Net metering Import vs Export the Problem & connection Problem

  Рет қаралды 140,390

Sustainable Every Day

Sustainable Every Day

Күн бұрын

#NetMetering #SolarMeter #BiDirectionalMeter
#SustainableEveryDay
Hi, If you are targeting Solar Industry jobs in Dubai , then this might be "SUPER helpful"
Learn all About Solar Plant DATA analytics & advance report creation:
www.udemy.com/...
Digital CV creation for Dubai JOBS on Solar PV Industry:
www.udemy.com/...
Download File / App Instructions:-
connect with me on Linkdln / Instagram , after sharing the video in a technical group on watsapp or telegram , message Me and drop a request for the file , I will share you the link to download.
For Questions/Technical support connect with me.
Subscribe:bit.ly/2XoCPH8
Linkdln:bit.ly/3xG9tQX
Instagram:bit.ly/3jLSV5e
Facebook:cutt.ly/JQDl7Ba
Quora:bit.ly/3iFvM4X
Telegram Solar Group:bit.ly/3iFC2d9
Twitter:bit.ly/3iEYdQw
IMPORTANT Solar Videos
SOLAR DC cable MEGGER TEST - • SOLAR DC cable Insulat...
Solar DC Cable management - • Solar DC cable Managem...
1500VDC Solar Plant - • 3MW Solar Central Inve...
Solar Plant Thermography - • solar plant thermography
Wrong PR%😭 What to do?? - • Solar PR% issue | Sens...
Solar Plant SECRET - • Solar Plant SECRET , ...
Tilt 📐/ Orientation📈 without PvSyst - • Tilt / Orientation wit...
Solar☀️ Plant 🔺 Thermography❗ - • solar plant thermography
Solar 100kw Plant , perfect installation - • 100KW Solar Plant | in...
Solar Plant power Factor🚫- • Solar Plant | Power Fa...
Solar Plant Specific Yield ?? - • Solar Specific Yield ?...
Solar Plant AC/DC earthing ? Why - • Solar Plant Earthing |...
Solar 🌞Net Meter Fault Solution - • Net metering Import v...
Solar 🌞 PID LOSS 📉♻️- • PID loss in SOLAR Pane...
Solar Plant Measurements - • Solar Plant Measuremen...
Solar Plant 🌞Ground Fault - • Solar Plant Ground Fau...
Solar Inverter Derating 🔥- • Solar inverter Deratin...
Solar Plant Overheating Issue🔥- • Solar Plant Over heati...
Solar Eclipse 🌞🌜Genration Analysis - • Solar Eclipse Genratio...
Free Pvsyst software Book ♻️- • Free PvSyst Documents ...
Solar Plant money Payback Calculation 💵- • Solar Plant Money Retu...
Solar🌞 plant LA earthing Calculation in हिंदी में♻️- • Solar Plant LA selecti...
Types of Solar🌞 cell Fault👨🏻‍🔧 हिंदी में - • Types of Defects in So...
Solar🌞 inverter Selection calculation👨🏻‍🔧 हिंदी में - • Solar Inverter Selecti...
Solar 👨🏻‍🔧Parking 🚕Installation 👨🏻‍🔧 हिंदी में - • Solar Parking | Cost |...
Solar tilt angle & Azimuth experiment🔅- • Video
Middle East Energy expo🔅♻️- • Middle East Energy exp...
How to use PVSYST software🖥️- • Video
Solar AC cable sizing Calculation👨🏻‍🔧- • Solar AC cable sizing ...
Solar DC CABLE sizing Calculation👨🏻‍🔧- • Solar DC cable calcula...
Solar DC earthing systems Calculation👨🏻‍🔧- • Solar DC earthing calc...
Calculate Solar Plant PR%🌞- • Calculate Solar plant ...
SOLAR PV modules comparison🔅- • Calculate How to Selec...
Solar Earth pit resistance Test 👨🏻‍🔧- • Simple Earth pit resis...
