Instead of the tape you used , try some 2-4” tall strips of tin. Screw into existing ductwork that’s too short & into the unit. A more permanent duct extension , you could duct seal it afterwards too.
@charlessolazzojr67672 жыл бұрын
Mike, Joey's comment short of lifting RTU and addressing curb is the best option. Galvanized sheet metal strips is your least evasive move. 4 strips, 1 for each side to fill gap. I'm not able to see if you have enough overhang to put a 1/2" 90° break on each piece to butt up against the underneath overhang if you have any overhang to begin with. Before using selt tapping sheet metal screws you can decide if you want to apply caulking to the back side of strips, I would before applying sheet metal screws. Don't use silicon caulking, it garbage for this type of repair, use a good caulking for the conditions this repair will be subject to in all weater conditions.
@Lewdacris916 Жыл бұрын
POOKIE
@ferreiraplumbingandheating13232 жыл бұрын
Sheet metal panning , strip it in with 5/16 zip screws then mastic tape over it or duct sealent
@oilburner99892 жыл бұрын
Should have told the kid to MOVE the fucking ladder or go wash dishes.
@Mike-hs8fq2 жыл бұрын
Keeping it real with the good the bad and the ugly. That's what I love about your channel. From the comments below I'm sure we all learned something valuable.
@JM-iu1yg2 жыл бұрын
When I was doing HVAC. I always had a roll of tin 4" and 6" wide for such occasions. Cut to length. Screw in place . Caulk the joints. If it moves again. Just relocate the screws!
@michaelmcewan50742 жыл бұрын
Sometimes the manufacturer has a drain plug in the center of the drain pan. At which point you can use that as your drain line but you’ll have to drill through the curb to run the line and establish your termination. Carrier RTU’s have them I’m just not sure if Rheem does, couldn’t tell from the video. Thanks for the video Saint Mike!
@eddiew.64852 жыл бұрын
That Drop from the pole to the structure was definitely live…….
@throttlebottle59062 жыл бұрын
here's my large electrical cabling cutters, give it a snip and see. (yeah DO NOT) very much excitement would occur, as the cable and tool turns into a fireball of long burning arc-flash, until it either fully burns in half or melts down upstream butt splices/connectors and they'll do that just that after a long period of buzzing, smoking the coating off, etc. I've seen service entrance cable below meter used for chaining up a dog! it yanked enough it shorted one hot leg to the ground braid and burnt the meter up and the whole cable on the home and 150 feet across the yard on three poles to the transformer, where it eventually burnt out a butt splice! it was a rental property and they're like can you fix it? someone else was there and only quoted them a main breaker. YIKES that was not a good conversation we had, the place nearly burnt down and I called for emergency disconnect of the rest, the other hot leg was still live!
@funbricknj2 жыл бұрын
sheet metal strips tall enough to cover the gap with a 1/2 inch bend, the put the double-sided sponge tape on the 1/2" side and press it to the top to seal there then sheet metal screw the sides, then tape the joints
@georgesummerlin16022 жыл бұрын
That is definitely high voltage. That's the triplex coming from the transformer on phone poll. Lol
@hartsfire57062 жыл бұрын
you did a good job with what you had to work with. you are right the real way to fix it would be pull the hole unit off of the roof and put a new Curb adapter in.
@demijenkins94862 жыл бұрын
Your kindness is a balm to all who encounter it.
@arthouston73612 жыл бұрын
Mike, you can’t rely on the insulation properties of a triplex power drop to maintain its integrity when exposed to weather. Putting your hand on that or touching it in some other fashion can indeed result in an electric shock. All you need is a pathway the size of a small pinhole. That bundle is the power for that building coming from that pole.... so yes, you want to avoid something like that, or……put approved insulation sleeving over it before you approach it. Some people think that a voltage such as that won't kill you, and those people are wrong. All you need is for your heart to go into fibrillation, and without an AED, you are dead before the ambulance can get to you are use their AED they have on the truck. Also, the real fix, as you probably know, it to re-curb for that unit. Many malls do not allow the use of curb adapters because of water issues.
