Can you tell me why this dLL sign keep coming even this is Brand new unit but the fan is from old Unit
@TropicSupply Жыл бұрын
Hi @Riteshpatel7283 ! The discharge line temperature has exceeded its temperature limits too many times and has thus locked the unit out. You will need to go to Copeland Mobile and look up Application Engineering Bulletin # AE8-1376.
@josegranados98357 жыл бұрын
I replaced the controller after that p2 and p3 appear .why ? I have to changed the low and high pressure sensor?
@mavimucit0423 жыл бұрын
EMERSON DİXELL KADAR DEVAM EDİYOR OLARAK KABUL
@NenoPetrušić29 күн бұрын
Hello, can someone explain to me what is PL alarm od Emerson compressor? Tnx
@TropicSupply27 күн бұрын
The closest alarm we can find is "HPL" - Copeland has said the following - System operation causing high discharge pressures (HPL) or high discharge line temperatures (DLL) repeatedly - check system operations. To clear an HPL or DLL lockout, hold the start button for 3 seconds 2 consecutive times, or cycle power to the unit. If using the reset button, the alarm condition will have to clear (DLT temperature drops or Hp switch resets) and any minimum off time will need to complete (5 minutes for the fixed Hp switch). (HPL) high discharge pressures lock alarm is displayed if 5 repeatedly HP alarms occur within 1 hour. We hope this helps!
@NenoPetrušić27 күн бұрын
@@TropicSupplythanks for help
@Fast2slow7 ай бұрын
What does alarm code p3 mean 😭
@KennethMedard-cj5dp Жыл бұрын
What is a p1 alarm
@KennethMedard-cj5dp Жыл бұрын
5:15
@TropicSupply Жыл бұрын
@@KennethMedard-cj5dp Depending on your model number it may be. Abnormal voltage rise or drop. Possible causes; power supply issues/ faulty reactor / faulty PCB