@CptEcho
@CptEcho 14 күн бұрын
This is completely normal for an AC coupled grid tied system. Loads turn on / off instantly but inverters (both by design and by Grid code standards) have a set maximum ramp rate, e.g. if ramp rate is 200w per second, and you turn on a 2kw load, it will take 10 seconds to hit inverter outputing 2kw. And then the same in reverse when turning off load. Multiply that my dozens of devices constantly turning on/off, increase / decreasing load and what you get is a constant ac couple tug of war. Your solar analystics and grid meter data is also only showing you these fluctuations rounded to 10/30m intervals, but its actually calculated internally to 1 second intervals. I have much more accurate data from some of my ac coupled systems which show this and might make a good video if you are interested
@ivanblogs
@ivanblogs 14 күн бұрын
This. The control loop in the inverter to alter output current in an effort to zero the grid feed isn't perfect. They're often in the 1 second update range, and quite damped to avoid oscillating. Switching on a load can take several seconds before the inverter cancels its mains draw. You'll also export a bit after the load switches off. Hot plates, ovens, water pumps, refrigerators and other short cycle devices exacerbate the issue.
@BenBrand
@BenBrand 14 күн бұрын
But wouldn't it be 200w per second in both directions? It would still average to 0w draw on average. To see an average import with 200w per second ramp up the ramp down would have to be faster, say 500w per second?
@CptEcho
@CptEcho 14 күн бұрын
@BenBrand there is no averaging for metering / billing, you are charged/ recorded for every second, which is then summed (not averaged) into the 30m blocks of data reported. So in a theoretical 30min block if you export 1kw for 15mins and import 1kw for the next 15mins, the average is 0, but you are charged / credited for both 1kw import and 1kw export.
@BenBrand
@BenBrand 14 күн бұрын
@@CptEcho yes, but it doesn't look like that's what's happening? It's rarely zero and never negative. I can see how if it ever does go negative it would just stay at zero since he's not allowed to export. But if it truly was even in both directions then it would be zero about half the time and positive about half the time?
@CptEcho
@CptEcho 14 күн бұрын
@BenBrand that's not how this meter records data, it has a seperate export register and an import register, in the video he is only showing the import register which is why it pegs to 0 when exporting, if the data was combined into a single graph you would see half hour intervals of import, half hour intervals of export and most importantly half hour intervals with both import & export.
@RossHogan1
@RossHogan1 14 күн бұрын
Try plotting the solar production along with your consumption. You'll find your consumption goes to zero when you are exporting significantly, say >1kW. As for the other spikes, the Deye inverter doesn't respond very quickly to a step change in demand. You can test this by putting the kettle on. You'll consume from the grid while the Deye increases it's output to match the load and then you'll export while it decreases it's output. Don't have a good explanation for why the rest of the input is so high though.
@electrodacus
@electrodacus 14 күн бұрын
You only get zero in the middle of the day when you likely export to the grid. 30 minute intervals is just way to coarse to see anything. It is most likely the inverter that can not respond fast enough to changes in load power so it briefly imports energy from the grid. It could be just a second or even less but enough for those spikes to be recorded by the smart meter. Thus what seems like fairly random data. You can see that at night imported power is fairly constant and much more variable during the day. So is the inverter that can not guess when a load will switch ON and it needs some time to react and correct the amount of imported power.
@TheCreat
@TheCreat 14 күн бұрын
While I agree with others that 30m is too coarse for a detailed hunt for the cause of the drain, I disagree that it's the ramp rate. That just makes no sense if you actually do the Math. Let's say there were appliances that frequently pull 2 KW for a short time, incurring a ramp rate as was suggested by @CtpEcho of 200 W/s (which seems rather low to me, but I live in a different country with different electrical codes). Since a fully linear ramp is equivalent to half the "ramp delta" for the same duration, that would be 1 KW for 10s, which is 0.0027 KWh. How many of those "ramps" do you expected to have over a day to get to almost 2 KWh total? About 740, so roughly 1 per 2 minutes (ish). Yea right. That would be literally insane appliance behaviour. I mean I don't know your electric loads, but we have everything electric, so no gas or other fossils used or even installed at all, and no AC. Even a dishwasher, washing machine, dryer or whatever will never pulse to such an insane degree. We also have smart plug monitoring for most larger loads (except the cooktop and electric water heater), and can just see that on a per second basis. For value comparisons, we also got a solar installation (only ~7.5 KWp, but smaller battery of only 7.8 KWh or so), and on days where we are as self sufficient as possible we're on 0.1 to 0.2 KWh grid usage. 1.8 is WAY too high for your setup IMHO. I would say throw some smart plugs into the monitoring situation (they are cheap enough with monitoring these days), and see how your actual loads behave. It might be that the reaction delay to any change (before the inverter reacts at all) is misconfigured? Or the ramp time is off by like an order of magnitude for some reason maybe? I would go over all the settings, but without knowing what your load profile looks like that'll probably be hard to identify...
@bartgrefte
@bartgrefte 14 күн бұрын
Why get data from the provider instead of straight from the meter's interface that it seems to have? Though could be mistaken.