@throttlebottle59062 жыл бұрын
yeah, they should stay away from it. but in reality they'd have to grab it with two hands or be touching something else grounded and grab it. the bigger issue is it's not fused and could become a nasty arcing fireball if it got shorted somehow, also any of the wiring there is a tripping hazard and could make you do a header off the roof. unless you're some crazy parkour person, taking a header off a roof never ends well.
@arthouston73612 жыл бұрын
@@throttlebottle5906 Actually, it only takes one hand. You would be shorting one of the hot legs to that messenger wire.... which is the neutral.
@throttlebottle59062 жыл бұрын
@@arthouston7361 yes that would shock you're hand, possibly cause arcing and maybe a fall from the ladder. the fall may very well kill you, but single hand touching at that voltage wouldn't, unless you have conductors ran around your body or are grounded at some other point. the power would stay localized in you're hand/arm end.
@arthouston73612 жыл бұрын
@@throttlebottle5906 Not true. There is a very high chance that hand shock sends your heart into V-fib. See above. The fall of 12 feet from the roof in question might kill you, but the V-fib will definitely kill you unless that rhythm is restored in under 10 minutes. We learned how to not die in lineman school, and I still practice that level of safety as a commercial HVAC tech today.
@michaelt1512 жыл бұрын
At 240 V with at least 200 A . NO BUENO!!!!!
@GreatCanadianGoose2 жыл бұрын
The right way is replace curb adapter but I had this issue and I ended up using sheet metal around supply and return screwed to the unit and folded to mate with seal on curb adapter
@ToxicwasteProductions2 жыл бұрын
I would use foam seal :)
@RobertKohut2 жыл бұрын
The wires your ladder is near is called a triplex. It has two 120 volt wires and one neutral. The bare conductor in that bundle is the neutral and can carry current is some circumstances... :-)
@dc62332 жыл бұрын
Unfortunately the curb or adapter needs to be fixed. BUT, those pans are usually reversible, and there isn't much holding them in there, I've ran into this and I shimmed the drain pan up on one side and shot some 5/16ths self tappers in it - up high, to hold it. I think I had to chop off a piece of the plastic pan that sat in a grove but it sure was easier than raising the whole unit. If the ductwork was installed correctly there's often enough play in the canvas that you can move the unit a bit up/down/sideways etc. Lots of guys don't even use a canvas though, or they do but then they lock it in place with hangin strap so you can't always count on that...
@mattfromtexas94102 жыл бұрын
Definitely leave curb alone unless you are ready for a proper fix. I always create a foot for the drain pan it can be all kinds of un-level on the outside all it wants but you definitely can create fall depending on type of unit some screws might need moving and stuff like that also depending on weight you will have to choose the correct material but start at the back of the drain pan work your way towards where the water exits. Create your own fall underneath the pan leave outside alone till proper repair can be.completed. The foot underneath the pan is always a good idea to get you thru.
@miguellopez-mp5fg2 жыл бұрын
Looks like you need a proper curb adapter made to the pitch of the roof so it sits level .I would extend the duct up or put a flex connector so the duct has a tight connection.
@codywiggins93872 жыл бұрын
He's got a set of balls setting the ladder up there that's for sure.
@twolfe42952 жыл бұрын
You could have a custom curb made and replace the one the unit sits on. Crane charges + curb + time = X$. Most new RTU"s are longer in the condenser end even though they fit an existing curb. Had one similar that a wind storm lifted the end of the unit up off of the curb and only had to use a pry bar to reset it.
