@ronnelson89547 жыл бұрын
Really enjoy your chiller/HVAC videos. Can you do one on the oil lubricating/bearing systems of chillers? Also videos on the different motors of screws, scrolls, recips, loading/unloading, etc?
@mrgreen90864 жыл бұрын
These videos make so much sense when you know your basic refrigeration cycle, and the seal system. Some great knowledge on this channel.
@lamichaelkreitz68215 жыл бұрын
As a Daikin Factory service tech (who was working on these today) I must say I love to see you using our machines as a template for your graphics. I love your videos and this one (although review) is no exception. Cheers!
@unclemonster484 жыл бұрын
LaMichael Kreitz us old mcquay boyz cheers
@reyruiz77634 жыл бұрын
Trane no daikin
@Baylessfishes3 жыл бұрын
Left Mcquay in 2005, Trane till 2016 and now I do service for them.
@lamichaelkreitz68213 жыл бұрын
@@Baylessfishes I’m happier here at Daikin than I’ve ever been in this trade! Great company to work for! I absolutely love engineering mindset videos as well.
@kaptaintrips2 жыл бұрын
@@lamichaelkreitz6821 You Daikin guys sure love your pannels and stripped out screws... Still decent engineering compared to others (cough, Carrier). When it comes to chillers, give me a complicated centrifugal any day. Then perhaps a screw...
@toyinorodare40726 жыл бұрын
Thank for your clear explanation. you actually develop my interest in HVAC training and as at today I can design it. thanks a lot
@sadiqueahmad95084 жыл бұрын
What is chiller surge? It's basically an unwanted situation which occurs due to difference in pressure between outlet and inlet of compressor. It may occur if the temperature of the condenser raises to a level at which the pressure becomes more at the outlet of compressor (going into the condenser) .
@shivaHVAC4 жыл бұрын
How to avoid this issue?
@IRSHADKHAN_75034 жыл бұрын
Thanks for an easy explanation, I have worked on York OM Titan chiller (5090TR) which had hot gas bypass line.
@TheSkunk1996 Жыл бұрын
vARY USEFUL. tHANK YOU FOR POSTING AND DEDICATING YOUR TIME!!!!!
@josephgeorge61894 жыл бұрын
Excellent explanation! Good job!
@karunakaranreddy72746 жыл бұрын
Nice and thanks Awaiting for VGD and PRV Control in chiller
@alak30736 жыл бұрын
thank you very much for your efforts
@munimechanical39423 жыл бұрын
Hi sir iam maintained at 1000tr Daikin chiller your video is very usefull
@fadiyasin6 жыл бұрын
very good job thaaanks
@CircinusMusic2 жыл бұрын
Thank you for the knowledge u share
@ibrahimosman33937 жыл бұрын
Good efforts waiting for ammonia systems
@Luzt.7 жыл бұрын
At t=292 you said about too great pressure and back flow. This is a description but not an explanation. What exactly happen with gas in the rotor just before/at/after the moment when this critical pressure is achieved? In particular why after achieving this equilibrium it does not become stable/static without flow.
@EngineeringMindset7 жыл бұрын
before it becomes compressed and heated. At, it finds a route with lower pressure/resistance which means backwards. After, it flow towards the least resistance which is forwards. It can't reach stability because there are different pressures on either side of it and heat is being added or removed.
@gabrielmanut3 жыл бұрын
Saudações aqui do Brasil. Antes de mais nada, quero agradecer e parabenizar pelo conteúdo. Não sei como não tinha visto esse canal antes. Não tinha percebido o "SURGE" dessa maneira. Se não for incomodar muito, poderia responder algumas perguntas? 1- Existe surge por baixa pressão? Onde o "Lift" do compressor fique abaixo do seu limite? Já tivemos casos aqui, que só resolveu corrigindo a vazão no evaporador. 2- A rotação do compressor realmente gira no sentindo inverso? Ou só desacelera? 3- Como posso criar conteúdos tão maneiros com esses modelos 3D? Ficou excelente. Mais uma vez agradeço
@mastadonwesley10423 жыл бұрын
Our Tranc chillers always surged when the auto fill malfunctioned and the return was starved for water causing the condenser to overheat.
@hectortorres542 Жыл бұрын
Thank you
@shaikhmudassirazmi69347 жыл бұрын
Thanks for this video Please upload design of hvac HAP software related video Please sir its a humble request
@franzpaez38827 жыл бұрын
Can you please also discuss about Oil Migration in Water-Cooled Centrifugal Chiller. Thank you in advance.
@WillieMakeit2 жыл бұрын
Thank you very much
@rickyhurtado28955 ай бұрын
Thanks,for good information
@Pito4227 жыл бұрын
again, great videos dude.