Best Solar panel 🌞cleaning method part 1 - • Best Solar Panel clean...
Best Solar panel 🌞cleaning method part 2 - • Best Solar Panel clean...
Renewable energy India Expo♻️- • REI Renewable energy I...
Solar DC👩‍🔧 string Fault Rectification method - • Solar DC string curren...
How does solar panels catch fire🔥- • Solar Cell Hotspot, कै...
Solar cell working in Hindi🌞- • Solar Cell Working in ...
Rooftop Solar plant visit🌞- • Understand solar plant...
How to check Solar Delta Inverters👩‍🔧- • Delta Solar string inv...
Solar Plant thermography test 🔅- • Thermography test of s...

Пікірлер: 435
@rameshdoshi2635
@rameshdoshi2635 2 жыл бұрын
आपका समझाने का तरीका बहुत ही अच्छा और टेक्निकली साउंड है आप बहुत ही मेहनत के साथ एकाग्रचित होकर वीडियो बनाते है और आपकी कोशिश यह रहती है की जिसको टेक्निकल नॉलेज नहीं है उसे भी आसानी से समझ में आ जाए इसके लिए साधुवाद एक 3 फेस मीटर को 3 फेस नेट मीटर से बदल दिया है इसे सिंगल फेस सोलर इन्वर्टर को सिंगल फेस सोलर मीटर के थ्रू ,थ्री फेज नेट मीटर से जोड़ना है तो इसमें फेस सिक्वेंस का कोई महत्व है या नही इस पर भी प्रकाश डालने का श्रम कर हमे अनुगृहित करे धन्यवाद
@668aqua
@668aqua 4 жыл бұрын
Ur doing a very good work. Knowledge is power. You are helping the youth of this nation. God bless you. 👏👏👍
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@kunalsvibe
@kunalsvibe 2 жыл бұрын
21 minutes worth it 😍 thankyou Very much for sharing your experience 😎
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
Thanks for the support
@naveenNegi1
@naveenNegi1 3 жыл бұрын
Very very nice way to explaination thanks
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the support
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the support
@channabasava4234
@channabasava4234 2 жыл бұрын
Explain solar check and soar genertion meter for Genus single phase, L& T 3 phase,
@nihalchand4615
@nihalchand4615 9 ай бұрын
V.good information.tnx😊
@ajeetbais9284
@ajeetbais9284 2 жыл бұрын
Thanks a lot Brother 👌🙏
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
Thanks for the support
@yahiyaka
@yahiyaka 2 жыл бұрын
I love yu our videos and liked subscribed Himanshu bete, I installed singlephase 3kw solar rooftop ongrid. Inverer Sofar. Meter L&T. My problem solar power generated on 3 June 13kw exported 9kw. Pls explain why export is less than generated power, yahiya from Kerala
@nitinpatel886
@nitinpatel886 4 жыл бұрын
Very useful information Sir Thank you
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@rajuptg
@rajuptg 3 жыл бұрын
very good presentation. Nice and informative
@sainathdevlekar7123
@sainathdevlekar7123 4 жыл бұрын
I am big fan of your, your all video is very grateful for me I am always use your tecnic in my side to give better service to my client... Always make such video better experience with you,.
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@mehakindersingh7805
@mehakindersingh7805 Жыл бұрын
Very useful information brother gbu
@amirk9969
@amirk9969 2 жыл бұрын
Well understood. How to open the connection plastic cover in case to renew load wires.kidly advise.
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
first cut off the power supply , then easily dismantel it using screwdriver
@amirk9969
@amirk9969 2 жыл бұрын
@@SustainableEveryDay tks for quick response. Supply is isolated n every care is taken.pse note cover is fitted with 2 nos screws.even after open both screw not able to remove terminal protection cover.ref.Sprint 350.reply highly appreciated.kindly advise.it is easy to remove terminal cover of other 3 phase energy meters.this meter is Slightly different.