@joemaxfield932 жыл бұрын
Maybe add a little ductwork on the low side of the drain pan so it’s higher now
@dirtywaterstd68312 жыл бұрын
Go to truck and grab jack from wherever its located. I always carry pieces of two by four. jack up unit after disconnecting gas pipe union. Make sure your electrical is free or has play. Jack up one side and add insulation foam tape, the thicker the better so doubling it up works too. Jack stands with four by four wood is good for safety. place blocks of wood in space to allow you to get cross member insulated fro supply and return.
@ktk5752 жыл бұрын
Hard to say what to do if the roof settles after the installation, we usually have the curb adapters made for the current roof pitch.
@ktk5752 жыл бұрын
maybe some duct board strips cut to squeeze in the gaps then silver tape.
@gomerhondo72492 жыл бұрын
You need a flag / Bosch sticker over the Navien advertising on the van.
@throttlebottle59062 жыл бұрын
that's a temporary fix, the unit is way too large for the curb, with too much weight in the "flying buttress" on stilts. that end is smashing the roof deck down, it may not be overtop any structure and wont quit sagging, it may even punch holes through the roof. a further temporary hack, would be using some 2x4's built up to a 4x6 or 6x6 to spread the load out far wider across the roof, but that would trap water and not be good for the roof, even if the wood was notched every so far to allow water drainage. for the duct and curb extension, cut tin into bands and screw it in place. *proper way? they need a new roof with a larger curb installed, connected and properly supported by the structure below. they may be able to just correct that one area and patch it in, if the roof and structure is good.
@dc62332 жыл бұрын
Ideally they should have bought a curb adapter, who knows if the S + R are even lined up or if 1/3rd of them are cut off.
@michaelsandford29602 жыл бұрын
Take 2 pieces of unistrut cut on side off on each piece sceew together slide it in gap anchor it to curb then use your mastic
@Capt41412 жыл бұрын
Absolutely that triplex was power, was it possible to retap the drain pan on opposite side?
@konstantinostsoukalas3622 жыл бұрын
Well Mike not many options. Crane lift level curb adapter drop the unit have a nice day.
@brettwing7372 жыл бұрын
Could you pan it off with sheet metal or not enough access? Maybe pan it off then have a roofer go up after and seal over the area you pan off with membrane or use vulcan? Idk didn't get to good of a look at it.
@ICONBADGTA2 жыл бұрын
Just use some pieces of sheet-metal cut then tape/seal it or use mastic-paste... Then once unit gets replaced on down the road, fix permanently..
@waitikubuliwaitikubuli61802 жыл бұрын
Mikey pipes ,the wielding kit and solder, daneil is using....is it possible to give a link to order the lot.... Is it a propane tank or exceiterylñ...
@alexibonnet26342 жыл бұрын
You do what you have to do to get the job done . Too bad it was not a Lennox package unit. (Depending on unit model # With Lennox you have the option to drain from the left or right side.
@AIMANNY2 жыл бұрын
That is live wire.
@Mr.unknownx12 жыл бұрын
Are you going to get into refrigerator and freezer rooftop for restaurant
@redneckbryon2 жыл бұрын
I'm surprised you still have a Navien Nticker, on the side of your van.
@russellhill59592 жыл бұрын
Tape for quick fix. Take measurements for pressure treated 3 to 4' wedges. Tape tops of wedges with black deck tape. Come back during next service call and replace taped quick fix with wedges.
@walterbordett20232 жыл бұрын
The unit sagged because there is weight on the compressible roof insulation. The RTU should be fully supported to the structural deck and framing. the unit may have to be pulled and reinstalled with structural and roofing corrections. If there need to be end supports, they need to extend through the roof into the structure, and be professionally treated as a roof penetration with an engineered roofing flashing solution. You are in the position of putting lipstick on a pig here. .
@dc62332 жыл бұрын
"Some" roofers do a great job, and some are absolutely horrible. They should have the unit on 2 x 6"s on the metal deck and spanning a couple trusses. I never cared where the print told me to put the RTU, unless the electric was roughed in already, I put them where I wanted and made up the ductwork to fit the register layout. I always loved being able to move things around when it made sense, these engineers go off of very old prints, they don't know what's been done to the building.
