Hey Chris. Real quick. The supervisory contacts are closed because when they are powered down, they supv relay opens. Just like a door contact on an alarm. This is to monitor AC unit working. It’s also to monitor the tamper off of one alarm contact. Example: the 2 alarm wires tie into the alarm relay with the resistor across to keep it supervised. But pull one leg of the contact off of 1 alarm terminal. Replace it with a jumper that will connect from alarm terminal to common of supervisory relay. Then the other leg of the alarm contact will screw into the terminal of the normally open supervisory relay. So basically, the alarm is completing its circuit with the resistor strapped over the alarm relay, then to the “closed” supervisory relay. So that when the detector is tampered with, or loses power, the circuit will “open” and cause the fire panel to go into a trouble. Hope this helps!
@hgbugalou4 жыл бұрын
24 volts can definitely hurt you... If you drop the transformer on your foot.
@SodiumInduction-hv Жыл бұрын
lol
@cjkokay6 жыл бұрын
Easy about the relay. The no/nc refer to the de-energized state. The sup relay with normally be engergized to ensure the alarm if power to the unit fails.
@44R0Ndin4 жыл бұрын
I was just about to comment this, that's why it indicates trouble when the power is cut. No power to pull in the relay, means you get an open circuit on the alarm wires.
@Elysiann5 жыл бұрын
In Australia, the way duct detectors are done is different. They are powered from the fire panel itself, not an external/auxiliary power supply.They are wired on the detector loops, so any alarm or fault condition is seen directly by the panel. Usually , there is one duct probe on a supply unit, to check for "smoke" in the outside air and the unit is set to shut down on a "fire" condition. Then once the "smoke" is cleared, the fan will start back up. The idea is to stop smoke from outside being put into the building. For return units, the duct prob is set to generate an alarm, set off the warning systems, call the fire brigade, shut down supply units,etc ... what ever the fire/smoke matrix calls for. IE: there is smoke in the building somewhere. This is a latched alarm, so you need to reset it from the fire panel. The dectectors are usually addressable, so you know exactly which detector is in alarm or fault. The duct detectors you're using, we do use too. But we use them on "dumb" or non addressable fire panels. They are the only device on the circuit from the fire panel. Only used on return air ducts. That all being said, the fire codes for the US and Australia are vastly different. In some instances, I wish we had the set up you have ( as displayed), in some other cases, the system you have would causes a lot of problems here is Australia.
@starlite5284 жыл бұрын
The installs that I've done, as a fire tech, had a 'less smart' unit, but the smoke head was addressable for the FACP and the detector unit still had the test/reset stations hooked up. The supervision and alarm all came through the addressable part, so a lot of smoke heads and duct detectors (dozens) are looped in on a single 2-wire circuit. There was a separate addressable relay (that the HVAC tech would tie to) that would activate upon alarm, or whatever other condition, from the FACP. A general fire alarm from the building would shut down the units, but a duct detector that has sensed smoke would usually only shut down the unit and send a supervisory alarm.
@murkyturkey52382 жыл бұрын
I like that bc if I’m working on that unit and accidentally trip the duct detector I don’t call the fire department over for a false alarm
@CHOMAHOMA Жыл бұрын
Thank you for taking the time to make this video. Extremely helpful.
@trebrehenuf6 жыл бұрын
Deep sir, if one can recognize the complexities of fa systems. You skirted at the right places.
@HVACRVIDEOS6 жыл бұрын
thanks!
@seang.20464 жыл бұрын
Perfect video, learned alot that I've seem to forget over the years. Refresh helped
@rayregal62584 жыл бұрын
great information, glad there's people like you with videos that make sense to watch.
@publicmail24 жыл бұрын
The resistor is an EOL end of line resistor to check integraty of wire loop, it has to be put at the end of the line loop.