@cads877
@cads877 14 күн бұрын
Thanks for the use of the term " Electric Boogaloo" . Needs to be incorporated more often into modern day of language.
@EEVblog2
@EEVblog2 13 күн бұрын
Indeed.
@mikesradiorepair
@mikesradiorepair 14 күн бұрын
You have to read the fine print that comes with the smart meter. It comes preinstalled with a electron gremlin. It was trained at the factory to only eat electrons from the grid. Solar electrons give it gas and no one likes a gassy gremlin. What you have measured here is the electron gremlin input.
@willdutt
@willdutt 14 күн бұрын
🤣
@2001pulsar
@2001pulsar 14 күн бұрын
Turn off the grid for a day or two and see what the meter says.
@IanScottJohnston
@IanScottJohnston 14 күн бұрын
With my set up, because I pull data from several systems, they don’t all respond at the same time, in fact my battery data comes from the cloud rather than direct from the inverter itself (yeah I know!) so it can produce some rather unusual wtf readings sometimes.
@pdath
@pdath 14 күн бұрын
What is the power factor of your home? Could this be the difference between one system measuring real power versus the other measuring apparent power?
@alch3myau
@alch3myau 14 күн бұрын
Inconsistent axis over various graphs trigger the OCD.
@LawpickingLocksmith
@LawpickingLocksmith 14 күн бұрын
No free lunch here. Somebody gotta pay the dodgy fee.
@Brian-L
@Brian-L 14 күн бұрын
Are you able to carefully manage appliance usage and go full off grid for ~24 hours?
@EEVblog2
@EEVblog2 13 күн бұрын
No, we don't have an AC coupled battery backup.
@helenwebster9445
@helenwebster9445 10 күн бұрын
Allen David Rodriguez Cynthia Robinson Amy
@wobblysauce
@wobblysauce 14 күн бұрын
Have a look at the scale of the graphs 0.45 highest, 0.06 lowest. but that 12th spike wasn't big in comparison.
@sayanchx
@sayanchx 14 күн бұрын
Smart meters are notoriously inaccurate especially with harmonic noise... Maybe an opportunity for you to try out a power quality analyzer / monitor
@pdp11
@pdp11 11 күн бұрын
Funny how these inaccuracies always turn out with the electricity provider getting more money. Incredible coincidence.
@LordOfCoding
@LordOfCoding 13 күн бұрын
The algorithm to select which power to "exported" from a battery to an AC system is always behind the actual usage. Take for example when a fridge turns on. it will introduce a peak then most likely it will overcompensate by providing little bit to much power etc.
@freman
@freman 14 күн бұрын
have you considered lead/lag? when you switch a load on the inverter can take a moment to pick it up and compensate by outputting more.
@christopherstaples6758
@christopherstaples6758 13 күн бұрын
yeh the AGL meters , I gave up working mine out after a month of not getting any matching data to my own data collection
@contemporiser
@contemporiser 14 күн бұрын
could this have sometning to do with reactive power? !
@MikeSmith-sh3ko
@MikeSmith-sh3ko 14 күн бұрын
I think you are chasing mo moos Dave (microns) slang😂
@SwordQuake2
@SwordQuake2 14 күн бұрын
The quite regular spikes are also pretty interesting. Are you doing something energy intensive that consistently? Or maybe it's something on a schedule.
@MrTripcore
@MrTripcore 14 күн бұрын
Does he still think they don't steal
@chasingcapsaicin
@chasingcapsaicin 14 күн бұрын
ADW200-D16
@James-wb1iq
@James-wb1iq 14 күн бұрын
It's elves.
@Kris_M
@Kris_M 14 күн бұрын
The "usage" graph is probably aggregating instantaneous samples of supply or demand separately, while the Excel data is all samples aggregated into 30 minute time buckets. What is actually being billed to you?
@elvinhaak
@elvinhaak 14 күн бұрын
It can be only synchronising-issues between your home-system and the grid. The electronics have to synchronise quite a lot depending on load but also on the grid. Especially with switching power-supplies in use, it will constantly need to synchronise and therefore put some small amount of load on the grid unless you can mechanically decouple it and later couple it back on. One of my inverter-battery-systems is using this and with a delay of 20 minutes unless significally overloaded. It just switches itself from the grid (relay-based) and checks again after at least 20 minutes. That now makes it really 0W overall. With this off, it was creating small loads all the time enough for the smart-meter.
@CandyceBuris-x5z
@CandyceBuris-x5z 12 күн бұрын
Glennie Islands
@aaron_11111
@aaron_11111 14 күн бұрын
Three further reasons for low level usage: 1. The BMS can request charging to balance its cells or to protect the battery from becoming over discharged (on my battery at 10% further use is prevented and at 6% SoC the BMS requests a slow charge to bring it back to 10%). 2.There is inverter lag (the time difference between a load starting / stopping and inverter changing its output power to match). 3. CT / Meter out of calibration. Inverter lag at least for me was improved by a firmware update. There is usually CT compensation settings which can be adjusted. In your case the CT might be reading too low so the inverter not fully catching loads.
