9:18 Hi sir, When I'm running short circuit fault check, I'm getting fault for the LV breakers showing 9:18 9:18 condition -thermal energy and rating limit, etc. how to tackle this fault
@SmartEducare9 ай бұрын
You need to select CB with proper rating for Ith limit issue
@dha9jay10 ай бұрын
Please guide. In switchgear ratings page. What shall we put? For ansi standard. Bracing and peak calues if we have 40kA withstand capacity
@SmartEducare10 ай бұрын
Can choose the same 40kA symm. SC withstand rating
@loupejr.fuentes7815 Жыл бұрын
What time of fault is this?
@SmartEducare Жыл бұрын
This is bolted 3-phase fault. Will upload single Line to Ground (LG), LLG, LLL fault also very soon..