@goodtimes26542 жыл бұрын
2" x 90 degree angle (tin or light gauge stainless ) around the duct between the unit and the duct, gasketed against existing duct and unit bottom, zip screwed into the existing roof curb or duct ( not bottom of A/C ) silicone or roofing tar any seam or joint. Will outlast the unit .
@b3d3g692 жыл бұрын
Was there anyway you could just prop something under ther evap tray ton pitch it foward?
@gomerhondo72492 жыл бұрын
That was 220V power. Those are power poles (telephone typically rent space from power company).
@BoilerMaker56 Жыл бұрын
A custom transition that a sheet metal shop could make up would’ve been ideal for this curb. Then you could’ve had it pitched the opposite direction.
@MoonRambo7022 жыл бұрын
Shoot some great stuff foam in there 😂
@DevinHVACInc2 жыл бұрын
Sheet metal with screws then tape
@SuperVstech2 жыл бұрын
Also, the stands in place now sitting on those boards, it will settle again. THe wood needs to come out, and a more durable support needs to be put in.
@davidseymore34112 жыл бұрын
should have leveled curb adapter. before setting unit
@Drtbiker882 жыл бұрын
Spray foam the gap for insulating purposes, shave it down. Bend up some sheet metal with 90's and self tappers with silicone at the corners and top of screws. Should outlast the life of that unit
@sh26972 жыл бұрын
so Im not sure what you did to tilt it?
@pomonabill2202 жыл бұрын
Air Force is sure good lookin' !!!
@tdadp2 жыл бұрын
It’s a Band-Aid fix one That has me starching my head . I hate to say Repitch the roof but it’s suck because of the cost to Repitch the roof
@atlasfueloilinc.24212 жыл бұрын
I sawed my boat in half. No way. Not a hack a band aid. the repair will be to install 2” by 4” angle sheet metal that has room to adjust more in the future. If needed. It is what it is. Fits here. Nice
@laker32 жыл бұрын
Sheet metal is the best option.
@hvacshinobi80472 жыл бұрын
Should of put mastic over the tape. Also should of showed what you did.
@jenko7012 жыл бұрын
Fill the gap with metal and seal with appropriate mastic.
@10minutenewhampshirebreak772 жыл бұрын
Unfortunately he’s got to get a roofer to come refit the curb sleeper, or remove the rtu and try to patch up the curb
@marielatour13842 жыл бұрын
Very attractive❇
@BartlettTFD2 жыл бұрын
Simply jack up the BUILDING an inch or so, condensate then flows properly, PROBLEM SOLVED😂
@cody54952 жыл бұрын
Can't you just change the angle of the drain pan and leave the unit out of level?
@Tanneritefilledfido2 жыл бұрын
That was a real low roof, should’ve just set in front of the sprinter and that rheem unit should really get lifted with tin knockers correcting the curb
@timothywalch71022 жыл бұрын
I wouldn't modify the drain pan wedge the drain pan that way you keep it nice tight seal on the curb clearly the business needs to get a new roof it's pitched up right but the train pan would have been the solution I would have gone with please try to
@jimhvac31212 жыл бұрын
Use vent glass to take up the gap
@billmiller50752 жыл бұрын
Make sure that trap is installed correctly, if not it will leak for sure.
@oldskool19792 жыл бұрын
why are you advertising NAVIEN on your vans ??
