This video is about The your heat exchanger is cracked so your furnace must be replaced scam
Пікірлер: 1 000
@michaelshevchenko854 Жыл бұрын
I'm a college student doing the HVAC pre apprenticeship course. My parents believed the HVAC technician, but I figured out we were being scammed. My professor made it clear that a cracked heat exchanger needs to be replaced due to the danger of carbon monoxide poising. I don't know how to fix the furnace on my own, but I had more knowledge than your average person. The fact I saved my parents from spending thousands of dollars that we don't have feels like an accomplishment.
@danieljolson5884 Жыл бұрын
I have a problem with my flue gas pressure switch making up so my burners can ignite. The flue gas blower had failed. I replaced it with a new one. The switch itself is new but when I fired up the furnace it won’t ignite the switch won’t close. I’ve used my fluke meter to verify this. I can pull out the flue pipe to get it to ignite. I also placed a vacuum cleaning on the flue exhaust outside the home and verified very good suction at the furnace. Please can someone help with advice which direction to go THANK YOU!
@scvle00 Жыл бұрын
@@danieljolson5884does the inducer/flue motor start ? if it doesn’t, check if the rollout switches are popped. if it does, make sure it pulls enough vacuum to close the pressure switches. test the switches again by gently sucking the tubing connected to it. should hear a quiet clicking
@scvle00 Жыл бұрын
@@danieljolson5884also , check resistance (ohms) on the switch. should be OL normally. then while gently sucking the tubing connected to it, check resistance and it should give a reading. if not switch is bad
@bertellijustin6376 Жыл бұрын
Check your glue pipe for a birds nest. Can’t tell you how often I’ve had pressure switches that wouldn’t close because of something so simple. If your inducer is good and your switches are actually good and not getting stuck, it’s likely an air flow issue.
@OGXX-bs5bc Жыл бұрын
Problem is sometimes the heat exchanger is more expensive then its worth. Depends on what you are working on.
@thisisme22466 жыл бұрын
As a 32 year veteran of the field, i have always asserted that any mechanic worth listening to will always volunteer to show you where the problem is, and can explain in common language, what has happened and what is the best course of action.
@erkl8823 Жыл бұрын
I'm praying I can find a *good* , *honest* , fella like that. The guys that came by today were very quiet, didn't say much about anything. I had them here to replace the thermocouple on a 1975 (not a typo) Carrier, & while they had it open I asked if they would vacuum out the building up beneath the burners, they did, & then they stood & watched it cycle a couple times & said the flames had a bit of odd movement as it cycled on, which they said indicated a possible hole & therefore could require complete replacement. Then I start reading about how that's how they drum-up work when it's slow, which it's obviously not rn (early January), & I don't think I'm in much of a position to question it, since my heater is almost 50yrs old... Anyway, I'ma definitely get a 2nd opinion since I've read that's a *must* , but ultimately I know the ol' thing's just not long for this world.
@TheDarrlelennis11 ай бұрын
30 years in and I try 2 always explain and show the problem
@nadine912 жыл бұрын
Have a 1969 day and night furnance. It works great. The gas company comes out each year and looks it over, cleans the burners, and looks for gas leaks and so on. Each year I get a different person. The younger ones all say to replace it. The older ones (over 40) marvel at how simple and clean the unit is and tell me the new ones are "junk." They all say their main concern is the firebox, and making sure there are no cracks, which I gather is the heat exchanger? My gas bill in winter (so cal beach area) runs about $90 a month in winter. Otherwise its about $35 a month . My neighbor s newer furnaces run them around twice as much. Anyway your videos are very informative. Appreciate you taking the time and making them.
@TheFizzBand12 жыл бұрын
Found this after getting this exact same story from a local hvac service. The guy seemed nice and very knowledgeable. Spent about 3 minutes then said that the little button had popped up on a sensor for the heat exchanger on my roughly 30 year old home heater system and that I needed an entirely new heater system inside and out. After watching your extremely informative and helpful video, I'm most definitely gonna dig in and do some recon of the system myself... thanks so very much and good luck with your channel. I'll follow as well!!
@brandonandresen37442 жыл бұрын
if its 30 Y/O and the heat exchanger has a crack it would be stupid to dump any money into it...
@Mkjaffar5 жыл бұрын
Appreciate your video, you saved us a headache. a technician came out with the same exact situation you described. Scared my wife while I was at work into thinking we have 100ppm of CO detected in his report. I got a second opinion, who stated this was all false and tested the CO levels with no detection.
@bobbyjayyda14 жыл бұрын
Majed J if they haven’t done a combustion analyst, or pulled out the burners, blower then it’s pure speculation which is usually them trying to sell you a furnace.
@flamaest2 жыл бұрын
I used to live in a condominium location where about every 5 to 10 years, they would slap notices on dozens of doors stating that they detected dozens of heat exchanger cracks and the only way to fix the problem was to completely rip out and replace the whole system. your video helps tremendously. I was convinced that this was a scam, no way that all of the systems would have failed so close together like this having yearly inspections of all of this equipment as a normal precaution. it turned out that the contract for the maintenance of all of these HVAC systems comes up every 5 years and the new companies that maintain the systems want to make a quick buck and force tons of tenants to spend thousands of dollars to pay for new HVAC systems.
@grayfurnaceman2 жыл бұрын
Sounds pretty ugly to me. GFM
@dwaynedickerson3 жыл бұрын
I own small HVAC company and I just wanted to thank you for producing this video!!! It is very informative and correct in every issue that you talked about… There is a NEED for more videos like this one to be on KZbin, so the public can actually be able too do a search and look up a problem, the I’ve found with there HVAC system, so the service person’s diagnosis’s can be validated in the customer’s eyes.
@grayfurnaceman3 жыл бұрын
Thanks for the support. GFM
@dwaynedickerson3 жыл бұрын
@@grayfurnaceman You are welcome!!
@picturemetrollin20938 жыл бұрын
I recommend having co detectors in any home with gas, oil or wood burning appliances. one near the appliance and in all bedrooms.
@picturemetrollin20932 жыл бұрын
@Crack Shot the building code, in my neck of the woods, requires one in every bedroom. But it also requires arc fault breakers for every bedroom, so..... I used to be on your side of the fence, but I got to thinking, and that's where things usually go off the rails, having one in every bedroom would make it a lot safer for heavy sleepers.
@bryanslayter40533 жыл бұрын
You can also do the static pressure test. With the gas turned off and the blower on, hold a burning match in front of each burner where it normally projects its flame into the heat exchanger. Use long tongs or a piece of wire to get the match directly in front of the burners. If the flame of the match becomes distorted or blown out by air coming back, this probably indicates a cracked heat exchanger.
@andrewrossnagel94332 жыл бұрын
This!!! So many people are gonna pay a lot more for labor when probably piss off the service tech when they say he's being dishonest lol. He's gonna take it all apart to show a leak that obviously needs to be addressed. I guess it needs to be done anyway if you are simply replacing the heat exchanger but most people nowadays rather replace the entire unit to save on bills and there's usually a rebate involved on new units
@markmarcantonio5808 Жыл бұрын
So do I just just turn off the gas valve and turn on the furnace and just the blower will come on or do I have to jump something? Then I understand - Hold the match- watch it dance ?
@mrofnocnon Жыл бұрын
@@markmarcantonio5808Nope no jumping anything .
@themonkeydrunken Жыл бұрын
Yes! I use one of those long-necked grill lighters with a flexible neck to get a flame in the orifice. If it dances side-to-side while the blower is on, that tube has a leak.
@michaelerickson15188 ай бұрын
Just turn on the fan and check no need to turn off the gas
@billsteil8002 Жыл бұрын
If the role out which kicks off that's a sign. The heavy gas smell outside the exhaust pipe. The temperature on top of the furnace is over 260 degrees F. Different colored flames bounced outwards not blue but orange. Very simple. I am just an electrician tired of scammers with licenses who cheat honest hard-working people. The furnace guy's job is very hard but good-quality installations are hard to find. Everybody cuts corners and the total job is always not right.
@andydanzig19264 жыл бұрын
I really appreciate you making this video available. I have a ThermoPride Model OL16-25 oil furnace installed in 1993 that has been serviced annually. Every tech who comes comments on what a great furnace it is. A different service tech company, a sub to my oil company, came out a couple weeks ago to do the annual maintenance. He did a combustion analysis (something he said most companies don't do), which said showed a cracked heat exchanger and recommended replacing the furnace. He based this on changes from readings before and after the blower turned on: CO2 from 10.4% to 9.2% and Excess air from 50% to 70%. (He only gave me a printout of the after blower readings, not the before.) CO read 0 ppm, but he said that's not measuring the air in the duct entering the house. His father, the owner called me a week later, to tell me the same thing. When I questioned the CO reading, he said they could measure ambient CO by drilling a hole in the duct work, but that I would be charged another service call for that. I have a working CO detector in the central portion of the house. Isn't CO formed by incomplete combustion or in a low-oxygen environment? Why would it be present from burning oil in air with high O2? The owner of the oil company called me tonight to tell me he was reviewing the service sheets and alarmed the tech didn't turn off my furnace. He offered to send his own tech to run the combustion analysis to confirm if there really is a crack in the HEx. He really hopes there isn't and that I don't need a new furnace. He said if they find one, they're required to turn off the furnace because of the imminent health threat. When I asked if he'll measure CO in the duct, he said they're not licensed to do that. Is this "requirement" to shut off the furnace real or a ploy to sell me a furnace quickly? Because who wants to be without heat when it's cold? Also, if there was a serious problem to be concerned about, wouldn't the CO detector go off and we'd notice a sulfur smell or something? Your thoughts and advice are greatly appreciated.
