Thanks for the reply. Just for your information, it was the compressor. It was overloaded with Freon. Overcharged with the Freon. Recovery of the freon did the trick. The breaker has not tripped since then. Thanks.
@douglieberman6406
@douglieberman6406 Жыл бұрын
That means we are looking a variations in current related to different resistance, or the resistance and current are inversely proportional. As the resistance goes down the current goes up !
@ricardomunoz9617
@ricardomunoz9617 4 ай бұрын
Thank you, sir. Your videos are very helpful They help me refresh my mind all the time.
@shaneisaac1184
@shaneisaac1184 11 ай бұрын
Hello Craig, which of your books would be best to learn the fundamentals of hvac split and troubleshooting methods? Am trying to save costs by DIY as much as I possibly can. Thanks.
@daveyt4802
@daveyt4802 4 ай бұрын
I have a Copeland that is 23 years old. Just have R22 with 30psi on the low side. I charged it up to 60 psi a few weeks ago. My current problem. No leaks found yet...
@TheWpruden
@TheWpruden 3 жыл бұрын
A megommeter should always be used to test integrity of winding insulation. Not a multimeter.
@rodgraff1782
@rodgraff1782 Жыл бұрын
Finally someone who knows how and when to use a megger. I have three AMEC megohmmeters, crank style. It is the proper tool for checking the condition of the insulation on the windings to ground. If a system has moisture or contaminants in the oil, it will fail a megger test.
@Hummer999xx
@Hummer999xx 4 ай бұрын
During startup the condenser makes a loud thumping noise, does it mean the compressor is bad? It’s a new build. The technician came out twice and said the compressor is not bad. I don’t believe it. My neighbor isn’t having the same issue.
@mickeylojkar5769
@mickeylojkar5769 3 жыл бұрын
On a 3 phase compressor, 2 windings reads the same. One is higher than the other. Is that term called shunted winding?
@emmaa427
@emmaa427 3 жыл бұрын
Thx for sharing your knowledge!
@blh3741
@blh3741 5 ай бұрын
your videos and books are great! thanks, Brian
@techhdan
@techhdan Жыл бұрын
My technician came today and put the clamp on the black wire while the system was running. He said the compressor was bad based on that reading alone. What should be the voltage when connecting a compressor to the black common line while running? Can you really tell if a compressor is bad by just clamping the black wire?
@samersarah957
@samersarah957 3 жыл бұрын
Is that better prove or using merger? Thanks.
@seek3n
@seek3n Жыл бұрын
So when ohm is high=burnt winding? And if there's resistance from compressor to ground showing resistance =shorted to ground? Because that means is connected
@Thomas-eh8lb
@Thomas-eh8lb Жыл бұрын
Why cany you clean the coil if you can clean the lines? Thanks
@handyertanto76
@handyertanto76 2 жыл бұрын
Thanks you sir, for delivering this information. It's usefull indeed and comprehensive. Greetings from Indonesia. 🙂👍
@tshokaphiri8381
@tshokaphiri8381 3 жыл бұрын
Hi guys, im a service technician in Botswana and love the great work y'all are doing with the videos! Coincidentally i had a similar problem just the other day with a Maclaren 12000 btu packaged unit! The compressor was heating up and much like in the video the thermal overload kept it from starting! I did an ohm test, continuity test and ground test to the compressor and everything checked out! I also tested the capacitor and also did a visual test and still everything seemed legit! I then took the decision to remove the thermal overload to see whether the compressor would start (big mistake) long story short the compressor overheated and shutdown! Can you help on what could have been the problem and what could i have done different
@2169scs
@2169scs 2 жыл бұрын
Very good education on AC compressors , thanks
@tytig94
@tytig94 4 жыл бұрын
I have that same meter! I love the dual temp probe feature, and LRA/inrush option. Also the min/max option is cool. Great video, thanks.