@johnhaydt75632 жыл бұрын
Seal the duct gap with duct sealer aka "pokey"
@doncaranci25472 жыл бұрын
Almost 40 grd buddy WTG
@ares39142 жыл бұрын
Flash off the the gaps with sheet metal tape and pookie. Of course its gonna take about 2-4 hours to do the job you'll have to cut small peices of sheet metal and screw it from the unit to plenums. Once you flashed all 4 sides of each supply and return plenums tape with sticky tape and pookie what you tape and that's life time fix at least for the life time of the ynit
@katysalter20212 жыл бұрын
Smokin Looking Superb (as always)
@mattmcdermott55392 жыл бұрын
1x1 angle is what I’d use just screw 2 pieces of that to it and call it a day
@nicholasbarrett76472 жыл бұрын
Strips of metal and spray foam, hack but real world situation. 99% of customers will not pay for proper repair
@JM-iu1yg2 жыл бұрын
NAVIEN BUMPER STICKER ON VAN !! !!!!!!!!!!!!!!!!!!!!!!!!!! I'M TELLING BOSCH!!!!!
@joea22742 жыл бұрын
Sheet metal is your friend Mike
@kennethnapier1312 жыл бұрын
Frankly, we would have removed the unit, corrected the curb, and reset the unit.
@Mr.unknownx12 жыл бұрын
I didn’t know that you do rtu
@clarkgwozdecki6782 Жыл бұрын
If you sell these rheem package units with micro channel plan on doing warranty work every year. those coils suck
@HVACGUY2 жыл бұрын
Hmm 🧐.
@michaelkuprian012 жыл бұрын
Try to raise the backside of the coil. Just an opinion
@frankstumbo17712 жыл бұрын
You should have shimmed the coil/pan. It would have taken a lot less effort
@dc62332 жыл бұрын
Easy peasy, they can be flipped so not much holds them in place...
@ThePappas332 жыл бұрын
I would say in this particular case that you made the rite decision to go with the jack and tape..otherwise we are talking about unnecessary cost for a piece of equipment that's only has a few years left cause of poor maintenance .. way to go Doc.....
@Mercmad2 жыл бұрын
Who was that ? the next John Holmes?
@racecar14792 жыл бұрын
Flex seal.!!!
@DevinHVACInc2 жыл бұрын
U need to put a Bosch sticker Over that WHJ on your truck
@SuperVstech2 жыл бұрын
I would tell the customer they need a proper curb…
@uspatriot95992 жыл бұрын
So i see your son is back working with you?
@lyndalawley20032 жыл бұрын
💗
@noracox34102 жыл бұрын
love 😘😘😘😘😘😘😘😘😘
@tmacgee12342 жыл бұрын
Patch sheet metal, mastic on top.
@RAYMOND1692 жыл бұрын
Spray foam
@adamedwards24352 жыл бұрын
Pipes is very entertaining.👏
@milotorres68942 жыл бұрын
Hack install from the beginning on the retrofit piss poor craftsmanship who ever installed did not level the connection to the unit , condensate pan pointed that out no need to work curb just level cap cover to unit connection and seal according to condensation drainage to avoid trapping moisture catch , legs on retro should have a full runner on roof catching trusses depending on runs for proper support of over hang of unit... Maybe the gist of situation , foam in behind tape , cut fill in strips of metal to cover foam retrofits inheriting a headache for sure on little jobs . A full roof jack should've been included on original retrofit bid... 😆 just my thought process..
@russhemp37542 жыл бұрын
Shim the drain pan
@addisynhull21652 жыл бұрын
💪
@stephwaylonwells32182 жыл бұрын
👍
@TheJimbob16032 жыл бұрын
Why are you advertising Navien on the side of your truck? Just to piss 'em off? Lol! Go Bosch!
@Silky_boi2 жыл бұрын
Tape and pookie!
@beverlydentdent28602 жыл бұрын
cool!💝 top
@mauikawi42902 жыл бұрын
good shit, good enough for that place. fun the haters
@OleRazzleDazzler2 жыл бұрын
Silicone
@cthomaspac2 жыл бұрын
To really do it right , you have to rip out the old curb, and install a new curb. Otherwise it's 2" angles ,screw's and silicone.
@mustangmike64212 жыл бұрын
Duct board and pookie
@williamdwyer33022 жыл бұрын
lesser of the two evil's.until when or if the customer is willing to pay for permanent solution.