Design of Axially Loaded Short Rectangular Column | Rectangular column Design | RCC Column Design

  Рет қаралды 48,946

All About Structural Analysis and Design

All About Structural Analysis and Design

4 жыл бұрын

Detailed Steps of Axially Loaded Short Rectangular Column has been explained, the column is short rectangular column which is axially loaded and is solved by considering minimum eccentricity as per codal provisions of IS 456-2000 along with design of lateral ties.
The Clauses of IS 456-2000 along with page numbers has been shown clearly.
Link of Axially Loaded Short Square Column : • Design of Axially Load...
Link of Axially Loaded Short Circular Column : • Design of Axially Load...
Checkout What is Column, Axial Load, Uniaxial and Biaxial Bending : • What is Column | Axial...

Пікірлер: 43
@mytinyfoods798
@mytinyfoods798 2 жыл бұрын
Thankyou so much sir, your lectures are very helpful for me 🙏🙏
@harendrapaltomar3480
@harendrapaltomar3480 3 ай бұрын
Thankyou sir for such an amazing content with such an awesome dedication
@anandgor4181
@anandgor4181 Жыл бұрын
Very useful and informative video thank you.
@farookali6693
@farookali6693 3 жыл бұрын
Nicely explained thxs.
@ravinandandr8886
@ravinandandr8886 4 жыл бұрын
Best lecture seen in structural pages.👍👍
@structuralanalysisanddesign
@structuralanalysisanddesign 4 жыл бұрын
Thank you for appreciating, keep watching and support us by sharing our content
@halalmeatshophk
@halalmeatshophk Жыл бұрын
Sir u made a mistake. In the IS 456 Clause 39.3, it says that "A.c." in the formula is "Area of Concrete" but at 05:37 you have taken it as "Area of Column". Please confirm if "A.c" is "Area of Concrete" or "Area of Column", thank you.
@sanjibsaha2315
@sanjibsaha2315 3 жыл бұрын
In case of determining the Asc u have considered the new Ag but in case of circular column u considered Ag as the calculated one not the new one(after increasing diameter) why sir is it limited only for circular column pls explain sir...and beside this thank u so much sir for explaining the numerical s and sharing ur knowledge..
@sonukumar-bp4wb
@sonukumar-bp4wb 4 жыл бұрын
Sir can I provide lapping in shear zone in any box culverts type structure
@marova._.chhangte7351
@marova._.chhangte7351 3 жыл бұрын
Nice lecture and very informative and knowledgeable...
@structuralanalysisanddesign
@structuralanalysisanddesign 3 жыл бұрын
Thanks a lot, keep watching and sharing
@soibamkhagemba8245
@soibamkhagemba8245 Ай бұрын
when you take d as 450mm emin aint 20 its greater than 0,05d . so its not satisfying . please explain this
@ojaswinikammili7489
@ojaswinikammili7489 3 жыл бұрын
Sir can you tell me what we have do when the dia in lateral tie is 2 mm which dia bars are used
@SoumalyaBaag94
@SoumalyaBaag94 2 жыл бұрын
knowledgeable video. Provide more. Is there any video on Load calculations of a house? if had, please give me the link. Thank you
@bishwashbartaula9452
@bishwashbartaula9452 3 жыл бұрын
Sir why number of bars is not multiplied with area of steel of 1 bar as u did in square column?
@TheChampionPushpendrarj
@TheChampionPushpendrarj Жыл бұрын
Watching it @ 12:40 AM
@Jaid17
@Jaid17 2 жыл бұрын
❤️
@civilideas1925
@civilideas1925 2 жыл бұрын
👍🏻
@mahmoodabdullah4547
@mahmoodabdullah4547 4 жыл бұрын
You explain clearly thank you sir But still I have doubts You changed breadth as 400mm, but you didn't check minimum eccentricity with this formula (l/+500 + b/30) why You changed depth as 450mm, but you didn't check minimum eccentricity with this formula (l/+500 + d/30) why
@structuralanalysisanddesign
@structuralanalysisanddesign 4 жыл бұрын
As it was not satisfying the axially loaded criteria it has to be designed as eccentrically loaded column, but after this stage i had considered 20mm as minimum eccentricity and solved as axially loaded column. Academically we can solve like this but practically the column has to be solved as eccentrically loaded column