@tytig94
@tytig94 4 жыл бұрын
Also your vacuum videos really saves me a lot of time. I use your 3 core tool removal tool method with 2 hoses, I pull a vacuum in 5 minutes or less with valves open! My company wants me to train everyone on how to do it, I did give you credit. I wish more guys would spend time mastering their trade away from work.
@noeeon9910
@noeeon9910 3 жыл бұрын
You guys make me want to learn the trade!
@Boojyman
@Boojyman 2 жыл бұрын
A good meter will tickle your peter
@delroymorrison7599
@delroymorrison7599 Жыл бұрын
If the COMPRESSOR show normal no reading is it good or further testing is needed
@fernandocortes9420
@fernandocortes9420 4 жыл бұрын
Hi I love your videos thanks for keeping us learning God bless you Sr 🙏🏼
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks for watching!
@albertrubian2971
@albertrubian2971 2 жыл бұрын
@@acservicetechchannel Good day Sir First of all sorry to how can i speak English but i hope you understand... What are the possible problems to compress Air dryer with alarm overload and everytime i turn on the breaker it always tripping (3 phase)
@ApartmentMaintenance
@ApartmentMaintenance 4 жыл бұрын
Great video & explanation Craig 👍
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Glad you enjoyed it
@hvacrtroubleshootingsimula301
@hvacrtroubleshootingsimula301 3 жыл бұрын
When it comes to identifying the compressor winding, I usually teach the winding opposite the highest resistance is the common winding. The second highest resistance is start and the lowest resistance is run winding. The major question is, why is the start resistance greater that the run resistance?
@andreagate542
@andreagate542 2 жыл бұрын
There is no comment on my name only a run whining and start whining and they both meet at a common point which is the common connection or C terminal
@brandonnewyork11
@brandonnewyork11 2 жыл бұрын
Because the motor has an in-rush of current when it starts which needs more resistance (start Winding has more resistance than the Run Winding
@SpottedEagleOwls
@SpottedEagleOwls 3 жыл бұрын
I have made a mistake by swapping the LIVE and NEUTRAL wires. Will this damage my compressor as my input and output pressures always stays the same ?
@copkhan007
@copkhan007 5 ай бұрын
While the system was running, my guages were reading equal pressures on both high and low sides. I checked the capacitor, and it was good. Disconnected all three wires to the compressor, I was reading 1.3 ohms between the 2 terminals and OL between the other 2 terminals. My guess compressor is bad.
@mikemorton6219
@mikemorton6219 3 жыл бұрын
If you get acid smell from refrigerant, it's a bad burnout. Put ammeter around all 3 compressor wires. If meter moves at startup, compressor is grounded.
@sonamtobgay1797
@sonamtobgay1797 2 жыл бұрын
Plz can u explain me why my cold store getting off time and again..I had change contactor also
@mlwee6796
@mlwee6796 3 жыл бұрын
You disconnected the wire from the compressor in the split unit. Is there any residual power or current in the compressor? Any precautions needed?
@Franklinveterinarycenter1of4
@Franklinveterinarycenter1of4 2 жыл бұрын
gotta use caution with the capacitor !!! KZbin how to drain "entergy" from capacitor
@jimbola77
@jimbola77 4 жыл бұрын
awesome! Craig thank you for sharing! all your videos are so well explained! have a nice and safe weekend.
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thank you for watching!!
@scetchport
@scetchport 8 ай бұрын
Easy to follow info. Thanks. In process of testing those in dometic harrier inverter rv airconditioner.
@francisguchie1973
@francisguchie1973 Жыл бұрын
So detailed - I like
@donniesmith8779
@donniesmith8779 3 жыл бұрын
If a compressor is locked up, is it still in a bad spot and not good?
@mytexasdays1526
@mytexasdays1526 Ай бұрын
I put in a new contactor, capacitor, fan motor and the fan is not turning on. I can't remove the wiring harness from the compressor. How do I get it off? It's a Copeland r22 3.5 ton 20+ years old.