@androidstreak
@androidstreak 3 жыл бұрын
Fantastic video
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the support
@Umar_Solar_Nanded
@Umar_Solar_Nanded 2 жыл бұрын
thanks a lot, sir i also learned a lot from your Udemy course also sir, I have a question for what capacity solar plant MFM meter should be used
@Ashish..300
@Ashish..300 3 жыл бұрын
Thankyou
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the support
@vivanthelove4399
@vivanthelove4399 3 жыл бұрын
Very good Sir.
@MaheshKumar-xm7iq
@MaheshKumar-xm7iq 4 жыл бұрын
Sir, Very Informative Video. Nice Explanation, Thanks
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@masood12124
@masood12124 2 жыл бұрын
How to connect hybrid inverter for net metering, What are phase balance issues, how to maintain phase balance
@dharmeshmevada3108
@dharmeshmevada3108 3 жыл бұрын
Men mitar pe 5 kilo wot lagaya hai to kya upar ka kaneksan niche vale mitar me joint kar saktehe
@HS-wy2ts
@HS-wy2ts 4 жыл бұрын
Very good 👍 video 👌. love from Punjab Paji
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@bookreaders7707
@bookreaders7707 3 жыл бұрын
Thanks
@mukundmparikh4187
@mukundmparikh4187 3 жыл бұрын
Appreciated
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
thanx for the support
@vishvajeet7064
@vishvajeet7064 2 жыл бұрын
Site m jo CT ration hota h (ex. 1000/5A)....toh apne meter m iska ulta ratio hona chahiye (ex. 5/1000A) ... Tabhi toh exact reading note hogi...
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
Are nahe yar , aisa nahe hota , meter mai humko same CT RATIO SET karna hota hai
@hemantverma5625
@hemantverma5625 Жыл бұрын
Bhai meter mai pc voltage our cc current our instrument ke hisaab se multiplying factor decide hota hai
@suryaenergysolarsystems3206
@suryaenergysolarsystems3206 4 жыл бұрын
Sir it's very good use full video....solar power Technicians
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
✌🏻
@bhupinderbakshi797
@bhupinderbakshi797 Жыл бұрын
We are not getting bills if we ask for the bill they will generate roughly hence how to check the bill correct bill
@anilkumaragarwal9530
@anilkumaragarwal9530 2 жыл бұрын
I have recently installed a 3 kw solar plant on rooftop . The earlier metre on ground floor is replaced with net metre . The solar power feed is injected to first floor mcb . I am having tenant on ground floor and I live on first floor . My main supply from mpeb is coming to ground floor and I have sub metre and mcb box on first floor .I am facing a problem that my first floor submeter is showing very high reading .not able to pinpoint the reason . I have two quarry 1) whether I should connect solar power to ground floor main metre or feeding power to first floor mcb is o k 2) how can I find out exact consumption of ground floor for calculating the tenant bill .
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
Go with first option
@SouravDas-hh1ts
@SouravDas-hh1ts 4 жыл бұрын
Sir please Give ur Insulation Gloves buying link actually in rubber gloves it's tough to hold but what you using is really good.Please sir
@tejaspatil1589
@tejaspatil1589 4 жыл бұрын
thank you sir
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@tapanmoharana2095
@tapanmoharana2095 7 ай бұрын
Thank you so much sir your video much more informative
@rohitjain6181
@rohitjain6181 3 жыл бұрын
Sir Punjab main bill kaisay aata ha on grid solar system lagane par jaisay fixed chargel or other charge
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Search PSPCL bill on google - it shows you the format they have a website
@solankiharsh7553
@solankiharsh7553 4 жыл бұрын
Sir i request u plz make video on ACDB nd DCDB Wiring Connection..