@thecurious6721 Жыл бұрын
Thank you for the great video. The only problem it took me 30 minutes to watch first 16 min trying to understand and figure out how you were getting 15kohms across SUP NO contacts 🤣 Thanks a lot for explaining that. If you skipped that I wouldnt be able to sleep today 😁
@fredrosas25756 жыл бұрын
I've wired these through the AUX contacts but never went in depth through all the other contacts and settings. Thank you so much for this video.
@HVACRVIDEOS6 жыл бұрын
thanks for watching!
@FJBANDHUNTER20243 ай бұрын
Great videos brother. Very in depth
@joshhope92875 жыл бұрын
So for people who are not in the fire or security industry(both are the same when it comes to EOl resistors I’m gonna break this down for you. On any wire that you have whether it be open circuit or closed circuit; the only way to ensure that the wire is good and hasn’t been cut down the line somewhere is to put a resistor with a certain resistance or ohm value at the end of the cable. 3.3 or 4.7k whatever it may be all it does is tell the control panel that the wire is intact. This is not voltage!!! It is a circuit. Ohms. Resistance. So you are correct we as fire people on a normal fire system are looking for a dead short, pretty much the wires touching together to indicate our alarm signal. In normal operation the panel is reading the value of the resistor. An open circuit or cut wire would indicate a trouble condition. This is different than a supervisory signal. Supervisory signals aren’t alarm signals!! Yes we want to know about it as it will report to the monitoring facility what the trouble but we don’t want it to create an alarm and activate horn,strobes and such. 99% of fire alarm circuits are open circuits because that’s the most efficient way of detecting the two states of the circuit open or closed. Closed for alarms and open for troubles. Anything else is just normal resistance value at the end of the cable or line.
@HVACRVIDEOS5 жыл бұрын
Great information bud thanks for taking the time to leave some info!
@Ufphen2 жыл бұрын
also the monitoring company should not be calling the fire department for a trouble signal when you turn off the unit.
@abc-coleaks-info3 жыл бұрын
They put those damn things in the ducts at a prison facility. The damn dust triggered the detectors everywhere and people were kept on the run for months looking for fires that were never there. A big expensive pain in the butt. Their staff conducted fire watches continuously 24-7 anyway as a regular part of the job. When there was a fire, the staff caught it, the alarm came on later. They were ignored after that.
@Akvan796 жыл бұрын
Great video very informative. I also had problems with duct detectors until I decided to learn about them. I’m no expert but I do understand the concept
@HVACRVIDEOS6 жыл бұрын
Thanks bud!
@dudefixesstuff21536 жыл бұрын
Way too many techs set these things off servicing the unit without calling to have service suspended. Great idea on putting the demo together!
@HVACRVIDEOS6 жыл бұрын
thanks bud!
@jeffreyarnold70423 жыл бұрын
I have watched this video every time I have to install an duct detector
@HVACRVIDEOS3 жыл бұрын
Right on man, hope it helps
@jth16995 жыл бұрын
I have run across controls that appear to be backwards - particularly in speed switches on generators that operate automatically- what is happening is that supervisory contact changes state when the power is applied. If installers dont realize this there will be start up issues. Why dont you measure the contact with no power applied and then turn on the power to the control unit and see if the switch changes state.. another advantage to that setup is if the n/c is closed with the power off and opens when it is energized the if the power went off the contacts would close to send an trouble signal - and for systems that depend on a normally closed circuit - which is generally the case - it would be the n/o supervisory contact that would be used to monitor for power and circuit trouble ... the resistor is generally referred to as an EOL resistor or End Of Line. Your explanation is correct except that the fire system senses the amperage or load on the detector circuit created by the resistor. No load equal open circuit and trouble alarm - shorted circuit equal alarm condition. These things are pretty simple once you know how they work. Course so is flying a 747 once your trained and have a few thousand hours of seat time... nice video
@HVACRVIDEOS5 жыл бұрын
Thanks bud! I will be going live on KZbin this evening 12/16/19 @ 5:PM (Pacific Time) to discuss my most recent uploads and answer questions from emails, the chat and Facebook come on over and check it out if you can. kzbin.info/www/bejne/lWOTmXqkn89-apY
@rookierefrigeration43576 жыл бұрын
Excellent video Chris. I’ve learned a lot from you and your videos. Keep them coming bud.