@heatncool
@heatncool 4 жыл бұрын
On thermal overload does it open 1 winding or 2? It opens winding between common and start? Or both between common and run?
@ajenjohnson7413
@ajenjohnson7413 2 жыл бұрын
I do enjoy your videos, great job there, but I do I have a question. I have a heatpump ( portable ac) and it is kinda noicy and I did some research on that and I learnt about using something called ac compressor blanket which wraps the compressor completely to insolate the noise it produces, can I use that on my portable ac compressor? If yes can I make a homemade cushion ac blanket and use that instead? What is your advice, please let me know. Thanks👍
@mtbbiker6401
@mtbbiker6401 5 ай бұрын
Are there better connectors for compressor wires than using wire nuts?
@CHOPPA78
@CHOPPA78 2 жыл бұрын
Not on All compressors tho ,,if it sn inverter values would be the same on each approx 2 ohms could you confirm?
@resurgensix
@resurgensix 3 жыл бұрын
You helped me out diagnosing this today. Thanks!
@jeremymorgan7199
@jeremymorgan7199 5 ай бұрын
I had a compressor blowing the breaker. I check resistance from C to R and got OL, C to Start was 47, start to R was also 47. But it wasn't grounded. The compressor wouldn't start tho. So I changed it. Did I do the right thing or did I miss diagnose something?
@RitinPali
@RitinPali 2 жыл бұрын
Daikin 1.5 ton inverter split ac. 5yrd old. R32 gas running pressure 150psi. Current 6.3amps Both indoor and outdoor coils have been cleaned. Service Technician says it's ok. But it's not cooling. Temp in the indoor blower showed 16'c or 60'My brand new split AC showed indoor temp at 6'c or 43'f Previously compressor would heat up and trip. So got the outdoor pcb repaired. Now it doesn't trip but keeps running. And does not cool the air. The discharge line had a bad pinch in it. It ran throughput last season. Am out of ideas any help greatly appreciated. TIA
@kurtsmith5202
@kurtsmith5202 Жыл бұрын
Ours want to start up , but won’t you can hear it engage but , will not start up , is our condenser gone or is the capacitor
@phongpham1453
@phongpham1453 3 жыл бұрын
thank for sharing your knowledge.
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
My pleasure!
@Saulgr
@Saulgr Жыл бұрын
How do you know when the compressor all 3 has to be the same value and when the 2 has to match the 3 value C-S= 3 C-R= 3 S-R= 3 Thanks AND C-S= 3 C-R= 2 S-R= 5
@jcmendoza8285
@jcmendoza8285 3 жыл бұрын
you guys are a great source of Knowledge Thank you!
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Thanks for watching!
@mrgreen9086
@mrgreen9086 3 жыл бұрын
How common do compressor plugs go bad?
@roymarksberry4152
@roymarksberry4152 Жыл бұрын
If you get completely on your meter from one of the terms on the compressor
@johnconnor7501
@johnconnor7501 Жыл бұрын
What if my start to run ohms don’t add up right. Like 30% off?
@calledout4437
@calledout4437 Жыл бұрын
So we had a power outage and then suddenly the ac breaker tripped. Now it trips the second the ac unit kicks in. It appears to be the compressor itself, however, it measures fine and does not appear to be shorted to ground and everything measures out normal. Could it still be a bad compressor or something else? I disconnected the compressor and just let the fan run and it stays on without tripping. Kind of irritated the a/c tech came and didn't even do any measuring and just immediately insisted the compressor is bad.
@heatncool
@heatncool 4 жыл бұрын
Why did a new compressor come in with 2 open windings ?! It was a 1ph lg 175v residential refrigeration compressor.