@navrajsidhu7418
@navrajsidhu7418 2 жыл бұрын
Sir jb se hmne cold store pr solar system lgwaia tb se per day units consumption brh kr 1100 ki bjaiye 2200 units per day ho gaie hai . Kisi ko fault pta Nai Chl riha..!! Help please
@mahipalsinghrathore8546
@mahipalsinghrathore8546 3 жыл бұрын
superb sir
@anmolchandi967
@anmolchandi967 3 жыл бұрын
Jbb home distribution box m net meter se mains supply and solar meter se supply aati h toh ..toh dono lines m full current h ...toh vo join kesi hoti h
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Using CT
@anmolchandi967
@anmolchandi967 3 жыл бұрын
@@SustainableEveryDay ok ct net meter m laga hota h??
@DeepakKumar-qn3ht
@DeepakKumar-qn3ht Жыл бұрын
Can you explain why does Load current getting decreased while Load voltage is near rated value?
@ganeshpowar4725
@ganeshpowar4725 19 күн бұрын
Jabardast... I also worked with BESCOM as PMA for IPDS project 😊
@TakytechParag
@TakytechParag 4 жыл бұрын
Sir mera export and import dono bata raha Par solar net meter se pahle agar mai 7 unit/ day use kar raha tha , wo 13 unit/ per day ho raha Aur export bhi minimum ho raha Yane solar lagane se pahle mai monthly 200 unit la bill pay karta tha Ab 400 kar raha Aur 200 solar k bajah se minus ho rahe Pura kharcha faltu ho gaya Kya wiring me koi prob hui hogi
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Please check CT ratio , per day genration is getting double
@TakytechParag
@TakytechParag 4 жыл бұрын
@@SustainableEveryDay sir mera ghar me jo supply ka wire jata hai wo solar meter k output se nikla hai Kya ye net meter k output se niklana chahiye Waise mseb wale bol rahe the Plz msg me here or on my no. 09405529336 so that I can clearly explain and send my wiring photo
@TakytechParag
@TakytechParag 4 жыл бұрын
Generation meter utana hi generation dikhaya jitna solar create karta Means hints inverter pe dikhata No prob in generation Just I am importing much more
@mukesharya0785
@mukesharya0785 4 жыл бұрын
Aapka import load bad gaya hai, check kare jo aap pahle load karte thy, abhi bhi whi load use ho raha hai ya nhi
@MrV7575
@MrV7575 Ай бұрын
Maine abhi solar bithaya hai, Import units of month - 201 Export units of month - 278 Total units generated of month - 366
@HibaTradingSMCPVTLtd
@HibaTradingSMCPVTLtd 4 жыл бұрын
Buddy how to check phase sequence . or how to know the phase sequence is connected correctly, I've tried all ways still having phase sequence error in inverter
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Phase sequence meter need to be used
@muhammadiqbaltetoo2223
@muhammadiqbaltetoo2223 Жыл бұрын
My load Soler 8000 PV and home load only 1.5 kva but meter showing very low unit export my Dec 2021 135 units and after Soler system 240 units and export unit 110 unit pls gide me thanks
@fmsrworkshop1384
@fmsrworkshop1384 2 жыл бұрын
Is CT available to purchase in open market? if yes what would be the cost
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
yes available
@fmsrworkshop1384
@fmsrworkshop1384 2 жыл бұрын
@@SustainableEveryDay price please
@shashibhardwaj1437
@shashibhardwaj1437 3 жыл бұрын
Kya hum ek he ct se multifunction meter or solar meter connect kr skte h
@ryanfreddysworld6501
@ryanfreddysworld6501 Жыл бұрын
Can you please clarify,when CT is reqd in a solar power plant.Is it when the plant capacity beyond certain power?