@mahmoodabdullah4547
@mahmoodabdullah4547 4 жыл бұрын
@@structuralanalysisanddesign eccentricity loaded coulmn means long column? Or different one
@kshitijpatil9305
@kshitijpatil9305 3 жыл бұрын
@Picture Perfect Studio bhai tu photos click kar jaaa
@mr.engineer3314
@mr.engineer3314 3 жыл бұрын
b = 400mm is wrong. When u put b= 400 in the equation, l/500+b/30, we get, e= 22.33 and 0.05×400= 20. e(min) > e(max) not OK.
@sh.joyshankersharma9611
@sh.joyshankersharma9611 2 жыл бұрын
Bro, here we need to consider e min as 20 because if it exceeds 20 we consider e as 20, and if it is less than 20 then we consider the gotten value.
@debangangoswami7092
@debangangoswami7092 Жыл бұрын
sir why dont you mention about spacing of longitudanal bars , is it not neccessary to specify it
@yangchinlhamu210
@yangchinlhamu210 3 жыл бұрын
Nicely explained sir👍🏻 sir can you tell in which cases we are supposed to assume 1%of steel. Becoz I have seen in some cases they aren’t using 1%of Steel.
@kwalicks
@kwalicks 2 жыл бұрын
when dimensions are not given
@vvbvb094
@vvbvb094 4 жыл бұрын
Can you upload the design of combined footing with eccentric loading?
@structuralanalysisanddesign
@structuralanalysisanddesign 4 жыл бұрын
Will soon try to workout on that topic
@dhavamanikrishnan293
@dhavamanikrishnan293 4 жыл бұрын
Sir, Please explain about ductility calculation for column and beam. If you done please provide the link. Thank you.
@structuralanalysisanddesign
@structuralanalysisanddesign 4 жыл бұрын
I will try to make on that topic
@kezangtobgay8601
@kezangtobgay8601 3 жыл бұрын
is the assumption , b=D÷2 , compulsory ? can we take other ??
@halalmeatshophk
@halalmeatshophk Жыл бұрын
it is just an assumption that was analyzed and failed. So second assumption was made later.
@earthbees
@earthbees 4 жыл бұрын
Sir please put on a videos for stair design
@structuralanalysisanddesign
@structuralanalysisanddesign 4 жыл бұрын
Soon i will try to upload it, right now focusing on columns, after columns surely i will upload
@earthbees
@earthbees 4 жыл бұрын
@@structuralanalysisanddesign waiting for your next design of column.... Please quickly uploade it
@ParthaPratim-xc9ir
@ParthaPratim-xc9ir 11 ай бұрын
I dont understand why in Re Design we will take b = 400 . Someone please answer this 💢
@Jaid17
@Jaid17 2 жыл бұрын
Sir sorry to say... little bit u r skipping..... otherwise superb
@abhinavashish1807
@abhinavashish1807 3 жыл бұрын
abe galat krr rha hai...emin ki value to change hoga na
@structuralanalysisanddesign
@structuralanalysisanddesign 3 жыл бұрын
First try to have sense to speak
@aizen9462
@aizen9462 Жыл бұрын
Sorry to say but Wrong explanation.
@prof.pravinspatil1727
@prof.pravinspatil1727 Жыл бұрын
kzbin.info/aero/PLtElM8k8rEY2QYenIfyVW-_lZmw3S1pKu
@Busyguy1119
@Busyguy1119 4 ай бұрын
What is wrong in this can u please explain?
Design of Square Column with Uniaxial Bending using SP 16 | Column design with uniaxial bending
17:16
All About Structural Analysis and Design
Рет қаралды 50 М.
لقد سرقت حلوى القطن بشكل خفي لأصنع مصاصة🤫😎
00:33
Cool Tool SHORTS Arabic
Рет қаралды 27 МЛН
ПРОВЕРИЛ АРБУЗЫ #shorts
00:34
Паша Осадчий
Рет қаралды 7 МЛН
Design of Axially Loaded Square Column | Short column | Design of RCC Column | Column Design
17:53
All About Structural Analysis and Design
Рет қаралды 123 М.
10 Basic Rules of Column Design -  Don't Forget Basic Rules of RCC Column
13:09
NSCP 2015: Design of Concentrically Loaded RC Short Column
36:51
DeanZano Civil Engineering Lectures
Рет қаралды 20 М.
Basic Rules for Lapping length in Column - Lap length in RCC Column
13:34
Design of Uni-axially Loaded Column| Solved example|
19:37
cwill structures
Рет қаралды 36 М.