Relay setting calculation|Restricted Earth Fault Protection relay Setting Part-2|KNEE POINT VOLTAGE

  Рет қаралды 30,369

ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE

ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE

Күн бұрын

Пікірлер: 61
@kulkarnir93
@kulkarnir93 3 жыл бұрын
Sir, Thanks for giving such good knowledge about REF protection. How RCT of 4 nos CTs i.e. 3 phase CTs & 1 neutral CT. Also explain the exact method of calculating wire connected with the 4 CTs.
@rameshtripathy5978
@rameshtripathy5978 5 жыл бұрын
It is very much useful for the commissioning engineers !
@priyal5354
@priyal5354 2 ай бұрын
Vs =60V will appear across secondary terminals of CT, right? How to choose Is?
@wongsabarchannel1335
@wongsabarchannel1335 10 ай бұрын
Do you have Low Impedance REF Calculation Video?
@thetruelegend2502
@thetruelegend2502 5 жыл бұрын
Thanks sir, Crystal clear to understand
@musicvideo1566
@musicvideo1566 3 жыл бұрын
very good
@patelsiddharth7698
@patelsiddharth7698 Жыл бұрын
Sir can we use REF protection for 1MVA transformer?
@sridhar3377
@sridhar3377 2 жыл бұрын
Is there any video of this calculation also done for the condition of NCT with resistively grounded??
@shantanumajhi5408
@shantanumajhi5408 2 жыл бұрын
Very Useful
@elavarashanrajesh6560
@elavarashanrajesh6560 Жыл бұрын
Very usefull sir thank u very much ❤❤❤❤❤
@bristykhatun2404
@bristykhatun2404 3 жыл бұрын
thinks sir vary good job
@jppatnaik2240
@jppatnaik2240 3 жыл бұрын
For Each CT whether we consider of One CT (or) all 3 CT ? ( RCT )
@surendrakverma555
@surendrakverma555 2 жыл бұрын
Very good. Thanks 🙏🙏🙏🙏
@hosseinshabaniroshan8174
@hosseinshabaniroshan8174 2 жыл бұрын
Hi.I want to know exactly how to draw the characteristics of this relay...? Do the differential current and bias current ,which are the necessary characteristics for this relay , come from the normal state of the relay or from fault condition?
@hzbajlanihzbajlani6699
@hzbajlanihzbajlani6699 2 жыл бұрын
We have a factory that requires 6 MVA electric power , Can we use one large transformer and limit the fault current with NGR? our transformer is 11/0.4 KV
@jitendradubey3682
@jitendradubey3682 4 жыл бұрын
Thanks sir.... Very informative 😊😊😊🙏🙏🙏
@balakabimuki2023
@balakabimuki2023 4 жыл бұрын
Hello sir, After calculated VS , why should we use the formula of CT Vnee>2Vs?? and here this video you increased the voltage from 120 to 400?????and you told that we can use 650V also..how to choose the maximum voltage ???
@yokeleetan8525
@yokeleetan8525 Жыл бұрын
It seems from your calculation Vs is the voltage across the relay and stabilising resistor.
@jyothiyecherla7964
@jyothiyecherla7964 4 жыл бұрын
Here RCT Value means combination of 4 cts or one ct?
@zahidulislam2458
@zahidulislam2458 3 жыл бұрын
Nice
@hplar2972
@hplar2972 3 жыл бұрын
Hi,just want to ask you is it earth that was intalled at MSB also the same funtioning?
@hplar2972
@hplar2972 3 жыл бұрын
I mean earth fault relay
@ranjan1436
@ranjan1436 5 жыл бұрын
pls make a video on knee point voltage. so far it is fantastic.
@electricaltechnologyandind5335
@electricaltechnologyandind5335 5 жыл бұрын
There is already a voltage on knee point voltage selection. Check the restricted Earth fault protection series
@learnbyshiva725
@learnbyshiva725 4 жыл бұрын
Thanks sir very good job
@thinkseeeatthroughvickus4555
@thinkseeeatthroughvickus4555 4 жыл бұрын
Please make a video on - what all relays can be connected from same CT, and where CTs to be installed in case of transformer protection, bus bar protection, so that it wii give an idea how many CTs required
@ManojkumarSahoo_electrical
@ManojkumarSahoo_electrical 3 жыл бұрын
Sir, How to calculate the power rating (Wattage) of stabilizing Resistor for REF relay.
@neerajpiplani185
@neerajpiplani185 4 жыл бұрын
Wonderful explanation. Could you please explain why knee votage should be atleast twice Vs
@CartoonwonderlandEdu
@CartoonwonderlandEdu 5 жыл бұрын
Love u yar ur vedios are so good to understand
@wary8113
@wary8113 2 жыл бұрын
WHICH CT RESISTANCE TO BE TAKEN IN CALCULATION? 3 CT OF LINE & 1nct is in parallel?
