I have meggered hundreds of motors during my over 35 years of testing etc... if the motor or the cables have bad insulation - I always knew it within a few seconds of performing the megger test. I always megger 480v volt motors at 1,000 volts, 240 volt motors at 500 volts and 120 volt motors at 250 volts and never had an issue finding a good or bad motor or cables. Plus, we always kept records of motor testing to go back and look at trends. Trending is very important if you have lots of 250 volt DC motors in your facility.
@electricallectures9 ай бұрын
Yes that is true. Trending is always belpful. But you cant deny these factors also. The readings can be misleading specially on motors where insulations starts to deteriorate. Where motor insulation is already damaged then these factors are meaningless
@Krispy10119 ай бұрын
If motor insulation is starting to break down you will see it in your trends as I have witness many times and then the motor is changed out for PM reasons(low megger reading). If the motor insulation is damaged you will probably be at the motor cuz it will not run and when motor is meggered you will get bad megger readings@@electricallectures
@30mAkills Жыл бұрын
Other 3 common mistakes: 1. Not checking the megger before using. 2. Using the megger on energised circuits! 3. Not discharging the item after testing is over. Thanks
@myasir13552 жыл бұрын
greeat work done sir,
@aldrincallejo4548 Жыл бұрын
Tips on how to test the Motor even iti is running. "Essential Load"
@bashiruosman47311 ай бұрын
Well done. ❤
@electricallectures11 ай бұрын
Thabks. Stay tuned and dont forget to subscribe plz
@deddie46455 ай бұрын
Nice
@hari_prasath_prudent Жыл бұрын
Bro's one doubt If need to check meggar insulation check for alternator in between ground to windings is that require to disconnect connections from main winding terminals in alternator....if checked without disconnecting avr what may occur
@electricallectures Жыл бұрын
No need to disconnect . You can check but remember for 400v alternator only apply 500v megger
@evanreyes2054 Жыл бұрын
hi sir what is the difference in result if we IR test the motor applied with 500v and 1000v?
@electricallectures Жыл бұрын
The motor rated for 400V shall be tested with 500v megger. If you apply high voltage it may rapture the insulation
@rafinostalgia10096 ай бұрын
I have megger mit310 insulation tester.when i check 250&500 volt readings showing e31 .what is the complaint is that. How correct that..
@electricallectures6 ай бұрын
Your instrument internal hardware error. Need service
@nokuthulamthimkhulu80082 ай бұрын
Next time please demonstrate after stating each mistake done or whatever you're explain that's easier to understand
@kapitbahaychanel Жыл бұрын
Thank you master
@electricallectures Жыл бұрын
Thanks. Stay tuned and dont forget to subscribe plz
@HassanMajed Жыл бұрын
Hello sir If you can help me, I have this device showing a wrong value for the resistors, what can I check to discover the defect?
@electricallectures Жыл бұрын
How can you test resistance of resistors with it
@HassanMajed Жыл бұрын
@@electricallectures sorry sir I mean resistance not resistors For example when I Check 1 MOhm this device showing 100 Ohm
@raulm9847 Жыл бұрын
Can I do megger test in a hot motor?
@electricallectures Жыл бұрын
There is apparently no issue to apply megger to hot motor except if there is a moisture , that would be dried up when its hot and you will get good reasult but derection of moisture is evident
@JDT73812610 ай бұрын
Very good narration, too bad the video didn’t have a live example on how to do it properly
@electricallectures10 ай бұрын
Thanks for the video. It is not about hiw to do megger. It is about highlightling the mistakes which are normally ignored. And you can learn without actually doing it
@jhunacosta6621 Жыл бұрын
Megger is a brand
@electricallectures Жыл бұрын
Megger is a device to test insulation resistance.
@buttheadya Жыл бұрын
@@electricallecturesLMAO
@nikolayhristov84934 ай бұрын
@@electricallecturesreally 😂
@kingofslotsmillion3263 Жыл бұрын
So I'm megging a motor a 480 v motor and reading 78.9 mega ohms to ground. Is that bad
@electricallectures Жыл бұрын
Perfect. No issue
@kingofslotsmillion3263 Жыл бұрын
@@electricallectures omg ITS A LARGE 350 AMP MOTOR AND THEY BRINGING A CRANE OUT TODAY TO PULL IT. WE HAD A FIRE ON A FORGING PRESS. and there was a fire near the motor melted alot of stuff. So I figured the varnish must have been compromised. So when I was getting the 79-90 mega ohms I called it bad. On what if one Legg was .079?
@electricallectures Жыл бұрын
Megger value must be large for all windins
@lhadytagupvlog Жыл бұрын
Nice
@electricallectures Жыл бұрын
Thanks. Stay tuned and dont forget to subscribe plz