Thanks for sharing. I’m changing the 2 nd regulator it’s leaking in the diaphragm and I didn’t know which port to take it out psi going into it generator. I also need a gage to do it. I thought or putting one directly into a port like you did on your primary regulator. $ is the cheapest option.
@TripleTRanchAndSawmillАй бұрын
Glad u figured it out. Just in time for winter weather
@eltonnoway7864 Жыл бұрын
Great video! Very informative... Thanks!
@TripleTRanchAndSawmill Жыл бұрын
Thanks!
@tractorman44612 жыл бұрын
Hot dang you were about as close to full load amps as the Generac could carry with just the water heater !! No wonder the old gal was huffing and puffing !! Awesome job my friend.
@TripleTRanchAndSawmill2 жыл бұрын
Little embarrassed that I didn’t check name plates before any work, but I heard the hi psi reg squawking so I jumped to conclusions. LOL. Love the Frontier videos!
@tractorman44612 жыл бұрын
@@TripleTRanchAndSawmill I do the same thing on occasion....and jump the wrong direction. LOL. The main thing is you got to the answer without too much fuss. I have an old 15 kw propane fired 4 cylinder Onan generator I got off a jobsite. When I got it, it had 700 hours showing on the meter. It's got all the electrical relays and contactors for automatic start but I leave it on manual because I don't want it starting every time we lose power. We are literally 5 miles from the power plant but we can lose power for five minutes at a time. Seldom do we have long periods of outtage. I also would prefer the electronic automatic controls like you have over these electro-mechanical controls.
@billskalicky5400 Жыл бұрын
Generator should have 10 to 12 inches of wc at the inlet of the generator. Your gas pressure is too high.
@-Primer-Ай бұрын
@@billskalicky5400 My 26kw says 3-7 wc on Natural gas.
@acetech9237 Жыл бұрын
Sure do appreciate your time to film this.
@stevethetoolman243510 ай бұрын
Nice video
@Cantfindahable13 күн бұрын
12” is enough
@acetech9237 Жыл бұрын
Could I ask a question? The internal regulator on my unit, there's a propane line going into it obviously. I just bought a 12kw Generac Guardian for 1200 bucks. I'm taking a gamble. Anyway the line was once taped up but it degraded and the pipe is filled with rust. Can I just unthread that from the regulator?
@TripleTRanchAndSawmill Жыл бұрын
I am not an expert on that part. But u got a great deal so I would consider the whole regulator contaminated and buy a new one.
@jameschuke41044 ай бұрын
Naw something else wrong that 23kw cant do a water heater i think you need some training
@TripleTRanchAndSawmill4 ай бұрын
Seisco RA-28-240 tankless electric water heater == 116 amps 22kW Generac model 0065532 generator == 91.7 amps Your right I need training!
@AD17709 Жыл бұрын
That sounds like it needs a new battery.. It is cranking too slow.