@HVACRVIDEOS6 жыл бұрын
thanks!
@elijahgoodman3140 Жыл бұрын
Hey Chris, can you jump out the tamper switch to see if the amber light clears?
@michaelsullivan4795 жыл бұрын
Excellent video STEELY EYED REFRIGERATION DUDE! I also set up electrical components on a board for our guys to learn on and become experts. We have to know how things work in order to know what is not working.
@ryanprice57685 жыл бұрын
I appreciate your videos so much. I'm in my first year of school for HVAC and your troubleshooting and thorough explanations of electrical problems etc. are more than helpful;they are incredibly interesting and well worded plus motivating. Thank you thank you thank you.
@murkyturkey52382 жыл бұрын
You’re welcome
@jamiebaker36154 жыл бұрын
Not sure if this is already been posted the reason why the supervisor is different is because when the powers on that actually energisers that relay so the normally open gets closed so when the power goes out at triggers a trouble conditions
@DDRighteous6 жыл бұрын
Great video. I think the Supervisory relay is labeled backward because when the unit is in a Supervisory condition, the common to normally closed contacts are closed. If the relay was labeled "Normal Operation" then the labels would be reversed. Also, the Supervisory relay is normal when the Detector module is powered and there are no abnormal conditions. When power is shut off, the relay de-energizes, which alerts the fire alarm panel. Also, when the smoke heads get dirty (internally) the detector will go into a maintenance alert, and open the Supervisory relay. This will be indicated also by a blinking amber LED. You can clean the inside of the smoke detector with a clean horsehair brush, and reassemble the head, or replace the affected smoke head. I have not had very good results trying to clean with compressed air.
@Ufphen2 жыл бұрын
I know its super annoying, you'd think it would work like the alarm contacts or any other set of dry contacts in existence, but no its got to be special.
@DDRighteous2 жыл бұрын
@@Ufphen It has to operate like this so the panel shows a trouble when power is removed. Otherwise you would not know the detector has lost power.
@Ufphen2 жыл бұрын
@@DDRighteous but why is Normally Open not normally open
@DDRighteous2 жыл бұрын
@@Ufphen The supervisory relay is labeled correctly when there is no power applied to the duct-smoke. To make it supervised, they apply power to the relay when no trouble exists. That way it transfers when in a no power state, or when there is a trouble condition. If it were to operate the other way, you would never know when power has been removed. Or you would have to install an external power supervision relay to cause a trouble condition when power is removed.
@Ufphen2 жыл бұрын
@@DDRighteous Its a set of dry contacts so regardless of power one side is going to be open or closed. Why would you have trouble condition be the normal state instead of no trouble condition as the normal state. These are dry contacts, they are passively designed, one side is always going to be shorted and one will always be open.
@jacobmergens91354 жыл бұрын
Danm, I've been making it so much harder on myself. THANK YOU!
@jeffmoss25473 жыл бұрын
great video!
@joemartinez76195 жыл бұрын
Thank dear sir. Putting food on many families tables. I prey u keep passing it forward.🇺🇸🎁🎄
@brianmcdermott17185 жыл бұрын
Great job. Good info.
@pincheburro9566 жыл бұрын
Great video. Worked on a few lately.
@HVACRVIDEOS6 жыл бұрын
right on thanks bud!
@GabeDT5675 жыл бұрын
great video . adding to my learning folder . thanks
@HVACRVIDEOS5 жыл бұрын
Thanks for watching bud
@abazism2 жыл бұрын
Hi, what is that control board called ? The one that is connected to the smoke detectors
@jaysingh-ho7eb2 жыл бұрын
Thank you for great video
@lancerudy99345 жыл бұрын
Very nice video. This is a great learning method for any body. Please keep up the great work!😁
@aleksandrliudogovskii84915 жыл бұрын
this video is understandable and helpful! thank you
@HVACRVIDEOS5 жыл бұрын
Thanks for watching!