@dineshverma1658
@dineshverma1658 3 жыл бұрын
धन्यवाद सर जी कंपनी मे सोलर प्लांट लगाने से पावर फैक्टर क्या प्रभाव पड़ेगा
@hemantverma5625
@hemantverma5625 Жыл бұрын
Solar plant ke running condition mai company ka power factor low ho jaata hai
@lakshmikantpatel3759
@lakshmikantpatel3759 2 жыл бұрын
I wasn't Coll you sir
@saamarth_sollar
@saamarth_sollar 3 жыл бұрын
Please help sir
@mohanprathap1999
@mohanprathap1999 Жыл бұрын
My load is 96HP I am Instaling solar 50kV how much I am maintain PF I am from andrapradesh in with out solar PF we are maintaing 1
@chauhanelectricals5221
@chauhanelectricals5221 4 жыл бұрын
Sir full installation soler on girid set video plz
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Sure soon
@Chandansingh0003
@Chandansingh0003 3 жыл бұрын
I want to know the how net metering work , plz help me
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Logic is simple it records export & import power
@tkgnair4334
@tkgnair4334 3 ай бұрын
This problem of phase sequence comes only if the on grid inverter and solar meter are 3 phase type.But upto 5kw it is enough to have single phase inverter and songle phase solar meter.In that case you can connect it to any phase and there will not be any problem of phase sequence.
@asifiqbal-uc5yy
@asifiqbal-uc5yy 4 жыл бұрын
dear sir Himanshu Tewari can i ask some thing different, in your video behind you these are sun2000-60ktl or 50ktl, you have connect through smart logger 1000 3000a or3000b either you plant is synch with gen set. i have commissioned one plant with 60ktl 8nos and we have 3000a smart logger, now i want to install acrel pz96l zero export device but with gen set can we set direction CT to forward direction and set 20% current setting to reduce power from all inverters. if you have any idea please guide me. we already in touch with mr rizwan and mr aayush huawei technical team dubai may you know them.
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
The plant behind me is connected with a different make RS485 data logger , plant is grid connected and export genration. Yes I know them , also they will have the installer login password they only would be able to make that parameter settings in inverter to sync it with zero export device
@mukeshbhardwaj1756
@mukeshbhardwaj1756 4 жыл бұрын
If ct ratio of metering side is not matching with generation side then how much kwh different or not
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
For eg CT ratio mentioned on CT is 100:5 that means multiplying factor is 20 , but in meter you set it to 100:20 so now the MF is 5 , so if your inverter genrates xxkwh then meter will show the difference as per MF of the active current flowing at a time
@naaz158
@naaz158 3 жыл бұрын
please make a vedio how to connent bidirectional Meter.
@hariharan4022
@hariharan4022 3 жыл бұрын
Hi g Recently I have found that secure Meter perimer 300 in this KVAh was not matching with the multifunction Meter EM6400 KVAh reading Per day consumption difference between the two meters are around 2600KVA
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the info , it may be happening due to CT rating mismatch , or wrong CT RATIO SET IN METER
@saamarth_sollar
@saamarth_sollar 3 жыл бұрын
Pura proper connection kiya hai tabhi Jada import hai
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
CT ratio settings proper hai
@jagdishgupta8778
@jagdishgupta8778 11 ай бұрын
kya solar meter necesary hai हमारे vander ने solar meter नहीं लगाया है now what happens
@samadhanpawar3243
@samadhanpawar3243 Жыл бұрын
Sir, HT consumer hai jiska load 500 kva hai usko 80 kilo watt ka solar plant lagane ka hai to uska metering installation kaise karty hai plz explain
@krishnakantvs7211
@krishnakantvs7211 3 ай бұрын
Net meter is three phase but our solar inverter is single phase and our house load is also single phase How to connect single phase grid to three phase Net meter
@dshah6410
@dshah6410 4 жыл бұрын
sir i have question my solar panels and inverter distances is 15 meters DC code is 4 mm. inverters and both meters distance are 1 meter AC code 4mm. in this case do i lost solar power genret units ? If yes then what is the solution. 4KW Solar Thank you
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Why do you think there will be loss ??
@parbatmodhwadiya4550
@parbatmodhwadiya4550 2 жыл бұрын
What is difference between TVM and ABT meter?
@rpsingh8184
@rpsingh8184 Жыл бұрын
Grid Power low voltage fluctuations stop kernel k liye stabilizer kaise connect kere
@vivanthelove4399
@vivanthelove4399 3 жыл бұрын
Sir mere ekk question hai .ki Abt meter me agar kisi do phase me load jayad hai aur ekk me kam to kyaa to kyaa phase kaa import aur export badal sakta hai.