@ascot4000
@ascot4000 14 күн бұрын
As neither the smart meter or the inverter/battery system measures power directly the voltage & current variations between them will add additional noise to the data, beyond that of the pure MID accuracy rating, as you pretty much covered already. Arguably the additional need to measure supply voltage and (simplifying here) raise it for export, balance it for 'zero' and lower it for import adds additional noise as the inverter/battery system cannot presume the supply voltage and has to sample it regularly. I presume that the inverter will have a set limit so that it does not chase the supply voltage spikes to above the regulated supply voltage, dropping the output and resampling until within limits. As an aside, here in the UK my supplied voltage is always very near the upper legal limits as it is advantageous to the suppliers. [UK = 230v -6% / +10% (or 216.2 to 253.0v). The lowest I have ever seen is 239.57v and is usually in the 247 to 250v range. Last month's highest supply voltage was a sparky 254.53v. The Dilithium Crystals can take it, apparently. Phase management is another active system at play as the battery/inverter system will need to tune itself to the (relatively minor) phase fluctuations on the supply side. As with voltage and current measurement the inverter/battery system will respond somewhat in lag as it has to sample the incoming before tuning the export to the grid. This 'input sample & export' cycle will also show as a tiny import reading may also add additional noise that trends towards an import measurement. Of course, everything needs to work as intended too... my SolarEdge system has basic mathematical errors in the displayed calculations.
@TubularNut
@TubularNut 14 күн бұрын
All your graphs have different scales, so can’t compare days directly.
@rosskirkland3089
@rosskirkland3089 14 күн бұрын
If optimisation towards zero net import is a hugely important goal, would it be worthwhile to prepare a power duration curve & payback calculation on different peak power output battery options?
@anthonywilliams7052
@anthonywilliams7052 14 күн бұрын
That graph at 1:34 looks far too consistent unless clouds haven't been invented for the Aussies. For us in Ohio most days are a white haze now, can't see the Sun or Moon most of the time for the past 15 years, now back to normal the past 2 weeks. I won't say why but 757 size planes come in from the NE, leave something behind, and go back to their start point. Closest airport 130 miles that direction.
@AIM54A
@AIM54A 14 күн бұрын
Wonder how much money they're making on that "little" error across all their customers.
@alch3myau
@alch3myau 14 күн бұрын
I just clicked this because I saw the graph and numbers and tables...
@alch3myau
@alch3myau 14 күн бұрын
1:20 .. whats with that audio? Is it my speakers?
@EEVblog2
@EEVblog2 14 күн бұрын
Yah, I can hear some funny business going on with my mic.
@borisjohnson6809
@borisjohnson6809 14 күн бұрын
Hot water timer??
@jaro6985
@jaro6985 14 күн бұрын
He has a dedicated current clamp for the hot water.
@EEVblog2
@EEVblog2 14 күн бұрын
I have a heat pum that switches on at 10am for a few hours, 1kW draw.
@TobyRobb
@TobyRobb 14 күн бұрын
I'm assuming these are not three-phase values and you're looking at the single phase? Might be time to get some more metering equipment. I tested many many meters working on the network and almost every single one was very accurate.
@alch3myau
@alch3myau 14 күн бұрын
@@EEVblog2 Wouldnt have that issue with a gas HWS.. ;p
@EEVblog2
@EEVblog2 14 күн бұрын
@@TobyRobb Yes, single phase.
Hyundai IONIQ Keyfob Teardown + Battery Replacement
11:19
EEVblog2
Рет қаралды 7 М.
The World’s Largest Wind Farm has a Tiny Problem
13:38
Undecided with Matt Ferrell
Рет қаралды 851 М.
Win This Dodgeball Game or DIE…
00:36
Alan Chikin Chow
Рет қаралды 39 МЛН
Spongebob ate Michael Jackson 😱 #meme #spongebob #gmod
00:14
Mr. LoLo
Рет қаралды 10 МЛН
UNSW Talk - How I Became The EEVblog Guy
26:41
EEVblog2
Рет қаралды 28 М.
Perhaps the weakest link in the US electrical system
25:48
Technology Connections
Рет қаралды 4 МЛН
The invention that broke English spelling
22:47
RobWords
Рет қаралды 257 М.
The dark side of AI voice cloning (Elecrow responds)
13:06
Jeff Geerling
Рет қаралды 93 М.
AGL Energy Smart Meter DODGY?
9:49
EEVblog2
Рет қаралды 4,3 М.
EEVblog 1566 - Rigol DHO800 12 Bit Oscilloscope FULL REVIEW
1:00:46
The REAL Problem with Smart Meters
20:05
RECESSIM
Рет қаралды 540 М.
UK Property Just Changed FOREVER
11:28
Property Hub
Рет қаралды 657 М.
2024 Product Reveals for the Commander X16
25:53
The 8-Bit Guy
Рет қаралды 187 М.
Matrix PSU Unboxings & Teardown
28:02
EEVblog2
Рет қаралды 23 М.
Win This Dodgeball Game or DIE…
00:36
Alan Chikin Chow
Рет қаралды 39 МЛН