Great tip on the bend first then trim! Not that I'll ever be installing 16mm2 cabling but I enjoyed the little bit of learning something new.
@MrCarnivoure Жыл бұрын
Those were 25mm2
@robertburrows6612 Жыл бұрын
Thank God a sparky who trims the tail when they put bends in them , I've been convinced for years I was the odd ball , because I've always done done it, because I had good sparks that trained me, I give you 5 stars, in fact I would say your one of the best sparks on KZbin
@corymac Жыл бұрын
Awesome and engaging video Mike. Not to mention insanely well shot 🎥
@michaelbarlow3686 Жыл бұрын
Excellent Video Mike Best Wishes from a retired time served sparks
@thetruth6693 Жыл бұрын
Your videos have come a long way Mike 👏 I havent messed with much TT either but I always thought they had to have a 100mA time delay up front and then 30mA covering everything else. None the less looking forward to getting educated with the next vid 👌👌👌
@tomorichard Жыл бұрын
100ma time delay rcds are required to provide fault protection whilst keeping selectivity with other circuits. These days with metal distribution boards as Mike has touched on, with tails clamps the incoming tails can be considered appropriately protected from fault protection and apart from spd conductors (which in my view require fault protection) all over wiring should be protected via rcd to achieve relevant diss notion times.
@edhunter84 Жыл бұрын
Worked for BG on metering for 10years. Thats a smet1 smart meter. The extra bit connected by the wire is the coms hub. Seriously doubt BG would authorise the move but maybe the supplier has been changed to a smaller less anal supplier. Looks like you’ve done a better job than some meter fitters. Couple of things, theres a marker on the side of the isolator to make sure enough is stripped back. With multistrand meter tails I like to get some pliers on the copper and unwind/flatten the end thats being terminated. We were always told to try and go into the isolator on the topside, purely because if the cables became loose they wouldn’t be able to drop out exposing live conductors (the chances of that happening are slim to none with double screw terminals but stranger things happen).
@temp06j723-pmeighttq Жыл бұрын
Wouldn't you agree that the Meter's Incoming Line(L) would probably fall off too, towards the gravity ; hence posing the same abovementioned Hazard?
@treehouse786111 ай бұрын
why have 2 hazards when you can have 1?? @@temp06j723-pmeighttq
@UKsystems4 ай бұрын
They can authorise the move if they hold the buildings coming down and they don’t have any availability to get it moved
@AronBrynjar27 Жыл бұрын
can you do an updated toolbag tour???
@luke_swift_mjq Жыл бұрын
Such a quality video! Looking forward to the earth rod install!
@CarlosArruda77 Жыл бұрын
Be careful with that very initial statement. Often the DNO can put that fuse the wrong way up! Plus, only the customer's supplier should be moving meters. I'm surprised the DNO and the suplier refused to move the service and the meter. The DNO is not known for refusing paid work. That seperate unit is the comms hub.
@davidduckworth9094 Жыл бұрын
That is correct it is down to the DNO. However, where was your testing? No testing on cutout or the meter.
@tommackay2660 Жыл бұрын
Rcd main switch satisfies fault protection this is determined by the resistance of the earth electrode- 100mA is commonly used however this theoretically could be as high as 500mA. 99.9% of circuits will not comply with the maximum zs of the OCPD as per bs7671 to allow for 0.4s disconnection time. 30mA additional protection counters this and allows for ADS of supply.
@dudemar1000 Жыл бұрын
Amazing, I was wondering how this might be done just the other day. Thanks for the upload, look forward to the TT electrode installation.
@Ragnar8504 Жыл бұрын
VIR cables/singles have vulcanised rubber insulation and I've been told the vulcanisation of the rubber during manufacturing would oxidise bare copper conductors, which is why rubber cables and flex always had tinned conductors until fairly recently. Not sure why some UK manufacturers continued to use tinned copper with PVC, haven't seen that anywhere else. Force of habit maybe.
@tonywebb9909 Жыл бұрын
Tinned copper used on high voltage D.C solar cables
@james5553 Жыл бұрын
I use it in a lot of marine installations@@tonywebb9909
@alangriffiths8401 Жыл бұрын
Could the meter tails and earth have been fitted before offering up the Consumer Unit into the box and fixing in place. Some very good tips in the video thank you.