@mithulthere278
@mithulthere278 4 жыл бұрын
You are so good...so many people don't share their knowledge...but you are explain and deliver ur knowledge to us...keep it up..sir
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@allinoneencyclopedia6501
@allinoneencyclopedia6501 3 жыл бұрын
kzbin.info/door/FFz1VjHmrUr9RbBvlKXqMQ
@zaidi62
@zaidi62 3 жыл бұрын
Sir Himanshu, if there is no color codes types cables installed in residential 3phase connection like an old grid connection and user have only multimeter instead of professional uses phase sequence meter in this situation how to check correctness of phase sequence if it wrong then how to fix? please guide or make a video for common user of small size residential plant holder. thank in advance.
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
By isolating the system and doing colour coading using insulation tape , by checking continuity
@shashibhardwaj1437
@shashibhardwaj1437 3 жыл бұрын
Agar hum usko aise connect krte h to solar meter inverter se kam kWh show krta h
@mamoonrasheed3855
@mamoonrasheed3855 8 ай бұрын
Sir i have 3 phase chint energy meter which show more value rather than bidirectional meter less value
@BabuBabu-dl4id
@BabuBabu-dl4id 28 күн бұрын
Sir do you have user manual for type E3M024
@maddikuntabhoopathi9842
@maddikuntabhoopathi9842 3 ай бұрын
Solar panel meter Laguna emprtent 5kv single phase thanks ky
@karansinhjadejavlogs3310
@karansinhjadejavlogs3310 3 жыл бұрын
net meter kitne phase ka hota he? solor plant me
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Single & 3phase both
@linuspec
@linuspec 2 жыл бұрын
Sir when export is more than check meter generation g?
@SustainableEveryDay
@SustainableEveryDay 2 жыл бұрын
That's not possible , it can happen due to CT ratio inaccuracies
@suvendusahoo7905
@suvendusahoo7905 Жыл бұрын
Sir please sma q solid-50 inverter bare main janchatanhu
@anilpawar8211
@anilpawar8211 4 жыл бұрын
Very useful information sir Thank you.
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Thanks for the support
@raghavaram-uu8mo
@raghavaram-uu8mo 2 күн бұрын
Thank you so much sir very useful
@milindparab5681
@milindparab5681 3 жыл бұрын
Good information. Do you know how to Funcationing HV Net meter
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
you mean , reading the data from the HV net meter yes!
@nageshk9100
@nageshk9100 4 жыл бұрын
Bro ..i have one doubt bro....When load is fully runned by solar power ..then what happened to grid input power at the same time
@mukeshbhardwaj1756
@mukeshbhardwaj1756 4 жыл бұрын
Nothing bez bidirectional meter seans both side readings
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
So Nagesh , if the running load completely runs on total Energy produced by solar during the day , and the load don't require any more power so yor net meter will not so any import nor any export
@nageshk9100
@nageshk9100 4 жыл бұрын
@@SustainableEveryDay Tq Brooo
@AmitKumar-qz2us
@AmitKumar-qz2us 3 жыл бұрын
Generally two same net meter are installed in sereis..with same ct pt... but if we installed it with two different ct,pt with each meter. Than meter will give different readings
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Exactly
@SS-uf1yw
@SS-uf1yw 4 жыл бұрын
Very informative video with diagram. Bhai mujhe ek doubt hai yadi main 2 KW ka system install karu aur 3kw ka load chalana chahta hun to kya remaining 1kw grid se aaega ya solar system aur pura 3kw on grid se aaega .
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Grid pe power share ho jayegi
@SS-uf1yw
@SS-uf1yw 4 жыл бұрын
@@SustainableEveryDay 1) kya heavy load like ac me sharing ki process smooth hogi Bina koi problem k...2) solar power generation fluctuate hota hai throughout the day to kya hamare devices mein problem Nahin aaegi due to frequent change..