@grayfurnaceman4 жыл бұрын
First, I am concerned about the change in combustion when the fan comes on. That is an indication that the separation of the combustion gasses with the circulating air has been compromised. CO may or may not be produced but if it is cracked, that could change with more use. The issue of not being licensed for ductwork CO testing is suspect to me. You have a detector, and they are quite sensitive. In some jurisdictions, they are required to shut down the furnace if the heat exchanger has a crack. Generally, if there is leaking combustion gasses into the ductwork, there will be a smell. CO does not smell but other products of combustion that usually accompany it do. Lastly, heat exchangers are replaceable. GFM
@andydanzig19264 жыл бұрын
@@grayfurnaceman Mr. Gray, Thank you for your thoughtful reply. Our town building inspector confirmed that the oil co. is required to shut down the furnace if a crack is detected regardless of CO detection. At his suggestion I called the Fire Dept. which came out right away with 2 CO detectors. No CO was detected at the furnace before and after the blower was on, nor in the air in the house at the vent outlets. Rather than have my oil company rerun the combustion analysis and risk having my furnace shut down, I'd like to have heat while I get estimates for a new furnace in case I really do need one. Does this sound reasonable?
@andydanzig19264 жыл бұрын
@@grayfurnaceman PS. I'll also install a CO detector next to my smoke detector near the furnace.
@grayfurnaceman4 жыл бұрын
@@andydanzig1926 I think you are ok with running it. The CO detector would be a must for me. I also would not let any grass grow under me on getting this repaired or replaced. GFM
@andydanzig19264 жыл бұрын
@@grayfurnaceman A quick update. I hired an independent service guy (from a reputable reference) to check out the furnace. 2 things were readily apparent: 1) the gaskets on the 3 ports that he opened were shot and had to be replace; 2) there was a lot of ash in the heat exchanger and in the flue pipe elbow connected to the furnace. He didn't expect to see so much ash less than 3 weeks after it was allegedly cleaned. He vacuumed it out and searched for cracks by shining light on one side and looking for light on the other side. No cracks were found. I was hoping he'd be able to repeat the combustion test, but he said his instrument was out for annual calibration. He thought the worn gaskets could have accounted for the other readings and assured me the furnace was fine. My next step is to contact my oil company and see if they'll own up to the sloppy work of their technician. Any advice on how to approach them? Thanks again!
@donreinholz81213 жыл бұрын
We had this happen to us by a furnace repair company that uses their fancy camera. We didn't do it so then he said our furnace passed. A friend told me to only use a company that has been in business for many years instead of one that ran a big add in a newspaper with a special coupon. Good advice! Great video!
@Vinces6185 жыл бұрын
color of flame can indicate crack exchange,, not always but is good starting point if you have solid blue cone i wont worry about it
@erkl8823 Жыл бұрын
I have a 50yr (almost, 1975) old gas Carrier model furnace. Does Carrier have a lifetime warranty? Cause that'd be just AWESOME. Otherwise, after 50yrs, I can probably drop my guard when they say it needs replaced? They just came by & were talking about the flames moving oddly when it kicks on, but they weren't sure, & definitely didn't run any cameras in there or say they actually saw any holes...
@grayfurnaceman Жыл бұрын
Carrier has a lifetime warranty on some 90+ efficient furnaces. There is no warranty on yours. The Carriers of your vintage had a habit of getting rust holes in the front of the heat exchanger. That could be causing the flame changing. I would replace it. GFM
@thehvachacker6 жыл бұрын
Good video! I think you should have addressed flame roll out. If I am in front of a furnace with good burn until the blower starts then flame starts dancing and rolling out that furnace gets written up with a bad heat exchanger. At that point, you need to give the customer the option of tearing apart their furnace looking for the crack or hole. Most just want a new furnace when they see the rollout. It will be found yet might take 4+ hours to remove heat exchanger to show them. This means a $500 expense + cost of system replacement unless exchanger still warrantied. Most exchangers on resi last 15-30 years before failing. Unlike RTU that only seem to last 7-10 years.
@kendallang48543 жыл бұрын
I came to the comments to see who else talked about flame roll out when the blower comes on. 100% that's cracked
@Slavelife92792 жыл бұрын
Small cracks usually don’t cause flame roll out depending on location of crack.
@bertellijustin6376 Жыл бұрын
Nah fam, I had this issue once just out of school. Thought cracked heat exchanger. Then got to the control board, tightened a few loose wires and the main molnex plug…..and whammy perfect blue jet flames. Looked like a slam dunk cracked heat exchanger but was actually just loose wires on the control board. Had to call my instructor and tell him about it (he’d said the same thing about “def cracked heat exchanger” in school)
@troydanielboy Жыл бұрын
Any time I've had an hvac person inspecting my 45yrs old Lennox, I've stood over their shoulder so I could "see" what they're talking about. It's STILL running. From the 1970s.
@Denniss74208 жыл бұрын
Seen this scam too many times. I've seen newer high efficiency units where the condensation drip tube was backed up and they were trying to sell the customer a new circuit board. Saw a 2007 Forced Air Furnace being replaced because it had a bad circuit board! Also saw an HVAC company sell customer a 450 dollar control valve (which didn't solve the problem)............................because the Customer didn't even have gas to the unit! Her house got new gas line for a tankless water heater and they left an appliance valve in the off position somewhere in the attic. When I get called for a heat exchanger and cannot find anything (either by using CO detector or physical inspection) I refer them to another HVAC company for a second opinion. Most of the newer units come with a 20 year warranty on heat exchangers.
@grayfurnaceman8 жыл бұрын
Sad when we fail. GFM
@Gatsu1995 Жыл бұрын
I look for carbon monoxide in the return as the hot supply gives false readings, and flame wavering when the blower comes on. Then I verify with a visual inspection. Then we provide options and timelines for the client. Replaced heat exchanger if it is still available, or a new furnace. My local safety authority requires me to decommission the furnace if it is cracked until the system is repaired. Until the repairs are completed I make sure my clients have space heaters free of charge until the repairs can be completed. My clients almost never doubt me because I present them with all of the relevant information in a professional manner.
@KettleBlacktheBat Жыл бұрын
I was also told about a cracked heat exchanger. He couldn't show us in person but he took a picture and there was the tiniest little mark next to a screw. He red tagged us and told us to either pay for a new furnace or use space heaters for the newborn babies (mind you, we live in Minnesota and this was in January. It was - 20 degrees out.) Got someone else out and he said he saw no crack or anything that indicated a problem. We have a CO detector down there that has never gone off. The original guys inspection has never even shown a CO reading. Our furnace is about 14-16 years old. We're afraid of getting another person to look at it because it's hard to tell who has an agenda to try to upscale us.
@DEValentine Жыл бұрын
Same scam pulled on me. They showed me grainy photos of what might have been hairline cracks. But no CO leaks. And the furnaces ran perfectly -- beautiful, steady blue flame. That was four years ago. Still running perfectly.
@jimgill57066 жыл бұрын
My daughter lives about 120 miles from me. Her Carrier gaspac's HX only had an 8 year warrantee. It was diagnosed as having bad inducer motor and the replacement quote was $500. I drove up to replace inducer motor and found that it was running fine but the HX tubes were rusted and had about a 1/4" wide crack along the bottom of the 3 burner tubes. The HX and gaskets cost almost $500. I didn't charge her any labor and it ran like new for 3 more years or more until she sold the house.
@daviddeal15946 жыл бұрын
Yep you can replace the heat exchanger...1 year warranty... later that winter the Induced draft motor fails... next summer the board fails in AC... just keep on throwing parts in... Customer should be given the information and let them make the decision ... I always give the customer the best information I can... then I let THEM make the decision... if the unit is over 20 years old I will recommend the upgrade to 90% technology....
@grayfurnaceman6 жыл бұрын
Agreed. GFM
@toastrecon6 жыл бұрын
While this is true conceptually, how will those incremental repairs compare in price to replacing the entire unit? I mean, even if you had three repairs at $500 each time, no way is that going to outstrip the $5k replacement cost for the entire unit Also, the extra 10% efficiency wouldn't see ROI on $1000 in extra cost where I live for ten years. Assuming (generously) that it would save $20/mo off of a $200 bill during winter (when it was used). I just find it's interesting that the voice of frugality says to maintain and repair an older car, but somehow the only thing that's ever done with HVAC is total replacement, unless it's an ignitor or flame sensor or something. Unless your system is a total dog efficiency-wise, there's no way that another 5-10% is going to make you money back, especially since most people aren't staying in their homes 10+ years, depending on their life situation.