@jackieg42775 жыл бұрын
I need some help with wiring d4120 duct detector with rts2-aos multi signaling acc. On a Lennox 12.5 RTU
@davetatro4786 жыл бұрын
Ever seen them wired to the power exhaust? I have...cant remember if it was code..
@MrBdogg3172 жыл бұрын
Great video 👍🏼👍🏼
@NOEISY16 жыл бұрын
thank you, this was my first in RTU unit class and excellent
@HVACRVIDEOS6 жыл бұрын
Thanks for watching bud!
@SCOTTYD20313 жыл бұрын
That was very interesting, thank you for that class teach!
@anibalgutama93134 жыл бұрын
Hi I’m Antonio I like your vireo help a lot thanks for thinking an other person
@HumanRightsRevolutin5 жыл бұрын
Thank you very much VERY HELPFUL!!!
@Randylazz6 жыл бұрын
Really enjoyed this video great job.......
@HVACRVIDEOS6 жыл бұрын
Thanks Randy !
@aircooledtx6 жыл бұрын
Great Info on SD wiring.
@HVACRVIDEOS6 жыл бұрын
Thanks! I did this same presentation at my local RSES meeting once last year, it is probably time to do it again!
@crazyk662able6 жыл бұрын
Thanks I been waiting on a video about smoke detector I get a lot of services call about smoke alarm an when I get there the Rtu is running but the alarm panel is showing fault and I’m lost from there cause I don’t know what to check so I just tell them to call the alarm company.
@HVACRVIDEOS6 жыл бұрын
Thanks for watching bud if you look down in the show notes there is a link to an article I wrote for hvac school on the same topic
@Colt-wr6wx3 жыл бұрын
Definitely not simple but thanks Chris!
@TheMontanasv62 жыл бұрын
It is residential house, I am trying to interconnect the duct smoke detector on the furnace to the ceiling smoke alarm. Would you please share some information how to interconnect these two? Thanks.
@majindomttv39033 жыл бұрын
Awesome video I don’t think I’ve seen one not come installed in a unit in a year or so now. Can you hook these up to an ansel system? Reason I ask is because the ansel system has dry contacts so it is breaking the signal from up above so is it possible to hook them to the smoke detector or is the ansel system basically taking the place of the smoke detector?
@Ufphen2 жыл бұрын
ansel system is taking the place of fire detection, its actually covered under fire suppression and not fire alarm, we hook into it for an alarm condition when the ansel system as well as the electricians for electrical shutoff to the stove, griddle, oven, etc. Ive also seen damper controls hooked into it as well
@jasonclements4607 Жыл бұрын
My AUX is causing a dead short. Causing transformer to pop the 5amp. Ill recheck wiring tomorrow. But I feel it has a bad relay in the smoke detector. Nothing pops if I pull the AUX wires. could not find a PDF when I was there. Any help would be appreciated.
@tomtreece32246 жыл бұрын
Great video these give me fits you cleared up some questions I’ve had. Love the board for training!
@HVACRVIDEOS6 жыл бұрын
Thanks bud
@franciscojesuspachecoballa25665 жыл бұрын
Great video bro!!! Thank you for you help...
@titolocho7 ай бұрын
The reason that the sup contact are reverse is because you suppose to test it with the power off
@bobcasseus73815 жыл бұрын
I really appreciate your video very interesting and understood thank you again!!
@apr92865 жыл бұрын
Gonna need to look into a duct fire dector that have an alarm indicating it is damp. Any suggestions? They lowered the vav temperature from 68* to 64*. Not sure if it is in the same duct.
@brennan22995 жыл бұрын
So in hindsight i would call the fire panel monitors and let them know i was going to do something to the fire detection system that might set off a false alarm or trouble signal and or put that zone offline till works completed
@HVACRVIDEOS5 жыл бұрын
Yep that's the best bet!