@Arif-shah
@Arif-shah Жыл бұрын
netmeter pe reading hi na aarhi ho to kya kare sir ?? its faulty net meter from Electricity board ?? need to replace it ??
@lovelonglife8794
@lovelonglife8794 3 жыл бұрын
You are a electrical engineering god
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
No I'm not god , I'm just a good student
@akshaykumarak8735
@akshaykumarak8735 Жыл бұрын
How to install Three phase main connection with single phase solar inverter
@dhruvgamit
@dhruvgamit Жыл бұрын
Nice video sir. I have one question. I have 3 phase supply at home from Torrent Power. Recently i have installed 5KW solar plant at home with single phase inverter (Sofar brand). The solar technician connected the neutral of solar inverter to the neutral of the grid which is correct as seen in your video. But he connected the Line from inverter to the blue phase of the grid, telling me that with single phase supply from solar inverter , one can connect it to any one i.e. red or yellow or blue. Is it true? Does it make any difference?
@akshaykumarak8735
@akshaykumarak8735 Жыл бұрын
Same problem with me three phase main and single phase solar inverter
@gyanchandra1128
@gyanchandra1128 4 жыл бұрын
Sir plz make a video 3phase net meter ct connection
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Very soon
@ramkumarsharma4139
@ramkumarsharma4139 2 жыл бұрын
How to check inverter and net meter units same in net meter
@mustaqahamed1853
@mustaqahamed1853 4 жыл бұрын
But in Mumbai jaha discom is meter lagta hai bahot conjusted hota hai , waha par puri chawl ka meter hota hai , aur waha se hamare yaha grid supply aata hai , toh Kaise possible hai hum waha par bidirectional meter laga sakte hai .... agar hum hamare ghar mai bidirectional meter lagvayenge toh sahi rahega
@MrKhabbu
@MrKhabbu Ай бұрын
Old meter and bidirectional meter ki size mein koi farak nahi hota hey. Koi problem nahi hona chahiye . Discom wale per chod do aap chinta mat karo. Bada sawal yeh ke aap chawal mein so,aur panel kaise lagaoge .
@amoryblaine1102
@amoryblaine1102 2 жыл бұрын
I don't have net reading? Why? Same model.metre
@greenengineer2130
@greenengineer2130 4 жыл бұрын
i hope separate solar meter requirement is not there, as all inverters are built in with energy meters and online data monitoring.
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Correct
@dekhzarahatk
@dekhzarahatk 3 жыл бұрын
@@SustainableEveryDay Then what is the purpose of installing this meter?
@MrKhabbu
@MrKhabbu Ай бұрын
Solar meter is required to correctly measure the energy produced. The inverter can loose data and a mismatch happens . In my own system I am having this problem . Inverter is showing 6000 units less than the so,aur meter because the data was lost . Solar meter and nett meter are both tallying with each other.
@9422175243
@9422175243 4 жыл бұрын
DOES LOCATION OF BIDIRECTIONAL METER MAKES DIFF. IN TERM OF POWER GENERATION OR CURRENT LOSSES ? IS TOO MUCH DISTANCE BETWEEN GENERATION METER AND BIDIRCTIONAL METER MATTERS ?