@tomorichard Жыл бұрын
100% the best . Some others carry out questionable work which is unfortunately taken as gospel. 👍 truly great at his job
@dataterminal Жыл бұрын
Cool video, thanks for that. Nice to see it from a different view point outside the realms of the DNO. I had our meter replaced about 6 years back, and the guy that came got dressed into a fully cloth suit (that looked like the outer gloves you had) and what looked like rubber gloves red inside, and black on the outside. No cloth outer gloves were used from what I remember, but he did wear a fold down mask. To be stood behind him watching as he got dressed up for this, me thinking... hang on... don't I need some kind of protection here lol. Thankfully, the fuse was pulled and replaced within minutes and he got undressed again.
@0liver0verson9 Жыл бұрын
There's only one true gripe I have with customers when I'm working, and that is when they stand directly behind me watching like a hawk
@dataterminal Жыл бұрын
@@0liver0verson9 You'd hate me then. I'll even ask if you need any help or want to borrow some of my tools. 👌
@0liver0verson9 Жыл бұрын
@@dataterminal oh god no haha
@stevedebbiemoore Жыл бұрын
Tbh not a bad effort, I used to train and asess MOCOPA for British Gas and a bunch more and apart from some anal Nuances you did a great job. The main considerations are first and foremost correct polarity, then tight connections (loose wires cause fires) , no copper showing, no extreme bends in cables job done.
@stevedebbiemoore Жыл бұрын
@@residualelectrical don't sweat it ,those of us that subscribe know how committed you are to quality workmanship 👍👍👍
@JohnSmith-ws7fq7 ай бұрын
You got a pair of those sweet Mocopa pliers?😉
@g7eit Жыл бұрын
Where I live I am the electric supplier so I fit meters all the time. The DNO come out occasionally to add bits, they swear at me then leave. Happy days.
@AndrewBaker-z9r Жыл бұрын
Great work mate, very competent electrician
@systemalive11 ай бұрын
Used to work with a guy who spent years working on the railways, he told me a horror story about this poor bloke who pulled a 2A fuse in some electrical hut, it was damp, the fuse and carrier was rusted. The resulting arc blew most of his fingers and hand off…
@09weenic9 ай бұрын
Crikey that’s horrible . I knew someone who hacksawed through a ‘live’ SWA cable - they thought they isolated the cable after testing it with a voltage pen 😖
@Dooguk2 ай бұрын
I know of an electrician who hammered a screwdriver through an 11kv HV cable. He thought it was a red street lighting duct. This happened right outside a substation, so the HV tripped out immediately. He was still left with 60% burns.
@electrician247 Жыл бұрын
Signed up Tado. Great shout mate and awesome to hear they are supporting you! Promise not to clip the video and share it out if context as Mike helps us all bypass our meter 🤣. Top job.
@Swwils Жыл бұрын
Tado are on last legs. They haven't improved the product in years.
@edmondkelly1942 Жыл бұрын
I am a spark and I a contractor. I don't under stand why the DNO companies don't licence guys like us to be able yo break seals etc. I am not saying all of the time but in certain situations. Like most if not all responsible contractors we don't really have anything to gain from messing around with meters. So if you did a job and put your licence no on it and then take a photo of your work and submit it you should be good. Any
@stephenwillis9518 Жыл бұрын
What would you do if the cut out decided to fall to bits, live and neutral came together and was arcing continuously? With the potential to burn a house down. I wouldn't imagine you having procedures in place to arrange substation access to pull fuses or have digging teams and live cable jointers avaliable to cut the service cable ? Pulling a cut out fuse is easy when everything goes right, DNO's have specific training, ppe and procedures when 🤫it hits the fan.
@stephenwillis9518 Жыл бұрын
@willmitchell255 really think videos like this on KZbin shouldn't be posted purely because it gives other sparks justification to do the same. If something went wrong here, the HSE would have an absolute field day, so many wrong doings that you have to ask yourself why would you want to do it in the first place?
@stephenwillis9518 Жыл бұрын
@residualcurrent I agree, meter operators are trained and authorised to do this so why not sparks ? Surely having more training is safer ?