@HVACRVIDEOS5 жыл бұрын
thanks for watching I'm gonna go live this evening 4/29/19 at 5PM (west coast time) to discuss my most recent uploads and answer questions from emails, the KZbin comments and the chat come on over and check it out . kzbin.infolive
@andycheng45342 жыл бұрын
thank you very much
@Tactical-Black4 жыл бұрын
I know this is an old video I'm just looking around to see if anybody was able to get multiple key test stations to signal (independent horn and strobe on other keystation installed on other air handlers) I have three rts2aos and three d4120 duct detectors Everything works except signaling the other key stations. It probably cant be done but I'm checking
@HVACRVIDEOS4 жыл бұрын
Im pretty sure I have seen multiple key stations lit up before when one was tripped, does the global shut down not do that? I will be going live on KZbin this evening 1/27/20 @ 5:PM (pacific time) to discuss my most recent uploads and answer questions from KZbin comments, emails and the live chat. Come on over and check it out if you can, kzbin.info/www/bejne/a3zXh5yflLmqa68
@Tactical-Black4 жыл бұрын
@@HVACRVIDEOS no when you flip one key station only that one lights up and sound off, I called the supplier and they told me it cant work like that because their isn't a connection in there for that It's a d4120 and rts2-aos key station from system sensor
@jareddory21556 жыл бұрын
On the 7 minute delay for trouble, if you “solve” the trouble or close the detector cover before the 7 minutes would it still send the code to the alarm co?
@HVACRVIDEOS6 жыл бұрын
No if you solve the trouble issue and or replace the cover before the timer ends it will not signal a trouble
@wesjordan69725 жыл бұрын
Right. Cause at the end of the day it isnt voltage that hurts you, its amperage.
@HVACRVIDEOS5 жыл бұрын
I will be going live on KZbin this evening 10/14/19 @ 5:PM (pacific time) to discuss my most recent uploads and answer questions from the LiveChat, KZbin comments, Emails, and Facebook comments come check it out if you can. kzbin.info/www/bejne/qnOUYo2KiK2bnqc
@om6789gg Жыл бұрын
What's the model of the smoke detector? Thank you
@marisnchz2 жыл бұрын
We don’t have these but It’s cool to me 😎
@leokim18732 жыл бұрын
Hi @HVACR VIDEOS I realise by watching your videos and reading the manual that this particular unit has a separate unit to manually reset the alarm mode. Is there a way to make this automatically reset the whole unit? because it says there is a 0.6 seconds reset when powered down, please let me know your thoughts.
@joshuaschaffner39734 жыл бұрын
what would say is more common wiring from unit to the Aux? I’m guessing 24v from the RTU? Sorry to bother you still in school, we don’t cover this at all?
@HVACRVIDEOS4 жыл бұрын
send me an email and give me more context to your question hvacrvideos@gmail.com I will be going live on KZbin this evening 2/17/20 @ 5:PM (pacific time) to discuss past videos and answer questions from KZbin comments, Facebook comments, email’s and the Livechat, come on over and check it out. kzbin.info/www/bejne/mYWliZaVg5mCZ9k
@gtmrefrigerationac6 жыл бұрын
Great videos
@HVACRVIDEOS6 жыл бұрын
Thanks!
@MrOhiousa6 жыл бұрын
how would you wire the (AUX) to a gas furnace to shot the fan off?
@HVACRVIDEOS6 жыл бұрын
I am going live on KZbin tonight at 5:00pm pacific time come on over and check it out! kzbin.info/www/bejne/aoKrkn1mqMp1oa8
@donaldmckee5855 жыл бұрын
Thank you it is VERY confusing I have some that just shut damper and others shut the whole unit down
@HVACRVIDEOS5 жыл бұрын
no worries bud
@joshhope92875 жыл бұрын
Yes the Fire Marshall for the jurisdiction you’re in has the ultimate say so as to what he wants the detector to do. Shut the unit down, shut the fan down, close dampeners or just notify monitoring center. Main reason for shutting down the un8t if smoke is detected of course is to sto0 any airflow from feeding a fire but also to prevent pumping smoke to other areas of a location.