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
No , because it's a AC system , transmission power drop is less
@yogirajpawar7260
@yogirajpawar7260 3 жыл бұрын
How practical to calculte self consumption unit from solar system in net meter
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
It shows in your monthly bill
@dlpme2005
@dlpme2005 Ай бұрын
Is diagram me xtra inverter and battery kaha lagaye for night power cut? Mere pas pahale se inverter and battery h
@youssefbouzida3127
@youssefbouzida3127 4 жыл бұрын
Why No English
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
My country has 130million people who need quality education in native language
@karansinghthakur9028
@karansinghthakur9028 4 жыл бұрын
Sir I have 1 question Is it possible practically if I have 1 on gird system and I connect another hybrid inverter with batteries parallel to on gird system with the help of contactors(automatic transfer switch) so when there is No grid supply we can use that Pv panel to supply our load and charge the battery & when Gird resume then it will get connected to ongird inverter (In short wants to make hybrid system like Studer hybrid inverter system but in budget )
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
Yes it is 100% possible
@karansinghthakur9028
@karansinghthakur9028 4 жыл бұрын
@@SustainableEveryDay thank you sir it will me more cost effective become I saw the price list of those inverter in market is around 1.25lac for 2.5kw even though they have more feature and if we go with the combination of 3kw ongird and 3kw hybrid it will cost maximum 60-70k
@jatinderthakur8514
@jatinderthakur8514 Жыл бұрын
Hlo sir please help me 3 phase lt ct meter connection diagram
@dngroupengineeringdesignso486
@dngroupengineeringdesignso486 3 жыл бұрын
HT consumers ke liye Net metering kese hogi...11kv input supply to transformer
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Existing 11KV metering panel , wala meter he replace hoga with a bidirectional meter, the process to apply for the netmeter is the same as for domestic
@vedanthomesolutions2298
@vedanthomesolutions2298 2 жыл бұрын
Sir mera 26 kw ka plant 2 din huye installation kiya he but genrection ka issue aa rha he plz kuch help kar paoge
@vithalkulkarnikulkarni7387
@vithalkulkarnikulkarni7387 3 жыл бұрын
very nice information ... keep it up . we have learnt a lot from your vdo's and installed many solar residential plants so far...
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the support
@anoopthakur333
@anoopthakur333 3 жыл бұрын
Plz creat a video for net meter Kw and kva dimand and
@ravibarot7670
@ravibarot7670 2 жыл бұрын
Sir 3 nos system 3 ph ka 14kw 11kw. 13 kw lagaya he ak penel me ak sath or export zero nikal raha he .. To yahi problem ho sakta he kya?
@shamansamir9243
@shamansamir9243 3 жыл бұрын
I am from utility really very practical himanshu
@SustainableEveryDay
@SustainableEveryDay 3 жыл бұрын
Thanks for the support
@jatinderpalsingh3925
@jatinderpalsingh3925 3 жыл бұрын
Hello bro. Agar import units export units se 100 125 ya 150 units ziada hai.kia phir bhi phase sequence mein problem hoti hai?
@anurag4004
@anurag4004 4 жыл бұрын
Hello sir ek doubt hai agar ghar mein three phase conection hai aur solar inverter single phase ka hai to ye work karega ya phir three phase ka inverter hi jaroori hai please sir cleare my doubt
@SustainableEveryDay
@SustainableEveryDay 4 жыл бұрын
It will work , just connect single phase solar inverter with any of the one three phase R,Y,B
@anurag4004
@anurag4004 4 жыл бұрын
@@SustainableEveryDay Thank you Sir
Never Install Low genrating Solar Plant | What to Do?? | Increase Genration
12:21
Solar Plant Earthing | Chemical Earthing | LA , AC, DC earthing
18:59
Sustainable Every Day
Рет қаралды 227 М.
Inside Out 2: ENVY & DISGUST STOLE JOY's DRINKS!!
00:32
AnythingAlexia
Рет қаралды 13 МЛН
ОТОМСТИЛ МАМЕ ЗА ЧИПСЫ🤯#shorts
00:44
INNA SERG
Рет қаралды 4,8 МЛН
Watermelon magic box! #shorts by Leisi Crazy
00:20
Leisi Crazy
Рет қаралды 60 МЛН
Solar Plant Measurements | Voc | Isc | Vmp | Imp | +ve to earth -ve to earth
11:35
Solar Plant | Power Factor Correction | PF | Calculation
11:18
Sustainable Every Day
Рет қаралды 26 М.
Inside Out 2: ENVY & DISGUST STOLE JOY's DRINKS!!
00:32
AnythingAlexia
Рет қаралды 13 МЛН