@UKsystems4 ай бұрын
They generally do, but they require a bit more than just allowing you. The main issue is if the cutout fuse holder was to disintegrate which can happen or something they have to ensure you can correctly deal with the situation.
@itsmyview2024 Жыл бұрын
Sorry if i missed it but did you check the polarity? Nor unknown for jointers to get it wrong.
@georgecorden9526 Жыл бұрын
I agree. I’m a jointer, and been called to some pretty sketchy set ups by fellow jointers
@retrozmachine1189 Жыл бұрын
Yes, was just about to comment about polarity and an independent earth test to confirm it.
@inothome Жыл бұрын
He would have definitely found out when he fitted the neutral from the meter if it was swapped. But yeah, always check first so you don't find out that way.
@UKsystems4 ай бұрын
He may have tested that at the consumer unit, not at the meter or cut out due to the fact that he’s done the rest
@MizunoIronMan Жыл бұрын
Quality content as usual Mike.
@syntaxerorr Жыл бұрын
Great video. It's crazy how different panels are between the UK and US.
@yaboi7376 Жыл бұрын
US is a joke
@Wintersky136 Жыл бұрын
Compare a german panel to a panel in the US… and you notice that US electrics are stoneage shitshow electrics!
@arjanvanraaij8440 Жыл бұрын
@@Wintersky136 They say that they went to the moon and back.
@Daniel.Dalziel Жыл бұрын
As always quality video Mikey 👌
@Phil-Sands Жыл бұрын
Why not push the tails through the nut, then the holes in the gromet then screw them into the fuseboard gland?
@sajidsajid-st7oc Жыл бұрын
Awesome video. Enjoyed the journey.
@Mike_5 Жыл бұрын
Great upload love a Green Street Cabinet install like this all you need now is some local youths to come round and spray paint graffiti on it and the jobs a good one!
@PaulWebb-w8d3 ай бұрын
Great job , I taught Paul Meenan
@dantheapprentice6261 Жыл бұрын
Amazing video mate once again just learnt loads in 30 mins thanks Mike 🫶🏼
@shiamjad Жыл бұрын
Top content .... your video is really helpful for a sparky like myself. keep making such videoes....SUBSCRIBED
@OvhanDevos Жыл бұрын
Isn't using your cutters on your alan key like that going to dull them?
@twan9615 Жыл бұрын
Good video and nice install! I would advise wearing a flash jacket and face visor when working on a cut-out. Also I would imagine the meter, cut-out and isolator were not sealed after?
@hallga2 Жыл бұрын
Nice thoughtful work!
@Wintersky136 Жыл бұрын
14:07: TT-System: Incomer -> Meter -> Small enclosure (Mains Switch & RCD 100A, 30mA, A) -> Consumer Unit! Always keep in mind the logics about cascading RCDs!
@michaelcostello6991 Жыл бұрын
Thanks for sharing your knowledge
@M8d9R Жыл бұрын
Great work mate, very interesting video 👍
@markpunt96389 ай бұрын
Presumably request to remove was refused but they would have installed a new supply but that cost would’ve been horrendous?
@andychara1631 Жыл бұрын
Another great video mate. Question. Can the isolater switch have the meter tails go in through the top or bottom going out to the consumer unit? i always though they should go through the top from the meter and coming out from the bottom for the consumer unit. keep the vids coming they're great .
@rayc1503 Жыл бұрын
It's essentially a double pole switch, so it can be either top or bottom as long as the tails are adequately supported.
@chrislane3974Күн бұрын
Always at the top for meter tails as if it was on the other way round like this , any debris in the top of the switch then it would have to stay there.
@g.williamswilliams84423 ай бұрын
Nice job Good video Not easy with those gloves on.. well done
@bipedal-ape-man3 ай бұрын
1:19 what is the actual name of that thing and do all boxes have them?
@Dooguk2 ай бұрын
It's a cable joint. In this case the plastic single phase cable is jointed to the original paper lead cable feeding the property. This is done with the paper lead cable live. Don't attempt it!
@bipedal-ape-man2 ай бұрын
@@DoogukThought it was some kind of male/female socket connector. was thinking why people dont just dig a hole and find a compatible Y or T adapter. But yeah, an unfused live is no joke.
