So glad I saw this video. Scenario 2 is exactly what I’m have in on my boat and LED wasn’t showing any codes. Compressor doesn’t even gets hot when working like this.
@diegosauda9596Ай бұрын
I have 13 vdc,gas is fine, but...compressor starts humms for 3 sec then shuts off,cycles this way 3 sec on 1 min off 3sec on and so on ,i just wish to eliminate that stupid electronic card, i tried 3 diff ones and non keep the comp running ,do you have a schematic to hardstart the comp. To test how much amp i get on a running comp afetr a minute into cooling??
@freedomtrucker23327 ай бұрын
With an unbreached system ..how does the refrigerant escape?? ..mine will not cool ..compressor and fan are running fine ..I’m having a difficult time with my particular diagnosis ..further to that ..how do I add refrigerant?don’t really see any pressure plugs or caps ..
@ShaunDobbie8 жыл бұрын
If it is overcharged just let out some gas until the suction line no longer freezes.
@tarutamahome4 жыл бұрын
Is a newer Wancool control unit backwards compatible with a BD35F compressor (original unit 101N0500)? They both have FACDCPT plugs.
@user-qe5li3jh2v6 жыл бұрын
Very good my friend
@vitalrage91248 жыл бұрын
what a legend
@iwanthomas39394 жыл бұрын
My Fuse keeps blowing as soon as I turn it on, also was running at high amps before this started happening. Any ideas on this issue?
@zebelliott57804 жыл бұрын
If the system is 12V then the fuse should be 15A. If you immediately blow a fuse it could be that you have a dead short somewhere in the system. Use a multi meter to check the continuity across each of the pins of the compressor to confirm the resistance is less than 5 ohms. Also scratch a small area of the body of the compressor back to bare metal and again check each pin on the compressor to the bare metal to see if you have any continuity. If you do have continuity or high resistance across the pins then unfortunately you will need to replace the compressor
@petermoygannon6983 жыл бұрын
I've got a danfoss cr1110..not cooling the compressor is humming . the fan on the pipes and fins on back has failed . could that stop the fridge cooling.
@zebelliott57803 жыл бұрын
If the compressor is running and not cooling it has a leak in the system, even if the fan is broken I would expect some cooling from a steel cage condenser. It sounds to me like you need a fridge engineer to check the refrigerant
@petermoygannon6983 жыл бұрын
@@zebelliott5780 i don't think you can re gas them easy. sealed unit.
@diegosauda9596Ай бұрын
Buy a clamp on 1/4" valve,at your united reffigeration or grainger ,clamp on add a bit of gas test with 50/50 water soap solution find leak stop,clean,sand paper ,remove pressure, epoxy hole,wait 24hrs regas,and enjoy imported beer. Dont ask questions just read 10 times