Unused CT core should be short circuited not the terminals. If the other terminals of a used core remain open nothing will happen. Please rectify the concept.
@ErKKJHAwantAsuccesssfulLife9 ай бұрын
Please make video on turbo generator
@electricalexpres9 ай бұрын
Ok
@sanjaykashikar9407 ай бұрын
If 1S1 and 1S2 are used then 1S3 and 1S4 shorting is not required. However if it is not used then it needs shorting.
@sanjaykashikar9407 ай бұрын
If 1S1 and 1S3 are connrctected no need to short other two terminals However in case no external connections are made then shorting of all 4 terminals is essential