Short Circuit Calculations and Symmetrical Components - Part 1

  Рет қаралды 118,129

Brainfiller Arc Flash Training

Brainfiller Arc Flash Training

Күн бұрын

In this video, Jim Phillips diagrams and demonstrates the calculations by walking you through a few equations. To learn more check out Jim's Short Circuit Analysis CEU on demand class brainfiller.co... or his Electrical Power Systems Engineering livestream course brainfiller.co....
Per Unit System and Symmetrical Components are used for many short circuit calculations. Electric Utility Data is also often provided in terms of Per Unit and Symmetrical Components. In this video Jim explains how to use the positive, negative and zero sequence impedances in a per unit format to calculate the three phase and line-to-ground short circuit current.
Obviously there is more to the theory of symmetrical components then Jim shows here, but as far as the calculations, they are simple.
-----------------
Since the planet is a large place and Jim can't be everywhere, we are bringing Brainfiller training programs to you by offering arc flash safety, power systems engineering and regulatory update programs through this online learning program. Most classes offer professional continuing education units, so you can meet your annual compliance requirements through brainfiller.co.... FREE classes and CEU’s are also available for those on a budget. Visit Brainfiller Online at brainfiller.co....
About Jim Phillips: Electrical Power and Arc Flash Training Programs. For four decades, Jim Phillips has been helping tens of thousands of people around the world understand electrical power system design, analysis, arc flash and electrical safety. He has developed a reputation for being one of the best trainers in the electric power industry. See Jim’s upcoming training events: brainfiller.co...
Read Jim Phillips’ bio - click here: brainfiller.co...
Sign-up for Jim Phillips’ monthly publication “Grey Matter” which contains news about new standards, conferences, technical articles, electrical engineering and more! bit.ly/2BB083d
Brainfiller was founded in 1987 by Jim Phillips. Since those humble beginnings many decades ago, the Brainfiller brand has become synonymous with some of the best training programs built on Jim Phillips' four-decade career, having taught thousands of classes to people from all seven continents. Visit Brainfiller brainfiller.com.