@stephenwillis9518 Жыл бұрын
The old tinned copper tails could potentially have asbestos lining in the rope 🫡🫣 always worth just bracing the cutout with the back of your over hand, chipboards crap at holding screws in 😂 polarity checks maybe 😬
@ShalomBrother Жыл бұрын
I’ve never heard of VIR tails having ACM’s in them and I’ve been working on them 22 years.
@alistair1978utube Жыл бұрын
@@ShalomBrother I’ve never heard of a plural having an apostrophe in it and I’ve been working on them 40+ years.
@ShalomBrother Жыл бұрын
@@alistair1978utube me no understandy
@mondoabz Жыл бұрын
If you are going to the trouble of double gloves do you not think your flash proof T shirt might need uprated too? 😂
@Dooguk2 ай бұрын
Flame retardant overalls and a full face visor was the order of the day when I was jointing, no matter what the temperature. Or else was bollocking time.
@ArthurTugwell Жыл бұрын
The tinning of the copper cable helps with corrosion resistance 👍🏼
@inothome Жыл бұрын
Agreed, used to be used more, now mainly just on panel SIS wiring and cases where it's needed.
@treehouse786111 ай бұрын
@@inothome not alllowed on meter tails
@inothome11 ай бұрын
@@treehouse7861 You can't use factory tinned wire or do you mean manually soldered ends? I know soldered wire is not good for screw or compression type terminals, but individually tinned strands is used in almost all panel wiring in substations. We call is SIS wire in US. Its copper strands with a very thin coating of tin.
@treehouse786111 ай бұрын
any of it, meter fitter for 10 years, only copper allowed or it gets taken out@@inothome
@njcelectricalservicessheff96849 ай бұрын
safe to an extent no eye protection?
@360stav Жыл бұрын
Dno have their own codes of conduct, when you see a baked in main fuse and they have to pull it revealing the line terminals. The main switch was isolated before we start chatting about under load. Nothing to do with this install
@kentmasic Жыл бұрын
great video but i think you might have put your main cpc in the wrong terminal in your earth block as you put it in bonding - when it should go in E
@kentmasic Жыл бұрын
@@residualelectrical fair enough mate, in fairness i wasnt sure myself and i knew you would of had a reason as to why, just wanted to point it out to you just incase :)
@greentoad6729 Жыл бұрын
over killed the PPE you forgot a face nappy buddy lol
@ImranKhan-cf8gs10 ай бұрын
Keep it up good job mate I have done that as well before
@sergiofernandez3725 Жыл бұрын
Really enjoyed that video Mikey. Worth checking that mains iso is wired correct. Some isolators have the supply at the top and the load at the bottom. I am looking forward to the next video for the TT earth rod/spike
@ridefast0 Жыл бұрын
I would worry about putting the main fuse in before the ground rod is connected. If the meter contains any filter capacitors from L to G and N to G, you can get half the supply appearing on the ground wire if it is not grounded. I had a small shock due to this effect from a filter in a washing machine. Please be careful!
@inothome Жыл бұрын
There is no ground on the meter, or at least I didn't see one on the original installation or on his. But in instances where there are the Y caps, that can give you full line voltage if one fails on the line side.
@UKsystems4 ай бұрын
Capacitors have to have discharge resistors on supplier equipment generally and where is the earth connected?
@kevinpoore5626 Жыл бұрын
You got to just love When you're their only hope no matter which side of the pond Iran LOL
@FluxLabsProjects Жыл бұрын
Decent vid, thanks!
@aphaseelec Жыл бұрын
Nice work king
@johnhoward2104 Жыл бұрын
Another interesting video, as always. Could've done with a light shinning in there though as it was a bit dark in there, hindering seeing what's going on. That rope cable you referred to may have been braided VRI singles - not to be disturbed as they can contain asbestos.
@simonmartin3433 Жыл бұрын
Rule of thumb keep the tails short on TT system and fix with cleats.
@jamesgee4748 ай бұрын
Always connect neutral 1st when making it off into live cutout
@reeceoverton1421 Жыл бұрын
That t handled boddington is the same size for the isolator
@danielelise7348 Жыл бұрын
Hey mate,where can I get one of those t-shirts? Cheers from Australia.🇦🇺⚡🔌💡
@timballam3675 Жыл бұрын
We're having our supply unlooped, National Grid can't do it in time so they have a contractor doing it, they can't move the meter so it'll be fun....