@ianp8764
@ianp8764 3 жыл бұрын
Freedom hall
@ianp8764
@ianp8764 3 жыл бұрын
Freedom Hall
@rodgraff1782
@rodgraff1782 Жыл бұрын
Always test the compressor before lifting it to the roof. There are ones that are bad, or are damaged in shipping
@techfive7202
@techfive7202 3 жыл бұрын
I had a carrier 2 stage residential compressor that threw me off. All terminals with plug removed showed continuity to ground but the terminals ohm out at .6 .8. .2. Not exact numbers but close. Normally the ohms are higher plus I never seen them add up when it is grounded. The compressor had 2 plugs which I never seen before. The other plug had only 2 terminals that I did not test. It was 2 stage obvious. Would trip breaker as soon as the unit turned on. Unplugged compressor and the fan would run. Another odd thing is it would trip as soon as I put the disconnect in without the contactor engaged
@steelod1528
@steelod1528 4 жыл бұрын
Hey craig could you do vids on light commercial equipment not too many vids on that
@belkacemfekkane2199
@belkacemfekkane2199 4 жыл бұрын
an alarm (compressor B fault) in a 30rqm / rqp 160-520 heat pump. Is the problem in the soft or the ccompressor?
@jhonnychingass6252
@jhonnychingass6252 2 жыл бұрын
What side you open 1st when you install a condenser,, low side or high side?
@sergiodoordie319
@sergiodoordie319 2 жыл бұрын
Don't Matter but most techs go for low side the thick pipe
@__aaron___
@__aaron___ Жыл бұрын
​@@sergiodoordie319 uh..no. always liquid side (high side) first.
@marvinostman522
@marvinostman522 4 жыл бұрын
I have had this scinerio a few times. Compressor blowing the breaker. Testing at the compressor two windings had continuity to the tubing but not the third. The two shorted show continuity to each other but not the third. I ordered out the new compressor and someone else goes back and later tells me there was nothing wrong with the compressor. The fan would test out fine. Can an open overload create a path to ground? I did have someone tell me not to use too high of a range on the meter because it can give a false reading. I have been using just the straight continuity setting with the tone.
@chefeatsher
@chefeatsher 3 жыл бұрын
An open overload would not cause a path to ground. It would just prevent from the control relay coil energizing.
@spartan5106
@spartan5106 Жыл бұрын
Excellent video, thank you for sharing
@tonyp6088
@tonyp6088 2 жыл бұрын
Is it possible for the compressor to test ok accross the terminals but when it's powered up goes to earth? I'm having that issue at the moment. I have OL from terminals on compressor to the housing. But when the compressor is running there is voltage in the housing causing it to trip the curcuit breaker.
@DaLeSy.
@DaLeSy. 9 ай бұрын
What did you set your multimeter to when checking if it is shorted to ground?
@thesetruths1404
@thesetruths1404 6 ай бұрын
Great video...thanks. This is what I have, does it indicate a bad relay? Whirlpool WRT111SFDW03. 7 years old. 11.2 cu ft size. Freezer on top. Start relay P/N: WPW10448874, aka W10448874. Capacitor ("cap") P/N: WPW10662129 Test relay connections with capacitor on the relay. Results: when together I can get cap to charge and discharge thru the start relay, just like it does when it's off the relay. With cap off and on, neither of the lower holes have continuity with each other. The hole on lower left has 0.0 ohms resistance thru the bottom blade of the back of the plug. The lower right hole has no continuity with anything but can be used to charge the capacitor for testing. The upper hole has 0.1 ohm resistance to the top blade on the opposite side. Remove relay cover and visually check. I cannot get combination relay apart without breaking it, so I haven't committed to that, yet. Ohm test the fridge compressor pins again. Make sure the Common (top) and lower pins are within 3 ohms. And the two pins at bottom should read about the sum of the Common with the Start and Run pins. See KZbin video... Results: Top and Lower Right : 4.4 ohm. Top to Lower Left: 6.0 ohm. Two bottom pins: 10.4 ohm. None of the pins are shorted to ground. My problem is it suddenly stopped cooling without noises or warning, but I caught it from hearing loud buzzing noise from compressor and relay area, and compressor was very hot. No smoke or smells though, and wires did not seem to be hot. Do you think it's the combination relay? Many thankz!