@cooltemp6 жыл бұрын
David Clawson David Clawson when using your math your right BUT 5k for a furnace change out ..... that’s high. Average furnace change out in Los Angeles, California is around 3200. With that being said, you replaced the warranty heat exchanger, then you have those 3 $500 repairs and your at the same price point but with an old heater. All this is obviously contingent on the age of the furnace and if it was installed properly from the start. Plug in 3200 for the furnace replacement into your equation, it will make more senses.
@troyboy20506 жыл бұрын
@@cooltemp Boy I need to move to California oh yeah the cost of living would kill the difference from Oklahoma prices !
@toastrecon6 жыл бұрын
Maybe I should be brave and get a quote. I could have sworn that my friend paid a lot more than $3k. May have overpaid.
@chessdaddy0720 Жыл бұрын
God bless you and you are an honest man. I just had experienced a potential scam last week by a local highly reputable company technician. The guy spent 10-15 min down in my basement, then came up to tell me the heat exchanger is cracked. Without showing me any picture or co test. The repair cost is 3200 dollars, even with the warranty. Yet he recommended me to replace a new one. My current one is 12 years old Carrier. Let’s guess next week’s sales quote for a new furnace. I think it would be more than 10k.
@far-out-reality382410 ай бұрын
in most cases i can tell if there is a crack in the heat exchanger in less than 15 minutes. they were probably right and it is cracked. this gray man video is bull, this guy is not good enough at his job to be able to tell if a heat exchanger is cracked quickly like a good tech is.
@copkhan0078 жыл бұрын
The company i work for goes to the customers house and conducts a visual test of the heat exchanger and if a tiny crack is found they use camera to verify it. The tech then calls the sales manager to verify the tiny crack. The sales manager will then sweet talk the customer into buying a new furnace. The tech does not conduct combustion analysis and shuts the gas off to the unit. The customer panics and buys the new furnace. Both the tech and sales manger get commission on sale. I am now learning how my company scams people.
@grayfurnaceman8 жыл бұрын
Pretty common tale anymore. GFM
@allenclark2715 жыл бұрын
Well if there are cracks and you don't believe the tech. Then you go behind the tech and run the unit, then you just screwed yourself. To many people not trusting techs will get them killed. Yes scams happen but be careful.
@HucksWorld5 жыл бұрын
Can you tell me when installing a furnace do you have to replace the plastic tube that run outside
@GPSJayDog225 жыл бұрын
@@HucksWorld Sometimes yes. If the old tube is the wrong type or schedule. ?Was the original vent installed correctly?,,, If it is the old clear type then YES! Some manufacturers use different size tube for the same BTU furnace depending on length, vertical rise, horizontal length and number of fittings such as elbows 45s, long radius or not as well as vent termination. The only real way to truly know is to read and comprehend the installation instruction. I know this is no easy answer but it is the only way to know. Jay 46 years, sales, service and installation of HVACR equipment.
@Puda4 жыл бұрын
YEP. True story. 3 different big companies came to our place and used that exact technique. We had another guy coming to our house and checking literally everything including the CO levels. Everything was absolutely fine. Don’t fall for it people. Get multiple second opinions. Believe me, it’s not worth the headache!
@AC-io8qs20 күн бұрын
I had a tech point out some flame rollout and a yellow flame on my '97 Lenox and said my heat exchanger was cracked when my furnace would only stay on for a few minutes.. I cleaned the blower, the coils, flame sensor, the flue, the burner assembly, oiled the induced motor, and replaced the high temperature switch and it's working flawlessly. Turns out this model always has a little bit of flame rollout on ignition due to the placement of the igniter. Reading of zero on the monoxide alarms still.
@mikemalone61038 жыл бұрын
Here's what you hAve in the end with a replaced heat exchanger. A $100 saddle on a $10 horse. A month later the blower dies, now your paying more than the replacement furnace, or the gas valve dies. It like putting a new engine in a 98 Taurus. Cars still only worth $200 when your done.
@grayfurnaceman8 жыл бұрын
That's one opinion. GFM
@hvac014538 жыл бұрын
thats the one that will always come back to haunt you. Customer cusses you out, because" YOU " convinced him to spend all this money on a piece of junk and now he's stuck with the bill for a new gas valve or blower motor, venter motor... No good deed goes unpunished... They get this weird idea in their heads you place some kind of timing device to have something fail in a few weeks or months.. I actually had a customer complain, "you were just here last year" was actually two years prior...
@grayfurnaceman8 жыл бұрын
Heard it too. GFM
@KevinJLyons8 жыл бұрын
I wish I had this magical timer that caused relays to blow on boards and bearing to seize!
@mvm93210 ай бұрын
Blower motor is $400. Where are you getting the "thousands of bucks" from?
@JackieGreeneBeauty5 жыл бұрын
Thank you! My furnace got water in it due to high winds and rain. I dried and clean best I could and got working. 1st Got professional cleaned. Then got flame rollout and safety shut off. 2nd guy hit reset told me I need new furnace. 3rd guy checked gas pressure was ok. Still rollout and safety turn off. Checked vents, flue on roof, and finally discovered exhaust vent on top of furnace not connected! First guy must have moved furnace when pulling to clean! 4 service calls and 3 guys with 25 years experience missed this?!?! Reconnected and furnace works fine!!
@grayfurnaceman5 жыл бұрын
Welcome GFM
@fjschneider6 жыл бұрын
I appreciate people like you. Thank you for sharing your knowledge.
@grayfurnaceman6 жыл бұрын
Welcome GFM
@evelynmahoney35692 жыл бұрын
I'm so glad you did this! I was told I had a cracked plenum and they COULD red-tag my furnace but would let me slide if i agreed to buy a new furnace from them for $4,000.00. It was about 20 years ago. My furnace was only 10 years old. I got a second opinion which involved a carbon monoxide sniffer. He said that if the plenum was cracked, there would definitely be carbon monixide registering on his meter, but there was none detected. The scam company even sent me an estimate that included pictures of soneone else's cracked plenum (supposedly mine, right?). I still have the same Furnace. I've never heard of anyone having this experience until your video. It's nice to hear if validated. Edit: Almost forgot - It was Christmastime and they offered to provide a fake receipt so I could claim it on the current year taxes if I agreed to sign a contract for them to do the work in January. Write-off a furnace repair for your main residence? I don't think so!
@jimdesalvo8873 Жыл бұрын
Im going through this now. I have a small house and the guy told my wife 10,000$ for a new furnace
@evelynmahoney3569 Жыл бұрын
@@jimdesalvo8873 Jim, Search KZbin for your furnace symptom. Mine was a loose ground wire, fixed in a few minutes. But the ripoff co. said beyond repair & $4k, can u imagine?! Could be something you can fix urself. If you can get a good idea what's wrong, you'll be able to know whether it repairable, or what part it needs. You can Google the part prices & labor cost, so you're not getting ripped off either way if you DO need to bring someone in.
@mrofnocnon Жыл бұрын
they were nothing short of criminals
@dpeagles9 жыл бұрын
What about when the blower comes on and the flame immediately rolls out the front. Doesn't take long to diagnose that.
@grayfurnaceman9 жыл бұрын
+dpeagles That's an easy one. GFM
@TheChristianCreator6 жыл бұрын
Roll out could be from low gas pressure of restricted chimney....that’s a flag but it doesn’t mean it’s cracked.
@siamakaghazeinali6 жыл бұрын
if the exhaust is restricted you see flame roll out all burners not one. if you see flame roll out on one burner or two or the flames arent even , the heat exchanger has cracked.Thanks
@Deacetis19916 жыл бұрын
Steady flame in warm up and rollout in blower almost always tells you what's up
@scotttaylor30496 жыл бұрын
HVAC Super Tech Hey Super Tech, what he’s referring to is if you have a perfect flame and negative pressure at the burner, meaning a good draft of the chimney, and then flame roll back only when the blower is running. That’s a no brainer definitely cracked heat exchanger.
@Farmhouse1688 жыл бұрын
I've noticed that I am getting a slight oil smell one the first floor in a bathroom. I had the furnace cleaned in the end of October, and just changed the filter myself today. The smell just started recently. The furnace is oil for heat only and probably about 10 years old at most. The burner is Beckett I believe. The last service was very thorough and the tech was here for a very long time. It's forced air. Used for heat only during cold winter months.. If it is a smell, are there other things that can cause that besides a cracked heat exchanger? I looked around and didn't see any oil spillage. Thanks so much. I have been ripped off many times on repair items so your advice is greatly appreciated. Great video also.
@grayfurnaceman8 жыл бұрын
There are 2 types of oil smells. Burnt an unburnt. If you are getting the smell of diesel, (The smell you get when around a diesel fuel pump), you have leak. If the smell is more of a burned fuel smell (like what you smell behind a diesel truck), you probably have a venting problem. Soot blocking the venting or heat exchanger are possibilities. You could also have a crack in the heat exchanger with the burned smell. You might try looking into the barometric damper in the venting to see if there is a lot of black soot in the vent. Hope this helps. GFM
@davidg5207 жыл бұрын
I fired an oil furnace up and smoke come out the vents upstairs,,, pulled the blower and could have put my head in that hole in the exchanger..... and I'm not sure if oil will set off a CO alarm...