@ArthurTugwell Жыл бұрын
Sorry to ask, but what does ‘having our supply unlooped’ mean?
@adriantyler277 Жыл бұрын
Means it's being tapped outside. Rather than looping in and out of the incomer inside the house.
@ArthurTugwell Жыл бұрын
@@adriantyler277 thank you. so what’s the need/benefit for doing that?
@Sparks0001 Жыл бұрын
@@ArthurTugwell A looped supply means that the supply cable from the road serves more than one property, looping from property 1 to property 2 for example, which results in a lower maximum supply current, which can be an issue if you want an EV charger for example. Being unlopped just means you are getting your own supply from the road, or whoever was feeding from your supply if you are first in the chain is.
@ArthurTugwell Жыл бұрын
@@Sparks0001 thank you!
@MrCarnivoure Жыл бұрын
How do you know if you cut correct length of conductors into top of cutout? You haven't checked impression on end of conductor on bottom screw. Since you have it done first time as you dont work for dno or energy company, you should have double checked by pulling out conductors in cutout after making initial impression by bottom screw. Seen many sparkys tampering with meters and tails and being cocky by only terminating conductors on one screw or 1 and half of other screw. Saying " That should be long enough " if you doing something first time, without double checking, that's cocky.
@Daniel.Dalziel Жыл бұрын
Don’t think he’s cocky at all, he’s very passionate about the industry and a very smart guy. Criticism is fine but no need for the hate brother ✌️
@UKsystems4 ай бұрын
First we would know from his other videos if you watched them he did make a demo board once and he’s done it but the likelihood is these can definitely have data sheets telling you how to terminate them correctly
@MrCarnivoure4 ай бұрын
@@UKsystems i work as meter engineer. I see many different cutouts every day. Over last 70 odd years there have been fitted dozens of different cutouts across uk. Some of them you can visibly see if your conductor is adequately long. In this case of this type of cutout you can't see it. The only way is to stick conductor in, do impression from the bottom screw, pull it out to visibly confirm. This guy clearly is not fitting tails into cutouts every day, unlike DNO engineers (who may get a pass eyeballing the lenght of conductor due to their daily experience) . And he clearly said in video that it looks alright but he is not 100% certain. And that's not good enough for me.
@UKsystems4 ай бұрын
@@MrCarnivoure really be 100% sure on these anyway the manufacturers actually recommend specialised and load testing
@chrislane3974Күн бұрын
@@MrCarnivoureThank you for your input as a meter operator. I'm a jointer. I love the pig tails, unmarked tails, no thimbles, tails in the wrong side of the switch, (The dno / mo installer can remove and tap out the debris safely) no proving of the iso switch. So much to go wrong! Let alone bare arms and a tee shirt. Let's hope the switch or meter isn't faulty. 100 amp fuse on an temp supply, 60 amp would be better. Take care young'un
@justastulpe326511 ай бұрын
hi, can you mess up with tales after the meter that are going to the house? want to install generator Transfer Switch
@UKsystems4 ай бұрын
This appears to be a DIY comment. Crack me if I’m wrong but you have to be qualified as it is notifiable and part P of the building regulations companies can create a bit of a hassle if what side does not match records you really need to get someone unqualified to do this as depending on how the generator is you have to do a lot of changing in the earthing
@cliveramsbotty6077 Жыл бұрын
very interesting thanks
@drake19891 Жыл бұрын
Is that a skin on your impact driver? Link?
@residualelectrical Жыл бұрын
yeah, i got it of ebay, M12 impact rubber boot is the name
@tomorichard Жыл бұрын
Not entirely sure this complies as you have no fault protection to the cables from the MCB to the rcd sockets due to exceeded ZS values??