@shankhachongder6065
@shankhachongder6065 5 жыл бұрын
Thank you for the video sir
@jamesowusu-ansah595
@jamesowusu-ansah595 4 жыл бұрын
Sir please, by safely choosing the the knee point of the CT to be twice Vs...Then it's safe to say the LCT's won't get saturated for high value external faults right?
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
Yes. That is one of the check point of REF setting
@jamesowusu-ansah595
@jamesowusu-ansah595 4 жыл бұрын
@@electricaltechnologyandind5335 So if it's unlikely to enter saturation by safely selecting your CT knee point, then i really don't see the need of a stabilising resistor Also, won't the stabilising resistor reduce the current in the event of a ground fault within the protected zone, hence, the relay might not operate?
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
When vs has occurred that will drive current through relay. For that stabilizing resistance is given. Please watch the video again
@jamesowusu-ansah595
@jamesowusu-ansah595 4 жыл бұрын
@@electricaltechnologyandind5335 But Vs only occurs when the CT'S get saturated right?
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
No. When current flows.
@ajithomas8342
@ajithomas8342 Жыл бұрын
🎉
@pceprojectspvt.ltd.6183
@pceprojectspvt.ltd.6183 4 жыл бұрын
In case the earth fault is inside the zone , how to ensure that insertion of stabilising resistor will not lower the fault current below the pick-up setting of the relay
@yctsang6561
@yctsang6561 4 жыл бұрын
I have the same doubt
@sujonshahofficial2572
@sujonshahofficial2572 3 жыл бұрын
Wow
@shashah769
@shashah769 2 жыл бұрын
😍😊
@rakeshnanda9506
@rakeshnanda9506 5 жыл бұрын
Nyc explanation sir
@thinkseeeatthroughvickus4555
@thinkseeeatthroughvickus4555 4 жыл бұрын
Can you do a video on PS or PX class CT sizing?
@nageshpawar2455
@nageshpawar2455 4 жыл бұрын
THANK U VERY MUCH SIR....
@ashutoshpokhriyal1020
@ashutoshpokhriyal1020 5 жыл бұрын
Sir please share distance protection setting calculations
@shujaatkhan6637
@shujaatkhan6637 3 жыл бұрын
Dear Sir, Can you please make a video on Knee point voltage
@ABHAYSINGH-um3wc
@ABHAYSINGH-um3wc 4 жыл бұрын
excellent but please make the more easy those concepts
@ashiqurrhman292
@ashiqurrhman292 3 жыл бұрын
Nc
@kameshwarmehta5507
@kameshwarmehta5507 2 жыл бұрын
Fault current calculation how.....
@mdronvai4405
@mdronvai4405 3 жыл бұрын
❤️🥰😏
@naimulislam41
@naimulislam41 3 жыл бұрын
nc
@akhilsm6840
@akhilsm6840 4 жыл бұрын
Why the CT saturated even though the CT knee point voltage is very high
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
Normal protection relay doesn't have high knee point voltage
@dilipsahusahu680
@dilipsahusahu680 4 жыл бұрын
Please please please Hindi sir
@mdborhan2690
@mdborhan2690 3 жыл бұрын
very nice
@mdborhun15
@mdborhun15 3 жыл бұрын
Wow
Relay setting calculation|Restricted Earth Fault Protection relay Setting Part-1|CT selection
12:39
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 38 М.
Osman Kalyoncu Sonu Üzücü Saddest Videos Dream Engine 275 #shorts
00:29
Osman Kalyoncu
Рет қаралды 3,7 МЛН
Ouch.. 🤕⚽️
00:25
Celine Dept
Рет қаралды 22 МЛН
Хасанның өзі эфирге шықты! “Қылмыстық топқа қатысым жоқ” дейді. Талғарда не болды? Халық сене ме?
09:25
Демократиялы Қазақстан / Демократический Казахстан
Рет қаралды 349 М.
Don't look down on anyone#devil  #lilith  #funny  #shorts
00:12
Devil Lilith
Рет қаралды 48 МЛН
Restricted Earth Fault Protection|REF relay working principle
11:56
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 144 М.
DISTANCE RELAY || CALCULATION OF DIFFERENT ZONE SETTINGS ( PART-1)
15:41
RELAY PROTECTION ELECTRICAL
Рет қаралды 22 М.
REF Protection and it's satbility
27:35
electrical engineerr
Рет қаралды 24 М.
Comprehensive Guide to Electrical Cable Selection and Voltage Drop Calculation
29:11
LOW IMPEDANCE RESTRICTED EARTH FAULT(REF) PROTECTION
11:10
RELAY PROTECTION ELECTRICAL
Рет қаралды 6 М.
Flawless PCB design: RF rules of thumb - Part 1
15:45
Hans Rosenberg
Рет қаралды 80 М.
Osman Kalyoncu Sonu Üzücü Saddest Videos Dream Engine 275 #shorts
00:29
Osman Kalyoncu
Рет қаралды 3,7 МЛН