@johnshaw16708 жыл бұрын
I just got a call from someone this weekend that was told they had a crack in the heat exchange, and the contractor turned off there furnace with the Idea they would be back on Monday to replace the furnace, and if they canceled the job they would have to pay a 25% cancellation fee. when asked if they where shown the crack they said no, but the contractor told them see the sparkles in the flame! that means you have a cracked heat exchange. All I found was a burned out hot surface igniter no cracks, no signs of cracks, no elevated O2 or CO2.
@grayfurnaceman8 жыл бұрын
Sometimes, I just can't believe what some of these techs do. GFM
@michaelmace9246 жыл бұрын
Unbelievable!! There's so much honest money to be made out here if you're good.
@grayfurnaceman6 жыл бұрын
So true. GFM
@rodneybrand85216 жыл бұрын
John Shaw...my a.c. wasn't cooling right I called a hvac tech..he told me my compressor was going bad and for 1,800 he could fix it I told him to forget it I paid him his service call..called a Friend who had a brother who was a hvac tech..about 20 min's later he came in turned the a.c. on and you could tell right away it was blowing harder and cooler..the A coil was dirty and he cleaned it ..WOW !!! Guess the other guy was trying to make some fast cash..you have to watch some of these guys..Cheers 🍻🍻
@mitchdenner97436 жыл бұрын
@@grayfurnaceman and you wonder why homeowners and do-it-yourselfers are coming on KZbin and watching your videos to try and fix and diagnose their own stuff can't trust anybody nowadays
@deseremere7 жыл бұрын
Very helpful and educational video. Not many industry professionals will talk about it. Thank you
@grayfurnaceman7 жыл бұрын
Welcome GFM
@Niazuma7376 жыл бұрын
So I have this exact situation right now, the furnace tech told me he saw the flame in the first burner bouncing around and told me it meant there was a crack, he tested it for carbon monoxide and was surprised it came back clean, any advice?
@murkyturkey52383 жыл бұрын
No he could be right. If the flame is moving around and not a steady flame it could be a cracked heat exchanger. Ik this is a lil late but he could be right
@blackericdenice2 жыл бұрын
I bought a 1993 house 2 years ago. I was told it need a new Hvac. My heater has had one problem. I replace the door switch the first year. The heat has work fine.
@grayfurnaceman2 жыл бұрын
If it is not broken, don't fix it. GFM
@airecraft19 жыл бұрын
One of our customers was told he had cracked heat exchangers in both furnaces one in fall one the following winter . On the second furnace the tech gave the customer a picture of "A" crack . I searched it there was no crack , the blue dotted a/c contractor sent a second tech out , I met him there and he wasn't able to locate any crack . He did tell the homeowner his kids could die in their sleep from carbon monoxide ,while I was in the room . It upset the homeowner and we ended up replacing the furnaces there was no convincing him that his family was safe , even though I caught the contractor lying to him twice.
@cindytepper88786 жыл бұрын
When someone tries the "kids" scare tactic on me, I always tell them I never really liked the kids much anyway. Throws them right off their game
@Mac-i72 жыл бұрын
Is it better to inspect the heat exchanger through the burner slots or through pulling the fan out? ………or inspecting on both ends? You mentioned it’s easier to inspect by removing the fan however I’ve replaced my fan and it appears the burner slots will be easier to access. I have a 30 year old carrier unit.
@johnnyprotalk33526 жыл бұрын
I love your video “gray furnace man “ very helpful. Helps me learn how to be a successful Hvac service tech. I believe in honesty
@happylucky296 жыл бұрын
I went to commercial work to avoid the sales side of hvac. It seems residential service is mostly upselling unnecessary equipment. With commission based work you will get scams. These big residential hvac companies actually train you on how to psychologically make people think they need new equipment.
@grayfurnaceman6 жыл бұрын
Phillip So true. GFM
@bdi37982 жыл бұрын
Thanks for posting - You mention CO readings in the duct but not CO in the exhaust. A 90 year old couple I know just got jobbed for a new furnace. They showed them the combustion analyzer reading of 8ppm CO and said he was legally obligated to disable their furnace right then and there. CO in combustion gas (at thresholds up to 50,100, or even 200) is expected but homeowners don't know that.
@grayfurnaceman2 жыл бұрын
Definitely a scammer. GFM
@cdb122980 Жыл бұрын
Hi thanks for your video you posted about this I just had a technician come to my home and basically what you said diagnosis within 5 or 10 minutes saying we needed a heat exchanger and or a new furnace and of course my warranty company doesn't want to cover it
@josephmorgan51236 жыл бұрын
Why isn't combustion analysis talked about? I can tell someone they have a cracked heat exchanger within a minute or two of fire up.
@markbeiser6 жыл бұрын
Yeap, well, I usually spend a few minutes eliminating other causes of erratic readings, but you can certainly know there is a problem within a minute or two.
@mitchdenner97436 жыл бұрын
How, excessive oxygen readings? And or maybe lower stack temps? I guess all readings would be diluted with blower air infiltration.
@markbeiser6 жыл бұрын
@@mitchdenner9743 Rising or unstable O2 readings after the blower starts, usually accompanied by high CO.
@mitchdenner97436 жыл бұрын
@@markbeiser thanks , makes sense. Why does the co rise? Adding extraO2+combustion= more co?
@markbeiser6 жыл бұрын
@@mitchdenner9743 Flame disturbance, also a breach in the HX can reduce the over fire draft and actually reduce the secondary air entering around the burner. Using a combustion analyzer I've identified breached heat exchangers that turned out to have holes as small as 1/8".
@BHPaintingRefinishing4 жыл бұрын
The gas furnace in this house is really old. How hard is it to clean it out, sort of afraid that the dust build-up could be big? I do smell a little gas when I come into the room. It is bulti into the wall and vents to a bedroom and the living room, the flue goes to the chimney. No fan noted, If I get a carbon monoxide detector, if it goes off, that is proof to shut down the furnace? Sorry for so many questions, this is a rental property that I or friends have lived in for a long time.
@grayfurnaceman4 жыл бұрын
I would be concerned if I smelled gas in the basement. You need to get someone to look at it. A CO detector is a great idea, but a thorough inspection should be done. GFM
@arborbreeze98845 жыл бұрын
We rescued many home owners from "Aggressive Sales Tactics" who thought to have a second opinion. Our last rescue was a local home owner who accepted a free furnace inspection from a large company over 1 hour drive time away. She had two 19 yr. old furnaces both where diagnosed to have cracks and needed to be shut off. They showed photos & recommended replacing both units asap for safety. We showed up, showed the home owner real time video images that didn't look like the shown to her by the other company, which proved no issues with either units. This home owner was scared for her family from what she was told. We gave her a peace of mind and established an relationship from honest service. This is a real issue that affects all honest companies trying to satisfy customers needs the right way. Aggressive Selling Companies makes us all look bad, Service before Profit will win every time.
@grayfurnaceman5 жыл бұрын
Ah, the second opinion. The bane of the aggressive salesman. Nice to hear there are honest techs out there. GFM
@rollinwithsonny79752 жыл бұрын
Been following and glad I came back to see if that were a scam or not. Had an old Rossoe oil furnace, probably in 1950s made with retrofit parts. A maintenance guy told me there’s a crack and said it would cost 6k to replace heat exchanger because of crack. Makes me thinking…I don’t smell any carbon monoxide and furnace still working fine.
@grayfurnaceman2 жыл бұрын
Put in a CO detector. GFM
@rollinwithsonny79752 жыл бұрын
@@grayfurnaceman thanks. Like you said finding a crack doesn’t take a few minutes to find it. And guess what after he change the oil filter and told me I have a crack in my heat exchanger. I’ve already got a CO detector installed nearby but no alarm goes off. Thanks again.
@MiHeatingGuy9 жыл бұрын
Good video. I have had exchangers ripped wide open and they didn't produce even 1 ppm of co. but on the other hand I have had units with tiny cracks produce over 1000 ppm. If a heat exchanger is cracked its cracked and there may be a chance of co. Older Furnaces should be inspected on a yearly basis.
@grayfurnaceman9 жыл бұрын
+Mi Heating Guy Absolutely agree. GFM
@georgehvac93779 жыл бұрын
I agree. If a heat exchanger is cracked, then the heat exchanger should be replaced at minimal. Even if the Crack is not producing Co at the time of testing, it's still a defect, liability, and potential hazard.
@Bear-cm1vl6 жыл бұрын
Carbon monoxide is only a part of the risk with a breached heat exchanger. Any of the flue gases are unhealthy and potentially toxic as they concentrate in the indoor space airstream. The breach in the heat exchanger allows the flue gasses to leak into the conditioned airstream and allows this buildup. CO makes this effect more dangerous as CO is more dangerous to humans in smaller concentrations than CO2 is, but even with zero PPM of CO, the leaking flue gasses are still dangerous to the building occupants.