Пікірлер: 23
@vishvakarthick8174
@vishvakarthick8174 4 жыл бұрын
How to calculate the short circuit current for Zigzag Transformer?
@eracismm
@eracismm 4 жыл бұрын
Nice video, very educational.....great presentation, and good graphics........Thx for taking the time to do this.
@Brainfiller
@Brainfiller 4 жыл бұрын
Glad you enjoyed it!
@jamesballah5223
@jamesballah5223 8 ай бұрын
nice presentation
@Brainfiller
@Brainfiller 8 ай бұрын
Thanks a lot
@user-eu8ro3lx7g
@user-eu8ro3lx7g 8 жыл бұрын
it is very useful tip! thank you a lot.
@calvinooi8198
@calvinooi8198 3 жыл бұрын
Hi, where can view the Part 2 ?
@carlitosways6442
@carlitosways6442 11 ай бұрын
Where can find the Part 2?
@MR-nl8xr
@MR-nl8xr 5 жыл бұрын
There should be some kind of test to show and teach people in the trade how to calculate the SCCR for their application.
@Brainfiller
@Brainfiller 4 жыл бұрын
Agreed. The US National Electrical Code is requiring the calculated short circuit current to be listed on more equipment. But to actually determine that value takes a bit of calculation experience. Even if software is used, it can be a challenge.
@MR-nl8xr
@MR-nl8xr 4 жыл бұрын
@@Brainfiller I believe Bussman has an app(that I've tried to use), called FC2 calculator; something like that.
@Satchmoeddie
@Satchmoeddie 8 жыл бұрын
Why are we not using phase angles? I have also worked high power RF transmission, 400Hz military, 25Hz legacy, and any actual symmetry is an assumed condition. When things do go to ground, take a look at plotted data from any metered parts of the system. I have seen conductors get into foliage, and slowly arc trickle leak down a tree, for instance, until the tree gets good and carbonized, and establishes a nice carbon arc track. After that you move onto an ionized air plasma arc running down the carbon arc track, of the tree. That is hardly a bolted short, and the over current protection may or may not open the circuit in a timely manner. Trying to foresee anything of that magnitude is akin to picking next week's lottery numbers. Thanks for the great primer on arc flash calcs. It seems like the NFPA has been influenced by engineers with an agenda, yet again. I have seen true bolted shorts, but they are rare, and 100% of those I have seen were the result of negligence and plain old stupidity. We had some 69KV lines with a lot of slack start flailing around, when someone switched on the power, while the medusa was still shorting all the phase conductors to earth. Ooops! One of the overhead pieces of ACSR wound up laying across an adjacent phase conductor. That, unlike the medusa clamped short, was not really true bolted short. Both lines were burned through, and wound up dancing around on the asphalt of a major street, and again, not a true bolted short. The OCP took almost 20 seconds to open the circuits. That 20 seconds seemed like an eternity.
@Brainfiller
@Brainfiller 4 жыл бұрын
The more robust solution would use phase angles but in this illustration, I was showing how determining the magnitude is relatively easy. When evaluating the interrupting rating of equipment, the magnitude is the more significant value.
@s3ltep
@s3ltep Жыл бұрын
how we can Z0 value?
@niksontalan5803
@niksontalan5803 4 жыл бұрын
MVA base is 100 MVA I wont ask you..where are 100 culculate..?
@CHLEOMENTETV
@CHLEOMENTETV 3 жыл бұрын
Nice sir
@nutregina
@nutregina 6 жыл бұрын
yeah, but where to obtain that MVAbase?
@Brainfiller
@Brainfiller 6 жыл бұрын
It's around 2:40 into the video. Most use a 100 MVA base to be consistent with others but technically you can select what you want. Just be consistent. However, 100 MVA means your data is likely compatible with other's data.
@nutregina
@nutregina 6 жыл бұрын
Sorry, my bad. Didn't notice Z was in p.u., and thought if i take any mva i'll get different current every time. That was a bit confusing. But then I saw the p.u. and understood that Z will also be changed
@Brainfiller
@Brainfiller 5 жыл бұрын
In theory, you "randomly" select it however, the industry has mostly standardized on 100 MVA so each entity's data is referencing the same base for compatibility.
@AZZEDDINE2801
@AZZEDDINE2801 6 жыл бұрын
I wish you explain it as Fortescue did on 1918
@Brainfiller
@Brainfiller 6 жыл бұрын
Thanks for your comment. This was only meant to be a brief "how to" for short circuit calculations given Z1, Z1, Z0 from a source such as an electric utility. I go into details such as developing sequence diagrams on one of the live training programs that I conduct.
@sherwinmayas4482
@sherwinmayas4482 4 жыл бұрын
@@Brainfiller Where did he get the 3.12 the Z0
Arc Flash Studies and Electric Utility Company Short Circuit Data
13:39
Brainfiller Arc Flash Training
Рет қаралды 10 М.
Coordination Studies - Preview to the On-Demand Class
8:47
Brainfiller Arc Flash Training
Рет қаралды 9 М.
Самое неинтересное видео
00:32
Miracle
Рет қаралды 1,9 МЛН
POV: Your kids ask to play the claw machine
00:20
Hungry FAM
Рет қаралды 11 МЛН
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 864 М.
Short Circuit Currents According to IEC 60909
38:29
Bentley EasyPower Software
Рет қаралды 10 М.
Short Circuit Current Rating (SCCR) vs Available Fault Current
27:04
Symmetrical Components
39:09
Graham Van Brunt
Рет қаралды 31 М.
Busbar sizing
9:27
stephen brooks
Рет қаралды 131 М.
Per-unit system calculations - Tutorial 1.part 1
12:04
CMTEQ
Рет қаралды 52 М.
Symmetrical Component Method of Short Circuit Calculations
34:38
Bentley EasyPower Software
Рет қаралды 60 М.
Response to: Watch electricity hit a fork in the road at half a billion frames per second.mp4
11:14