@nathanroman4968
@nathanroman4968 2 жыл бұрын
I called technician over my fan not starting after a power outage on the community. After he came and inspected I noticed that the circuit breaker was not fully engaged and after fully place that in the right place. He can started unit and the fan start spinning. He proceed to take out the fan and got into the unit and mess with the therminal plug it slightly out and then place the fan back and started again and told me that I have to replace the whole compressor because now I have a freon leak. How can an electrical issue not causing the dan to spin, will make the the final to blow when all the pins are present and the AC Wwas not on for longer than a minute and no creo was added??
@MrRalph438
@MrRalph438 4 жыл бұрын
Have your book and quick cards, Posters are also helpful. Recommend them to everyone in HVAC Trade.
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks a lot Ralph!
@hermesyanez1431
@hermesyanez1431 2 жыл бұрын
very nice buddy how always!, i love it all your videos, i follew you from Honduras, regans master!
@abmtz8537
@abmtz8537 3 жыл бұрын
Is it normal for my ac compressor to be wet from the thicker copper line down? It’s also taking very long to cool down my house.
@goldhammer561
@goldhammer561 4 жыл бұрын
Awesome video
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks for the visit
@mikeinocencio9516
@mikeinocencio9516 2 жыл бұрын
I got a hp 3 ton scroll ,comp plug burnt up. replaced compressor and plug. start up pressures equalized amps at 2.0. rated for 12amps. 208 1phase. replaced IT again, start it up same thing. any ideas?
@douglieberman6406
@douglieberman6406 Жыл бұрын
I would like to try white neutral line to neutral bar in breaker box for common of compressor, as start to common L1 Run to common L2 And common a neutral line to breaker box neutral. 2 breaker switches for compressor, one for L1 and other for L2 . It just that neutral (white ) is common and also hook up the ground line! Same goes for the 240 volt e c m . ! Just like a 240 v a c light bulb with 2 switches and one neutral.
@Hvacnc
@Hvacnc 3 жыл бұрын
Thanks for your videos man!
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad you like them!
@solomonkariuki4797
@solomonkariuki4797 4 жыл бұрын
Hi, so much working on ac in gulf. I have a question about central unit. Single room the thermostat is no switching on.
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
look up "acservicetech testing thermostat with multimeter" thanks!
@toupsclassroomtoupsclassro9557
@toupsclassroomtoupsclassro9557 3 жыл бұрын
question: ok, bad transformer in heat pump. However the wire on the com. is red, so I'm assuming I connect this one to the white wire on the univ. transformer. Is this correct? Also, the white wire is on the 240 of the old one so I would connect the white wire to the orange for 240 the sec'd wires don't matter in orientation. Is all of this correct? ty
@jackmcdonald7391
@jackmcdonald7391 3 жыл бұрын
I read ohms to ground between a compressor winding and the copper line to it and when I plugged it in it ran just fine.It was a scroll compressor.Not sure how it was possible but I almost condemned it for no reason
@bineshchauhan8713
@bineshchauhan8713 4 жыл бұрын
Wish you long live and better doing Happy teacher day 💐
@gail6904
@gail6904 7 ай бұрын
HELLO I have an Older window ac compressor ..I cant get the black tops off the top of ac compressor to test it~~~ has like a hard clay material glued on in globs...must hold the compressor black covers on ..any advice how to remove ? I need to test my compressor to see if it is bad..unit blowing hot air in and cold air out..hopefully only the cap is bad..no reading on HERM side in MF...
@Ashraf-bu6ob
@Ashraf-bu6ob 3 жыл бұрын
Hello. My fridge compressor got a reading: 1) 7.5 ohm 2) 17.4 ohm 3) 24.6 ohm Is the compressor is good? Thank you..