@arthouston73614 жыл бұрын
A three minute test that reveals an opening in the heat exchanger without ever taking it apart can be done by noting whether the flame changes from steady to an irregular motion as soon as the fan comes on. The only way the flame will be changed in that way is if air is being forced into or drawn out of the heat exchanger by venturi effect. This is 100% proof of some sort of opening between the burning gas and the air your family breathes. If you make the man take it apart, it will just cost more money and time. Pictures are nice, but note, a lack of a picture does NOT mean you are being scammed.
@ChristianApologeticsTruther5 жыл бұрын
I wish my customers could see videos like this. Sometimes I can jump through all these hoops minus the combustion check and they still call me a scammer. Watch for a rollout and dancing flame when the blower comes on, take the burners out and use an inspection camera, show them the pictures, and then they say that it’s a scam and that carbon monoxide doesn’t come into the house because of cracks. I had a “science” teacher tell me that having cracks isn’t dangerous. I calmly tried to explain to her that it’s true that not all cracks mean immediate danger but that it has the potential to be deadly. In cases like that I say I’m going to shut the furnace off until we can get a new install. I always explain to them that we can replace the heat exchanger if it’s under warranty but that if the warranty is about to expire and they put a new heat exchanger in then it’s not guaranteed to last another 20 years like they think. It’s like throwing a new motor in an old rusty car. Eventually you’ll have to replace the fuel system and shocks and struts. It doesn’t make a whole lot of sense. The part where people get angry is when I try to disable the furnace. I only do this because I’ve had more than one person who was suffering from flu like symptoms only to find out she had a hole in the heat exchanger. Make a video about red tagging furnaces.
@andrzejhajder64055 жыл бұрын
Nothing add nothing subtract,You said everything.
@andrzejhajder64055 жыл бұрын
I just shut off the unit
@dmfb685 жыл бұрын
You're 100% correct. Been there as well. I find it funny when we take our cars to get inspected and if it has an exhaust leak that needs to get fix but God forbid if you should make the same case when it comes to a person's furnace. It's okay/normal to be running a a 35 year old furnace knowing it has cracks but it's more important to replace a one year old cell phone because it's outdated. I've always said it ppl don't buy new hvac systems because it's a boring buy. You can't show it off and brag to your friends about it. can't wait to retire from this field.
@RARenfield5 жыл бұрын
@@dmfb68 Last time I checked the new iPhone still doesn't cost $7,000. HVAC systems have gotten nothing but less reliable. And in the 20 years since I last bought, they've doubled in cost. If you could do something different with the new unit (like you can with your new phone/computer/camera) that argument would make some sense. But you cannot. If the inventor of Air Conditioning, old man Carrier, was resurrected today, he would know exactly how to operate and service a brand new Trane. Nothing has changed in 100 years. Just gotten crappier and more expensive. Heat exchangers used to be cast iron and they lasted 45 years. Why on earth would anyone want to replace their HVAC? The lie that it will use less energy? Ahem. B.S.
@dmfb685 жыл бұрын
@@RARenfield I'm sorry, I'd leave you a comment but there's a bunch of babies that work for KZbin and delete my comments because Their feelings get too hurt on how the real world works.
@robert.tanner74647 жыл бұрын
5 minutes is all it took for serviceman to declare a crack in the heat exchanger was the problem. Furnace stopped and a loud humming noise was noticeable. A new heat exchanger was suggested. Should I get another diagnostic opinion?
@OurJourneyProject7 жыл бұрын
Why can't all people be as honest as you? Thanks for the info!
@grayfurnaceman7 жыл бұрын
Welcome GFM
@klutch14u2 жыл бұрын
Seems like many just don't want to do the work. Plus I think a lot of these guys get spiffs on selling new systems.
@giffy57752 жыл бұрын
I took the heat exchanger out of my oil fired hot air heater and found no cracks after carefull inspection. I installed a new castable liner, rebuilt the burner and cleaned out the chimney. Everything works just fine but when the burner shuts off and the fan is still running, I smell burnt oil smoke coming up through the duct work just before the fan shuts off. When the burner and fan are both on, I don't smell it. Can't figure out what it could be. Thanks Walt
@grayfurnaceman2 жыл бұрын
The only time I have seen that is when the return air has been disturbed and something has fallen next to the bottom of the heat exchanger. GFM
@hvaclife91349 жыл бұрын
its sad people try and scam people. i always bring customer to see crack or hole in heat exchangers to see if possible. my snake cam works best for furnaces
@grayfurnaceman9 жыл бұрын
+Hvac Life Those cameras are one of the best technologies we have available. GFM
@HucksWorld5 жыл бұрын
Looking for an answer if you can help me when we placing a furnace do I need to charge the plastic tubes that run outside
@Puda4 жыл бұрын
The problem is that we have NO idea of what we are seeing are cracks! If you don’t do a combustion analysis, it doesn’t make sense.
@kansascitychief49656 жыл бұрын
If your furnace is so old that you could even potentially develop a heat exchanger issue, you’re probably better off replacing it. Holding onto an old furnace may save you money from replacement but will cost you in the long run from utility bills.
@mrofnocnon Жыл бұрын
Perhaps more maintenance yes but here is often no increase in fuel use. It's not a car you know.
@funkybioped9 жыл бұрын
Is there a way to ask you questions in a private "thread" email or something like that?
@grayfurnaceman9 жыл бұрын
+funkybioped You can go to "discussion" at the channel. GFM
@waytospergtherebro3 жыл бұрын
USB borescopes are under $30 now so they usually go with "I can't work on anything that old and the new model won't fit there so we'll have to put everything in the attic where you can't see what we're actually doing for $20,000" instead.
@jeniferg84929 жыл бұрын
These creeps seek out females, elderly etc. I've been very ill with the stress and the horrible things they said to me when I called up asking what did they do to my furnace?! They mocked me........... I hope I get the last laugh.
@wattamutt8 жыл бұрын
oh my. i know how you feel. we just bought our house in july. its sept. i had the furnace serviced today. i get a phone call at work. he is decommissioning furnace because of cracked heat exchanger. he told me exchange cannot be replaced. that i need a new furnace. $6000. oh yeah they can finance me if i wanted it. im just at a loss for words and im beside myself with anger.
@grayfurnaceman8 жыл бұрын
I do too. GFM
@grayfurnaceman8 жыл бұрын
I bet you have the furnace checked before you buy the next one. GFM
@Denniss74208 жыл бұрын
wattamutt, what happened - Did you get a second opinion?
@wattamutt8 жыл бұрын
Denniss7420 the heat exchanger cannot be replaced. the furnace is at least 30 years old. i had 5 estimate so far. my house is 111 years old. i have no ductwork whatsover. sooooo its going to cost anywhere from 11,000 to 14,000 dollars to replace with high efficiency gas furnace and ductwork. i had and estimate for mitsubishi ductless minisplits with 5 cassetes is 15,800. someone was here today i told him how about a boiler with radiator? that would cost even more because of the pipes. closer to 20000.
@mj77286 жыл бұрын
I have a natural gas carrier furnace in my house. The house was built in 2001 so I'm pretty sure the furnace is 18 years old. A furnace guy came out when my furnace failed to start- found out it was a couple of wires that popped loose at a junction box- but anyway the furnace runs fine and is very clean and the blower motor is nice and quiet. He said because of the age I would need a new furnace very soon down the road at a cost of $5000. How do you tell if your furnace is going bad because of age or if the repair guy is full of it? We also have a CO2 sensor in the basement within 15 ft of the furnace and one upstairs near the bedrooms. Thank you in advance.
@grayfurnaceman6 жыл бұрын
First, the furnace in my home has been there since 1995. I check it regularly. No problem. So your furnace age is not necessarily bad. There are some models that had problems but baring that, most furnaces will last 20 to 25 years. GFM
@jacobdiaz64328 жыл бұрын
potential for carbon monoxide is serious...n u replacing an exchanger in a 1980s unit is a disservice to the homeowner...give them the option of replacing
@grayfurnaceman8 жыл бұрын
As was said in the video, replacement should be considered. GFM
@ottonotzl34543 жыл бұрын
My 40 year Carrier furnace has been red ragged by gas company. I have them to check it every year, but tis was the only time I have not been present. Note on red tag reads: flame impinging, heat exchanger appears to be raptured and compromised. I hired Nexgen company. The tech did a "hydro scan" and told me it will show 100% if the heat exchanger is cracked. I was with him all the time just kneeling next to him. He said "I see the water". I asked him to show me where because I didn't see any. He said at the bottom. I ask if I can check it and I slid my hand inside of the chamber and touch the bottom. We both looked on my finger and there was no water, only little of dry rust powder. Then I slid long wooden stick to touch it all the way in the bottom rear of the chamber and again we both did"t find any physical evidence of water. Then I asked him to spray the outside of the heat exchanger more so if we can really see the water. He water it more but no water appeared. He put in his report that he saw water anyway. He offered and scheduled coming back with his boss and give another look onto the heat exchanger. But next time the tech didn't show up, just his boss came offering me a new furnace. I complained for the tech not to be right and I feel like one of the victims you are talking about. I know the furnace is 40 years old but it is still running fine. I am not sure what to do, if ask both of them to come back, do another Hydro Scan and possibly have them to measure CO at the inlet and outlet. Please give me some advice. And how should I handle gas company red tag? And none of tech I spoke knew meaning of the word "impinging". Thanks a lot.