@MaTHEUuuS0513 жыл бұрын
It is very useful! Thanks a lot
@thabisopaul5287 жыл бұрын
I want more Industrial practical on refrigeration and air conditioning since I got diploma in mechanical Engineering.
@reyruiz77634 жыл бұрын
Thanks, not everyone take the time to share knowledge these days.
@emanuels.6541 Жыл бұрын
Good stuff. Thanks much
@eulaliorodriguez5325 Жыл бұрын
Thank you for sharing.
@muhammadawaisashraf26292 жыл бұрын
Very good video
@Jgriffin08080813 жыл бұрын
Awesome vid keep em coming
@muhammadawais63367 жыл бұрын
please make vedio abuot cool water chiller expension valve
@BasketballAve Жыл бұрын
Excellent video
@muhammadawais63366 жыл бұрын
please make on video on lastast sorew compressor and that parts.
@patricktsang10413 жыл бұрын
Fantastic video!
@everestinspections9088 Жыл бұрын
great video thank
@kavernianengineering29599 ай бұрын
Hellow, its allowed integrate a variable speed control on existing chiller with constant speed ?
@ToothyGus6 жыл бұрын
Same principle as a centrifugal compressor surge but that one is really scary to stand next to :)
@EastStreetBottleworks Жыл бұрын
What are the differences on how chiller surge occur for an air-chilled system?
@ISLAHIQALB6 жыл бұрын
Awesome quite fabulous it’s great quite
@superinggotv56222 жыл бұрын
Surge troubleshooting in contactor amperage
@hafizshams50776 жыл бұрын
Can you do a more detail video about bypassing the effect of surge.thanks
@jamesskelly33903 жыл бұрын
Add a hotgass bypass line
@menskills63684 жыл бұрын
Why does the chiller surge if the entering water sensor on the evap is bad ? (Changed it because the readings was too high and it worked fine after )
@MrBerniebling7 жыл бұрын
nice content, thank you
@karunakaranreddy72746 жыл бұрын
Could you please explain briefly the VGD in terms of function and control
@EngineeringMindset6 жыл бұрын
Vane Guides: kzbin.info/www/bejne/nF6xZZypnLaFfbM
@Your_searching_ends_here6 жыл бұрын
Frm discharge to oil seperator nd then condenser
@morabitaziz97875 жыл бұрын
thank you for this védio i am from moroco
@kyawmyintthan28694 жыл бұрын
Would an oversized non return valve in the discharge pipe help alleviate this problem.
@khaleejkha40267 жыл бұрын
thanks sir
@vhienandrade53534 жыл бұрын
What caused the chiller trip? By the way thanks to your vedeo
@PunKMeTaLicE6 жыл бұрын
Hi! I am curious that if the condenser water return is too low such as 21-23C , any issues or problems will be appeared? THANKS! Your videos are really helpful!
@EngineeringMindset6 жыл бұрын
Depends on the chiller. Some, older ones, need very stable operation but newer ones are made with variable conditions but still have some minimum and maximum temperatures and pressures. If the chiller approaches these limits it will trip and cut the power to protect itself. Check the chiller specifications
@ahmadjaber28186 жыл бұрын
Hi, first of all it's a great video, But i have a question,does the pressure relief vents prevent some how the chiller's surge? Thanks in advance.
@unclemonster484 жыл бұрын
ahmad jaber they are emergency blow offs in case of a pressure switch failure or issue with the machine keeps running past the fail safe pressures. It vents the refrigerant to avoid vessel rupture
@unclemonster484 жыл бұрын
Surge is just when the machine loses its lift due to being out of its design specs of running. For example someone raises the set point on the cooling tower and lowers the set point below design set point. Your out of balance and the liquid level in the evap will fall there fore affecting the impellers ability to lift the vapor from the lower liquid level in the evap. This is just one scenario, several factors can make a centrifugal chiller stall and surge.
@EngineeringMindset2 жыл бұрын
Seen our new pressure switch video? Link: kzbin.info/www/bejne/j3ibYqpmfauLhMU
@romeopascual61223 жыл бұрын
The chilled water cycle is not completed you need to add. The expansion tank for the make up refill the lost chilled water supply. Thanks.
@karrarkarrar25296 жыл бұрын
why increase pressure in the condenser
@americafirst60164 жыл бұрын
Couldn't surge be cause by adaptive purge not working correctly or not purging enough?
@mmfeiw86644 жыл бұрын
why does it also surge while the load decrease but pressure differential maintained?
@saqibomer24583 жыл бұрын
Add chiller display details video
@abhimat5 жыл бұрын
What is the hot gas bypass line? And what is this word you use often - velute or flute?