@nyikayaramba7460
@nyikayaramba7460 2 жыл бұрын
No the compressor ohms is to high which means the compressor is defective
@rjboxingit3368
@rjboxingit3368 2 жыл бұрын
My AC Breaker trips instantly when setting to cool. The outdoor unit is a Carrier 2020 model that was installed new last year. Anything ese I can try before having to call a tech? short on cash. 1. I tested the 3 compressor pins and they all show OL. 2. I disconnected the compressor to see if breaker would trip without it and breaker does not trip, Fan Spins also.(This makes me think there is not an issue with Breaker nor contactor and maybe it is an issue with the compressor or wiring.) 3. Outdoor unit is very clean, and I dont see any visual wiring issues.
@tonyp6088
@tonyp6088 2 жыл бұрын
Hey there, did you find the issue? My compressor does the same thing. Tests fine but trips the breaker when powered up. Not getting any replies on here. I did try disconnecting the earth lead on the compressor briefly just to see if it would run... and it runs perfectly. But it makes the housing live!
@rjboxingit3368
@rjboxingit3368 2 жыл бұрын
@@tonyp6088 Yes, I had to get the compressor replaced. Luckily My compressor was still under warranty.
@rjboxingit3368
@rjboxingit3368 2 жыл бұрын
@@tonyp6088 I was charged $1700 for repair, which is alot more than I wanted to pay.
@edsecce5685
@edsecce5685 3 жыл бұрын
My reading is off by 0.6 ohms, 1.5 plus 3.2 gives me 4.1 ohms instead of 4.7, it's my compressor broken?
@Tito-hvac8
@Tito-hvac8 7 ай бұрын
Great video. Thanks💯
@omgsogood5524
@omgsogood5524 3 жыл бұрын
its also possible for the lower resistance leg to be your starter right? ie, you showed 1.7ohm as the start as its a higher resistance but on my sub zero, im seeing the LOWER resistance leg is indeed the start leg [ its the leg for the capacitor ] for BOTH compressors. funny thing is i've checked both compressors and resistance is good as well as no short to ground. but for some reason, the freezer side is just not getting cold. also checked the voltage going into the relay as well as the capacitor.. so kinda scratching my head
Air Conditioner Troubleshooting! Connecting, Measuring, Fixing, Disconnecting!
21:05
10 Reasons Why A Mini Split Flare May Be Leaking Refrigerant!
18:15
AC Service Tech LLC
Рет қаралды 750 М.
Гениальное изобретение из обычного стаканчика!
00:31
Лютая физика | Олимпиадная физика
Рет қаралды 4,8 МЛН
1% vs 100% #beatbox #tiktok
01:10
BeatboxJCOP
Рет қаралды 67 МЛН
BAYGUYSTAN | 1 СЕРИЯ | bayGUYS
36:55
bayGUYS
Рет қаралды 1,9 МЛН
Your AC Compressor Might Be Going Bad, 2 Quick Ways To Find Out!
11:09
Diagnosing a Locked Compressor 3D
10:02
HVAC School
Рет қаралды 75 М.
How I Troubleshoot an Air Conditioner Compressor
12:17
Fox Family Heating and Air Conditioning
Рет қаралды 310 М.
Liquid Line Restriction on AC Unit Explained! Found Bad TXV!
13:35
AC Service Tech LLC
Рет қаралды 403 М.
Failed Compressors - Don't JUST REPLACE IT
24:59
HVAC School
Рет қаралды 68 М.
MINI SPLIT Parts Explained! Understand What They Do!
19:31
AC Service Tech LLC
Рет қаралды 672 М.
How to Test an Overheated Compressor (Diagnosis & Causes)
22:35
HVAC School
Рет қаралды 196 М.
Гениальное изобретение из обычного стаканчика!
00:31
Лютая физика | Олимпиадная физика
Рет қаралды 4,8 МЛН