@deltat57759 жыл бұрын
Grayfurnaceman, I appreciate your experience and knowledge and have been watching your vid's for a long time, but I must take issue with this particular one. I've been an HVAC tech for 23 years and have found many problems with exchangers during certifications and maintenance inspections. I painfully disagree with you about what you said in this video concerning how quickly somebody finds a crack indicates it could be a scam. I have a high definition inspection camera that allows me to see into the exchanger very quickly, in particular tubular exchangers and exchanges with crimp rings.Problems with these types of heat exchangers can be found very quickly. Sometimes within 10 minutes of entering the house. Maybe I'm nitpicking a little bit, but you seemed a little too adamant about that point
@monroekunz13316 жыл бұрын
I've been 35 years abd agree eith you. Heil furnce lot of times rings are laying on top of secondary ican pull that blower and look in less than 5 minutes. Nowadays my first check on any furnace is co level in exhaust after furnace runs for 5 minutes. Use a testo meter you can print findings and leave with customers
@warduke81923 ай бұрын
Any chance you could look at my residential furnace? It is running fine, but I'd like to proactively replace many of the parts instead of just buying a new one. It is a 2007 Goodman unit. No HVAC company I call wants this work, they just want to sell me a new unit. Thank you.
@tvrduude8 жыл бұрын
Been at this trade for 32 years as a service tech myself and happy to see this. Soooo many techs out there think or have been told that a cracked heat exchanger automatically makes CO. Not true. As several have noted here, TEST IT. I will agree that a crack is an issue that should be addressed, but using a likely incorrect scare tactic is what gives our industry a bad name. Now on a side note related.. for very many years I've had a "Thanksgiving theory".. why is it that turkey makes you tired on Thanksgiving..? but not the other days of the year? Ever wondered what leaving an oven (That exhausts INTO THE HOME) on for 3-4 hours while cooking the bird will do to your alertness? I hypothesize that its the long running oven and burners doing it, not the turkey. (of course does not apply to elec. ovens) Just a side observation...worth what you paid for it.
@grayfurnaceman8 жыл бұрын
Interesting idea. GFM
@KevinJLyons8 жыл бұрын
That "theory" of yours is listed as fact by the Godfather of CO and furnaces, Jim Davis. He uses it as an example of low level CO poisoning in his CO and fuel combustion class for NCI.
@grayfurnaceman8 жыл бұрын
On your side note: You may be onto something there. Gas range burners do produce CO. Add to that, you could have 20 people in a house increasing the CO2, which will also slow you down, and it could happen. It would be interesting to see if the CO2 detectors installed in some thermostats for ventilation would come on. Thanks for the thoughts. GFM
@Denniss74208 жыл бұрын
California requires all residential have CO detectors installed - The calls are off the charts. (most of the time for low batteries). Nothing worse than seeing people use a gas oven to heat a house though, sets off the CO detector everytime and is dangerous.
@KevinJLyons8 жыл бұрын
Denniss7420 We have the same law here in Illinois. The false alarms should only be for low batteries. Unlike smoke alarms, CO detector manufacturers intentionally set the alarms so that only go off AFTER the amount of CO becomes dangerous. If you look at the back of your detector you'll see the tolerances listed. They'll be listed as X # of ppm after X # of Minutes. This was done to decrease the number of false alarms. And it works.
@thomasstuart6861 Жыл бұрын
I have a furnace in the old house with a cast iron heat exchanger. Still running, built in Preston, Ontario, Canada in 1964. That was a problem for furnace manufacturers so they came up with the new heat exchanger design which they knew could fail the day it was installed. They introduced a repair kit, if the home owners noticed a smell. The heat exchangers were acceptable to the Canadian Standards Association and the natural gas distributors because the furnace, in the same way as the gas stove, because they could prove even if the clamp rings popped the furnace does not produce CO. It only produces CO when the flame is orange and that never happens they claimed. But it does happen when the blower comes on, it can cause roll back but there has to be over 5 ppm CO for it to be a hazard. As such, furnaces are now replaced every 20 years and that was worth the BS.
@AjDexter8 жыл бұрын
I'm dealing with some of this now so this is super helpful. Thanks @grayfurnaceman
@grayfurnaceman8 жыл бұрын
Welcome GFM
@windelljolicoeur46416 жыл бұрын
grayfurnaceman What about a heat exchanger cover failure
@ittech796711 ай бұрын
Thanks for posting this. We have one like it and seems to have some flame roll back. The flu vent is clear, How would i check for cracks? Thanks again
@edbrandt89723 жыл бұрын
I am getting some flames coming out of the burner tubes. It's not a big flame rollout. The temperature above the flame rollout switch is over 400 degrees Fahrenheit. The switch is tripping now and I have stopped resetting it. My guess is a cracked heat exchanger. Can I replace it as a DIY job? Or am I crazy to suggest that.
@tylerfriesen776 жыл бұрын
A crack doesn't necessarily mean a breach, flame pattern and a combustion analysis will tell you if you have a bad exchanger. Usually you will get bad smell coming off of exhaust due to aldahydes being produced. And yes if you get roll out when the blower comes on you will more than likely have a breach. Carbon monoxide is only produced when improper or incomplete combustion is present, I have seen a full breach on a old 1960s furnace with a ppm of only 7. It all comes down to experience of the tech and sometimes it's the protocol of the company that her or she works for. If you can always ask to see certification of the applicable trade.
@grayfurnaceman6 жыл бұрын
Mostly agreed. I am somewhat nervous about any crack, but if no CO I will get a signature recommend testing each heating season. GFM
@DeWittPotts8 жыл бұрын
Most of what I have observed from other HVAC people is that they will look for 'blowback' or roll-out when the furnace is running. If there is blowback or the flame rolls out from one or more of the burner ports when the blower fan turns on they they will assume that the problem is the heat exchanger and recommend replacing the furnace.
@grayfurnaceman8 жыл бұрын
That's what I use as much as I can. Checked with a CO detector. GFM
@mikemalone61038 жыл бұрын
DeWitt Potts we don't go checking heat exchangers in most part because of the time constraints. If we are doing an initial inspection or evaluation of the unit or during a pm we notice the flame dancing, flame lift or other abnormalities we look further. One time, I was doing an AC pm, and while walking past the unit exhaust pipe, I felt a current of air against my arm. Startled, I knew from the sound that the blower motor was on. Looking further, I popped the top to see a few large slots in two of the tubular runs of the heat exchanger. This unit had a positive pressurized heat exchanger. Being summer, I killed the gas and control wire from the stat to prevent heat. Of course the customer waited for a real cold day and continuous staff complaints till they did something, and then it was hurry up....😠
@grayfurnaceman8 жыл бұрын
Don't you love it when they do that. GFM
@hvac014538 жыл бұрын
yes 3;30 on a Friday the calls seem to come in for problems that occurred early in the week like lets say Monday morning...
@johnmayor1617 Жыл бұрын
1) Check the warranty 2) Do a combustion test 3) Make sure they use a camera and you physically look at the tech and the camera 4) look at Flame Blue flame is properly functional Orange flame is inefficient combustion which could potentially lead to co2
@ZachReifsnider Жыл бұрын
I’m a tech in Va, my brother lives in Colorado. They tried to talk him into a replacement for his 15 year old unit because he needed a $95 gas valve and they couldn’t guarantee something else wouldn’t break since the unit was so old….. think about the logic and apply it to a vehicle.
@grayfurnaceman Жыл бұрын
That tech would have a fit with my personal gas furnace. Its 30 years old. GFM
@robertloney393 Жыл бұрын
Two repairmen from a reputable HVAC service came to look at our cottage’s 9 year old furnace (two stage Frigidaire) that hasn’t worked for several months. They spent 1.5 hours with it and reported back to a third fellow with whom I’ve been in communication. He has concluded that the heat exchanger is either plugged or has a hole in it; he leans toward plugged. (I wonder that he should have to speculate. In 1.5 hours, shouldn’t they be able to see if it has a hole or is plugged?) He said the top door was off and assumes it had been off for a long time b/c that part was covered in spider webs. He said that with that door off, the heat that’s not supposed to be in the upper cabinet cannot escape. Apparently he thinks this situation damaged the heat exchanger. Does that sound right? I don’t think the door had been off very long while the furnace was functioning. And how would it being off prevent heat from escaping? He said the door being off might invalidate the warranty. He recommends buying a new furnace from them and gave me a quote.
@darrellmoody2873 жыл бұрын
Working in the basement with dusty conditions near furnace,Hot air,now living areas are dusty too,door closed,what went wrong?
