Removing the Start Enable signal (bypassing the auto mode) you can run the drive in Hand (manual).
Пікірлер: 10
@Man-xn2fuАй бұрын
Here's my personal scenario. Just in case there's anyone in these comments just trying to find any solution to this error message. I work at a school and there was a power surge. When I got to the building all my exhaust fan speed drives had this error. Turns out what happened was the fire alarm system had tripped which shuts off all the exhaust fans. Once I reset that all the 2021s cleared. I'm sure this won't help everyone, but I wish I had known this before I spent hours trying to figure this out.
@EdgAdmRmz001Ай бұрын
Thank you very much for your comments, and it is also important to check the fire protection systems as you mentioned.
@paolopa-bb2pb Жыл бұрын
Do you have instruction for this alarm repair?
@Ali_____Raza9 ай бұрын
Bro you changed auto mode to hand and run vfd how
@EdgAdmRmz0018 ай бұрын
Hello, thanks for visit the channel On the video I describe how to change the parameter, If the drive is in Auto and you try just to press manual (hand), is not going to work