@EngineeringMindset5 жыл бұрын
Gas bypass: kzbin.info/www/bejne/gWHbcn6wmbeCe8k Volute: theengineeringmindset.com/centrifugal-pump-basics/
@rajanrai22852 жыл бұрын
Surging setting ?
@yijiangwang57835 жыл бұрын
Could you reply what's the different between this surge system and and condenser tube clean, are they the same system ?
@krish67904 жыл бұрын
Chiller surge can be of any system where the condenser pressure is greater then the compressor discharge.. now these chillers condensers can either be water cooled or air cooled, if they are water cooled you can definitely clean their tubes by carrying out proper shut down operation etc and/or wash condensers if air cooled..
@capitolrefrigerationheatin75017 жыл бұрын
why isnt there a check valve in the discharge of compressor like hermetic compressors have?
@therealmcgoy49685 ай бұрын
What would happen if the fan was not operating correctly in the compressor?
@TheChillerGuysHub9 ай бұрын
Sounds like a high quality shop vac when they surge
@AkinjobiEnioIa3 ай бұрын
Pls what supplied water into the evaporator.... Is it the ahu ? I think what is coming out of evaporator is vapour not water
@EngineeringMindset3 ай бұрын
Water from pressurisation unit. See our chilled water schematic video please. Water comes put out of the evaporator in a chiller, the refrigerant is kept separate.
@mrabby85373 жыл бұрын
Why compressor oil comes in the evaporator, even if an oil separator is installed. Evaporator tube leakage oil, water, and refrigerant mix in my case. I will be very grateful if you make this video by giving the real reason.
@EngineeringMindset3 жыл бұрын
kzbin.info/www/bejne/p6m1eXaYntl_sKs
@mzs92627 жыл бұрын
please answer this , if there is good heat transfer in the condenser as you describing in the video ... then There is only removal of the latent heat ,... The temperature and pressure remains same. Then how we can eliminate the Surging phenomenon please tell...? Because for surging we have to decrease the pressure from the condenser ? Please correct me if i am wrong !!!
@EngineeringMindset7 жыл бұрын
Many things affect this, the supply and return temperature of the water, the flow rate of the water or refrigerant etc etc. If your chiller is surging then you should contact your service provider or manufacturer for assistance asap.
@altamashshh19847 жыл бұрын
Muhammad Zaroon Surging in itself happens when there is improper heat exchange caused by the combine effects of fouling,flowrate variation Etc etc inside the condenser...which directly leads to lower heat transfer and hence higher temperature and pressure build up.So your statement that the temperature remains constant is incorrect
@SombraLocs5 жыл бұрын
What are the causes of a low end surge?
@Rajajaber19773 жыл бұрын
Exclent
@eerie-0002 жыл бұрын
Vanes are already controlling the flow of refrigerant then why a VFD or variable diffuser is required?
@EngineeringMindset2 жыл бұрын
Vfd changes the rotational speed of the motor otherwise its a constant speed
@aboodi2977 жыл бұрын
Can you explain who Low section Temperature happen and what is the reason with solution
@EngineeringMindset7 жыл бұрын
Could be a lot of things, low refrigerant level, faulty or incorrect sized expansion valve, wrong refrigerant used. Best to take some screenshots of the VDU, check the fault code and look in the service manual to diagnose the problem.
@EngineeringMindset7 жыл бұрын
We just covered chiller faults in our recent video! kzbin.info/www/bejne/kKaTfYmMg7OJidk
@gregdaborn46206 жыл бұрын
The pumps should be pushing the water through the chiller, not drawing it through.
Velocity across the impeller increases until it can’t.
@twincam8253 жыл бұрын
Or tower filler coming apart blocking drip orifices top of tower ,
@jeejiean5 жыл бұрын
Thanks for the explanation! One of my chiller here was really troubled by those surging problems. The hot gas bypass, guide vane & VFD compressor seems like cant really coordinate well and suffered from surge tripping while the heat load was dropped suddenly (change of shift in a factory). The chiller part load table claimed that it was able to provide up to 15% part load, but the chiller just refused to run in so low speed (Chiller tripped in around 60% part load) While we are pretty sure most of the parameters (condenser delta T, flowrate, etc) was good during chiller surging, we are deeply troubled by this centrifugal chiller Any idea or thought of this? Thanks in advance for any comment!
@unclemonster484 жыл бұрын
jeejiean what brand of machine? Is it variable speed? Most machines struggle at part load anyways.
@EngineeringMindset4 жыл бұрын
VFD Video is now live! here: kzbin.info/www/bejne/r3azlmqIedmendE