@jakbo_ Жыл бұрын
Yes it absolutely possible to find a crack within 5-10 minutes. Carrier/BDP furnace develop cracks behind the limit switch which takes seconds to remove. Goodman/janitrol furnace crack at the eyelets behind the limit switch and can also be found in seconds. With that said, a full inspection should be done by pulling the blower and using a camera if cracks are not found behind the limit switch. Also, any service technician that says your heat exchanger is cracked should show you where it's cracked and lrovide you with a picture of the crack. If they can't do that, then they're full of crap.
@far-out-reality382410 ай бұрын
i dont need a camera to know if a heat exchanger is cracked. many other ways to come to that conclusion.
@barrysloas2772 жыл бұрын
With the high static pressure of the ductwork with the blower running, nothing will come out of the heat exchanger- air will go in the heat exchanger and will cause the flame to come roll out-you may get a reading before blower kicks on but if flames are burning correctly you won’t even get carbon monoxide-I have been in the business for 37 years with 10 in tech support
@grayfurnaceman2 жыл бұрын
I am surprised that, with your experience, you would make that comment. There are many swirls and eddys in the air flow around a heat exchanger that, despite static pressure, will allow CO to enter the air flow. I have personally diagnosed numerous times, heat exchanger cracks that both caused detectable CO to be present in the airflow and sickness/death caused by that CO. GFM
@mrofnocnon Жыл бұрын
It's very easy to miss a small crack with a visual inspection, also you cannot see everywhere short of taking the heat ex out. A combustion analysis will do the trick with an experienced user. An increase in oxygen will be shown when the blower blows air into the combustion chamber .Care needs to be taken that the front plate or vestibule plate gasket is intact and not leaking to confuse the issue. A flame distortion test can also be used. Please not carbon monoxide cannot escape the heat exchanger once the fan starts as it pressurizes the outside of the heat ex. However a plugged heat exchanger is a far more dangerous scenario as they spill flue products and C.O the whole time the burners are lit. This is usually easy to spot and many furnaces have a roll out switch that disables the furnace and stops this from occurring with out repair.
@grayfurnaceman Жыл бұрын
Agreed except for the CO. The entrance into the air stream of CO is dependent on the form the crack takes. You cannot guarantee CO will not enter the air stream. GFM
@pjlaske2 жыл бұрын
My furnace tech showed me a photo, supposedly of the primary heat exchanger, with rust spots on it. The video and all the comments only talk about cracks in the heat exchanger. Is it possible that the Hex is rusty, and therefore faulty, instead of cracked? My furnace is 13 years old but the Hex is warrantied for 40 years. It seems odd to me that there is rust after 13 years if the warranty is for 40 years. It is a Bryant Evolution Plus furnace. About how much labor is it to replace the heat exchanger?
@grayfurnaceman2 жыл бұрын
Rust could come from low firing rate or low return air temp. In any case, I would contact the manufacturer about this issue. GFm
@LarryWeston6 жыл бұрын
The labor costs it would take to pull the furnace in most cases plus to disassemble the furnace and cabinet to get to the heat exchanger in most cases could run as much as replacement would be. example: Horizontal application in an already tight attic. if it is mounted on a wall like most in Florida or sits in a garage with easy access then you might come out ahead to replace the heat exchanger. otherwise 25 yrs experience in 4 different states says costs is about the same only the heat exchanger is more labor intensive.
@stayinthemoment182 жыл бұрын
My furnace is 21 years old. I get it regularly maintained. Today the technician came and did his usual inspection and he showed me rust on the heat exchanger with his camera. There wasn't a lot of rust. It was just in about 5 or 6 small areas. He highly recommended a new furnace. I don't know if I should hold out until there's a crack or should I find someone who can replace the heat exhanger?
@grayfurnaceman2 жыл бұрын
If I replaced every furnace or heat exchanger that had rust spots, I would have replaced virtually all over 10 years old. I would just watch and install a CO alarm. GFM
@stayinthemoment182 жыл бұрын
@@grayfurnaceman We've had a CO alarm plugged in right outside our furnace room for years so we're safe as we can be. Thanks for the quick reply!!
@milmil65943 жыл бұрын
I wasn't able to be there during inspection but was told my heat exchanger was severely rusted...no reading of carbon monoxide was showing and he was unable to tell if any of the rust produced or was about to produce tiny rust holes..Also there was a scar in the heat exchanger that was either a crack or a scratch...He said it is difficult to tell the difference between a scratch or a crack on the camera.. I bought this home ten years ago and bought it as a default loan from a bank with no records of the age of the furnace or warranty..I decided to purchase a new furnace..Just to be safe...Could have been a scam but with the rust i really don't trust that holding up long..Wish i woud have watched this video first though and asked for second opinion...It cost 99 dollars for a service call though so a second opinion is pricey...Thanks for the heads up
@Cmill0588 Жыл бұрын
I had an HVAC tech try to scam me. I have a 28 yr old propane furnace. It was failing to light the burners. It would just poof when trying to light the burner. Everything was working just fine except not getting gas to stay lit. The tech used a camera and took some shotty images of the heat exchanger claiming it was cracked. He never checked CO levels. I know symptoms of a cracked heat exchanger and knew he was lying. So I decided check and clean the very basics. After putting everything back together it fired up and never skipped a beat. I later learned that moisture buildup in the gas line was what caused the problem. It’s been 3 yrs since then and it’s still going strong.
@derekkchung2 жыл бұрын
When flame rolls out on one or 2 of 4 the burners, that has to be a cracked heat exchanger?
@kommoncents00004 жыл бұрын
i was told by a HVAC company that my oil furnace heat ex-changer was cracked. I have removed some things on the furnace including an air duct so i can see in the plenum area, and most of the heat ex-changer. I have carefully placed an extension worklight with a 150w bulb in the combustion area through the inspection hole port. I then turned off all the lights in my basement and looked all around the heat ex-changer and it is pitch dark everywhere I look. There is residual soot in the combustion area and the flue, but the plenum and inside the ducts were brand new clean. When the furnace was running my CO2 detectors did not go off or give any reading that CO2 was in the house. A little hard to trust their inspection but I think they may be mis-diagnosing the problem. Any thoughts on my predicament, Thanks.
@grayfurnaceman4 жыл бұрын
A cracked heat exchanger in an oil furnace is somewhat unusual. Not that it does not happen but in 35 years in the business I only found a handful. What was his reasoning? GFM
@kommoncents00004 жыл бұрын
The oil furnace is too large for the house, and he's is now saying that the burner and furnace are too old, he spent about 5-10 long minutes visually looking for cracks in the ex-changer with a boro-scope type camera. He says there may have been some expansion and contraction of the ex-changer as to why it's compromised. Then gave me an option to clean out the soot in there, and try a new burner at the cost of $3200 (burners are what 600.00 at the most + the rest in labor ) and there may still be a crack so a new (smaller furnace) was recommended. When running the flame looked fine to me, adjusting the air band was possible, the flames were not dancing around or blowing back. But before any problems were noticed heavy soot was collecting inside the exchanger and in the flue going in the chimney, all the ductwork and plenum are very clean. What was happening to the furnace was un-burned oil was blowing back on the cad cell and transformer initially and some oil was leaking out the bottom seam of the furnace body. All my burner parts are newer, motor, the parts from the motor to spin the pump, new suntec pump, new primary control. I have a gauge on the pump it is set at 100psi when furnace is working. The nozzle has the part attached to it to prevent post dripping of oil. He is recommending a smaller oil furnace sized for a 1000 sq. ft. home. Here is my video if you want to see what it was doing when it was still operational kzbin.info/www/bejne/b5eVZ3ukh5V0Y80
@kommoncents00004 жыл бұрын
I have called a different HVAC company and they fixed my problem, I did not have a comprimised heat exchanger and I did not need a new furnace. My electrodes were set wrong causing delayed ignition. Other issues were not enough air and too large a flame in the combustion chamber. The pump pressure set at 90 psi instead of 100 seemed to burn better. Another issue was my transformer was not sealing down enough on the body of the burner and was causing unwanted air flow making some oil splash back onto cad cell. My furnace is running very good now. All fumes disappeared after residual oil has been burned off.
@grayfurnaceman4 жыл бұрын
@@kommoncents0000 Glad you found a good tech. Don't lose him. GFM
@stuntcardriver6 жыл бұрын
My issue is with my forced air natural gas furnace, the flames in the burner are yellow not blue. I am guessing the furnace is between 20-25 years old maybe older. I had my usually heating and cooling company send out a guy. He checked everything over except the heat exchanger. He said there wasn't an easy to check it and he said he had ruled everything else out. So $168 bucks and nothing fixed and not really sure its the heat exchanger. He asked me if I had a carbon monoxide detector, I said yes, he said did it go off? I said no, he said I should be fine to run it. I also pulled out the furnace filter because the heat vents didn't seem to have the same volume. He looked at the filter said it was fine and reinstalled it. So after he left the furnace played catch up and I could smell something hot. When I checked the furnace I couldn't hold my hand on the heat vent supply trunk. I thought that was odd. So I removed the filter to increase air flow and within minutes I could hold my hand on the trunk.