@joshuaschaffner39734 жыл бұрын
DECK-eM J what would say is more common wiring from unit to the Aux? I’m guessing 24v from the RTU? Sorry to bother you still in school, we don’t cover this at all?
@AMTECHMECH6 жыл бұрын
clear as mud
@hectornunez82624 жыл бұрын
Can you please send me wire diagram for single smoke detector for Lennox package unit
@ikennaogwogwo4 жыл бұрын
Thank you so much. I learnt a lot.
@capitolrefrigerationheatin75016 жыл бұрын
I have seen a hospital remodeling rooms and found the sensor in the detector not working proper, always was sensing smoke when none was present
@HVACRVIDEOS6 жыл бұрын
Yeah sometimes the detectors can be faulty, usually hospitals do routine inspections on their detector heads as they are usually held to higher standards.
@cristobalan5 жыл бұрын
What is the model duct smoke detector?
@HVACRVIDEOS5 жыл бұрын
System Sensor 4120 I think
@damarcojackson10055 жыл бұрын
How do i do a manual global shut down...."chain multiple alarms together manually"...?
@44R0Ndin4 жыл бұрын
You would need to put the contacts of each alarm in parallel, so that any one of them closing would close the circuit that you use to shut things down. If you only want the thing to happen when all the detectors are going off (for some reason), you need to put the contacts in series, so that you need to close all the contacts for the circuit to complete.
@SamuelParedeslopez17 күн бұрын
How much is the cost for install that ?
@bharatbeerrama64556 жыл бұрын
Thanks sir
@HVACRVIDEOS6 жыл бұрын
Thanks for watching! Take a look in the show notes and there is a link to an article I wrote for the HVAC SCHOOL website on the same subject
@airmechanical71636 жыл бұрын
Excelllent!
@HVACRVIDEOS6 жыл бұрын
Thanks man, I re shot the video 2 times because it just wasnt right!
@HVACRVIDEOS6 жыл бұрын
Also look in the show notes and there is a link to an article I wrote on the same subject on hvac school
@airmechanical71636 жыл бұрын
HVACR VIDEOS - I will definitely read your article. Thanks .
@JB-gx5vw10 ай бұрын
Try saying where you wired the reset
@MrDudezProductionz5 жыл бұрын
So, my fire alarm went off last night and when I turned off the AC, it turned off. I'm assuming that the duct detector detected smoke, the question is, from where?
@HVACRVIDEOS5 жыл бұрын
It's really hard to say because the fire alarm can be initiated by several things
@joshhope92875 жыл бұрын
Duct detectors are notorious for having false alarms due to dust and debris being sucked into the return.
@Game-ib3ql5 жыл бұрын
You ever had one making a whining sound?
@dailylife42484 жыл бұрын
Rts 151 2 wire smoke detector full detail
@dailylife42484 жыл бұрын
I have a smkoe detectors alarm generated by magnet / but not generate by rts key why any probelm pls tell me
@harrydickson45756 жыл бұрын
👍👍👍
@TerryGannon-jj1xu Жыл бұрын
How do I find a hvac dealer who can install this for me? I am zip 32164. Thanks Terry
@rocker86923 жыл бұрын
Just use a fire alarm
@TheGpaul9 ай бұрын
Too complicated I’ve seen sample
@IFIXCASTLES6 жыл бұрын
I had an alarm company break a 24v wire at a terminal strip buried inside there alarm box. Drove me nuts ....couldn't find where I lost 24v..the wire was extremely hard to detect a break. The alarm company is a constant source of problems.. How many times the panel was not reset after they were done testing and I get a no heat or cool call. I then have to go to that location and punch in the reset code. Idiots..Smoke detectors mounted on the ceiling pop off there mounts because the tech didn't lock it in....Idiots...job security I guess...lol.