@L2fish4 жыл бұрын
I enjoy your videos. Been searching to see if we can figure out what a part is on my girlfriend's propane furnace. Its a metal bar about 24 inches long we were told. Its burned in half and I assume its behind the burners. I wasn't there but the serviceman told her its unavailable. Its a Tempstar SP80 Model NTC5050BFB2. She said the furnace is about 20 yrs old. Looks like there are two bolts on each end with a flange. Here again the guy is telling her she needs a new furnace.
@grayfurnaceman4 жыл бұрын
If it is a small diameter bolt like device, it is a catalyst used on some furnaces to improve emissions from the furnace. If that is what it is, it is not necessary for the operation of the furnace. GFM
@L2fish4 жыл бұрын
@@grayfurnaceman Its like a flat bar but is stamped so it is not really flat. I dont see where it holds a sensor or anything but its obviously in front of the flame since its burnt in half
@grayfurnaceman4 жыл бұрын
@@L2fish Its probably a flame spreader. It is necessary for operation of the furnace. Probably a new furnace. GFM
@bretta29017 жыл бұрын
I hear you brother. I am a hvac tech and personally have only ever condemned a handful for broken heat exchangers. Typically, a busted heat exchanger will cause pressure switch faults or rollout trips. If a company is selling systems on busted heat exchangers, then please. PLEASE, let me give you a 2nd opinion. ha.
@grayfurnaceman7 жыл бұрын
Brett Allen No arguments from me. GFM
@WeatherNut275 жыл бұрын
I had a guy come in try to scare me saying my tenant can die or get sleepy with even just a little CO if the heat exchanger is cracked and told me the unit should be replaced asap. Well.. I replaced it only because the furnace was from 1973! A Carrier. After he removed it I asked him if the heat exchanger was cracked. He looked, he said no holes, no cracks. 47yr old Furnace was still running fine. I don't regret the upgrade though. It was time. $4000 cost included AC condenser, air handler, line set and gas furnace. In CT.
@acanswermantx77303 жыл бұрын
Removing induced draft motor and inserting a camera, while inserting a bright light inside the burner openings outside the heat exchanger is quick way to find cracks as well. Light don't lie. Even a pin hole will show up.
@user-ws2qq3gd5h Жыл бұрын
What about pitting from rust on cells from internally to externally? Would that be a failed exchanger as well?
@grayfurnaceman Жыл бұрын
If there is pitting, replace it. GFM
@horsedaddy2305 жыл бұрын
I have a hanging garage 50 ,000 btu Reznor furnace, I had it inspected and found a very small crack almost a hole at the front that is easily seen. I checked with a magnet and the 3 fins are steel. Can I have the hole welded ? Will this be safe ? Naturally it would be done with the gas off, as its off now. Thanks
@grayfurnaceman5 жыл бұрын
The steel used in heat exchangers cannot be welded. It will simply crack next to the weld. GFM
@j26fremont5 жыл бұрын
I was shown a horizontal crack roughly 5 inches. No flame rollout, and between 0 and 1 for CO count. Decided to do nothing since he said it appears to have been there a long time in a 34 year old Carrier. Am I lucky and stupid, or smart and frugal?
@grayfurnaceman5 жыл бұрын
Lucky and stupid. That is a big crack and it could warp anytime and upset the flame to cause CO. I would not take a chance of CO poisoning. GFM
@j26fremont5 жыл бұрын
@@grayfurnaceman dead right I'm sure. Currently all CO monitors show zero. I'll monitor this winter, and save for replacement. I'm probably wrong about the size. Prob not 5". Thanks
@markrush5013 Жыл бұрын
last winter my 30 year old propane furnance's pilot light kept going out. the guys l called replaced various parts but the pilot light kept going out. finally one of the guys came out and said there was a cracked heat exchanger and the blower was blowing out the pilot light. no parts available for my old unit.10-12 thousand to replace and add another few thousand to redo the chimney since building codes had changed. l didnt go for that and decided to add a couple more wall units...why give 10 grand for something that just burns propane when 500 dollars in wall units will burn propane too?
@ArtistaAndaluz3 жыл бұрын
Thank you for the video. I just had a guy leave who spent 2 seconds showed me what looks like a cracked piece of metal above the burners in plain view and said it’s too old to fix and I’ll need a new $4000 furnace that they can put in tomorrow. He mentioned the CO too but didn’t test. This is the first trouble I’ve had with this 80% efficient natural gas furnace for many years. Its too old for warranty but can it still be fixed? It’s a secondary furnace too and $4k seems pretty high especially when using existing ductwork.
@grayfurnaceman3 жыл бұрын
I would get a second opinion. Cracks in heat exchangers can be found quickly, but it sounds like you are not confident in the service tech. $4000 is not an overly high price. GFM
@ArtistaAndaluz3 жыл бұрын
@@grayfurnaceman thank you so much for your quick reply and opinion! This same guy mentioned replacing my other furnace as well but I fixed it. I have another person coming tomorrow. I appreciate your taking the time to make informative videos and answer questions. Thank you.
@ArtistaAndaluz3 жыл бұрын
@@grayfurnaceman I had another guy out today and he replaced the blower motor, what I told the guy yesterday wasn’t working. A $3500 savings! Thanks again for sharing your info.
@SaintWilliamIII7 жыл бұрын
My Daughter and her husband just went through this and ended up with a new furnace. I was suspicious but they were already scared plus the furnace was an 80%; so they upgraded to a 96% which was good. I did however tell her to inform the contractor to leave the old furnace.
@mwngw6 жыл бұрын
Would a short cycling symptom be caused by a cracked exchanger? What symptoms might be seen in a cracked exchanger?
@grayfurnaceman6 жыл бұрын
A cracked heat exchanger could cause short cycling, but usually it will cause flame rollout which opens a manual reset limit neat the burners. GFM
@markh.28998 ай бұрын
I usually see cracked exchangers on very old equipment and never on units within the 20 year warranty period.
@DP-ez1kt2 жыл бұрын
I have a natural gas furnace. It is 20 yrs. old. I've been having it inspected since I moved here 2 yrs ago. The guy that came last year said that I didn't have to have it tuned up every year. He said that the furnace has an automatic shut off if there is a carbon monoxide leak. Is this true?
@electriccar32532 жыл бұрын
I have never seen one that had a CO detector built in. Keep checking it every year. GFM
@ferdinandalama49442 жыл бұрын
My heat guy told me that my oil furnace has a leakage in the heat exchanger and it need to replaced.He recommend gas heat which is more efficient. I asked him the cost of the unit, he didn’t give me the answer. He said it’s a waste of money & fuel. He tunes up every 2 years.Sometimes I smell a little oil burnt odor when firing or blowing heat out of the floor vent.He tested with combustion analyzer.
@grayfurnaceman2 жыл бұрын
If you are smelling burnt oil from the vents, dump it. GFM
@ferdinandalama49442 жыл бұрын
@@grayfurnaceman This heat guy can do tune up in less than half an hour.Changed the oil filter,nozzle,bleed the oil pump, a little vacuum but not cleaning ir brushing soots accumulation.
@laurenconnell65904 жыл бұрын
I had a furnace tech come yesterday because the blower wasn't working. He said it's likely an issue with the circuit board or CPU or whatever module controls that at a cost of about $800. Then he checked the heat exchanger with a camera and showed me what looked like a crack and put a type A tag on it. I did see the crack and yes it did look legit but this wasn't what was causing the finance to malfunction. It's a 20 year old unit. I'm unsure what to do, I feel like they are pressuring me to buy a new unit which probably makes sense but is this what I should do? Advice appreciated.
@grayfurnaceman4 жыл бұрын
From what you say, I would replace the furnace. The tech sounds like he has done what is necessary to be sure. Of course you can get competing bids. GFM
@nicholasnarcowich91634 жыл бұрын
I had a guy do just what you were talking about, except for the CO meter, that was not done. However, he did cut the silver tape into the evaporator & I wonder if I can just go down to Lows, get some silver tape, fix what was cut, & then see if the heater makes CO, because, maybe, the crack is not yet all the way through the exchanger... what do you think?
@grayfurnaceman4 жыл бұрын
I would want to know if there is actually a crack in the heat exchanger. If the crack has started, it is all the way thru the heat exchanger. GFM
@genepierson17285 жыл бұрын
Do you recommend yearly Carbon Monoxide test of a furnace? I have one that is about 17 years old. It's working fine. Other than changing the filter 3 times per year and a blower motor that failed once, it works fine but I have never tested for Carbon Monoxide. Any advice is appreciated.
@grayfurnaceman5 жыл бұрын
I never argue with someone that wants to do a CO test. It may not be necessary but it could save your life. GFM
@genepierson17285 жыл бұрын
@@grayfurnaceman Good point. I'm just going to order a portable tester and use it to test. It's worth the $160. Thanks!
@amtpdb19 жыл бұрын
I appreciate your taking the time to do this video. Have a nice week.