@tomorichard Жыл бұрын
@@residualelectricalahh sorry buddy,👍 I’m guilty of not finishing the whole thing yet. 👍 production looks amazing on this one so far 😊
@craigmitchell4945 Жыл бұрын
I agree with other comments on here regarding moving a 1ph meter dno’s will move 1ph meters providing electrician has a bs7671 test to prove they have done dead tests on all circuits to prove there closed circuits there isn’t a cross polarity or short circuit potential . DNO’s and the one I work for will not move smart meter’s that would be the energy provider’s responsibility to do. Also when ever pulling the main fuse of a cut out you should always do your polarity checks and a efli reading as well. In this case you would use a volt stick first to make sure main fuse is live and a no light on the neutral to prove there is not a cross polarity. Then pull the main fuse test again with a volt stick, neon, test lamps. Then do a loop test efli before you do anything else. One last thing as it has happened before a electrician pulled the main fuse when he shouldn’t moved the meter and went to install the main fuse again and electrician had a flash over due to a phase to phase fault out on the main where a old t joint had a phase to phase fault right next to the new service joint that was next to it. After the dno attended to install the new service a phase to phase fault had developed with in the old t joint! Doing your tests before hand would have shown this resulting in the accident never happening in the first place. With test lamps if you went from the live to neutral on the 1ph head you would have got a blue 415 light on test lamps indicating that there is a phase to phase fault back out on the main.
@UKsystems4 ай бұрын
The DNO cannot move the meter if the metering company says no
@kevinpickett7249 Жыл бұрын
I would say The Gloves Thing 🤔 seems to be all u tube sparks have them be that putting a socket on or live work ( perhaps skin is not what it used to be 😄) I only put gloves on if I Work on anything over 230V that can't be isolated ( personal thing as I feel it's hard to feel what you need to feel through your hands or I have a built in torque setting 😂) then again I Dont get free gloves or have to try to film at the same time which always brings an extra element of risk to the job as you can't concentrate 100%
@mitracheLEO Жыл бұрын
Who gave you the materials initially was right: you need an RCD isolator on a TT System;
@Nomad-wv4oe9 ай бұрын
Love seeing this
@joshuaprest1590 Жыл бұрын
Most of the terrace houses i work with are tt work with that more than any other earthing arrangement. 9 times out of ten the house dosent even have an earth ot any bonding crazy
@Electronics-Rocks10 ай бұрын
Why I have never heard of this unless the property is condemned & unsafe to enter which the DNO did exactly what it shows in your video. Ok I had a building not condemned but old extension was gutted where our problem was the incoming & meter was in the extension. It was a pain to get a new meter but they did it in the end. They said a charge applied but the DNO was on my side saying the meter was too old/ unsafe so new meter fitted in the box. DNO did not charge as incoming head had issues(wink wink).
@dannyte83 Жыл бұрын
TT system circuits require 0.2 disconnection time, the circuits should be on RCBOs or use RCD main switch…. You would of had no fault protection 🤷🏻♂️ Good job owning it 👍🏼
@temp06j723-pmeighttq Жыл бұрын
Two(2) RCBO installed, insn't?? Watched the next video on TT Electrode Installation?
@kevinmordecai8930 Жыл бұрын
Normally where I am I usually pay SSE to do this.
@UKsystems4 ай бұрын
Sometimes the meter move has to be done by the meter in company and sometimes they tell you to do it and that’s the only option
@SurreyAlan Жыл бұрын
I thought I'd read that proper qualified electricians were allowed to pull the fuse (though not play withthe meter) now rather than do it illegally which is what they all seemed to do when replacing a consumer unit.
@Михаиллеви Жыл бұрын
It depends on the DNO but I think all now allow a competent scheme electrician to pull the main fuse but you need to get prior authorisation. I did with SSE. Easy process. Just need Competent Scheme ID and they gave me 5 stick on main fuse seals and a sheet to record my five and then take this back when full for a new sheet and seals. No fee
@UKsystems4 ай бұрын
Generally, they require some registration in advance I may make you watch some training videos in a way where they can actually see if you have just to deal with any unsafe situations
@Dooguk2 ай бұрын
If the DNO finds seals are missing the consumer could be fined.
@UKsystems2 ай бұрын
@ however in most cases the people doing the work do not care about this
@Dooguk2 ай бұрын
@@UKsystems Some of the comments on this video prove that. I was a jointer for 30+ years and I've seen/heard some horror stories
@szaki95 Жыл бұрын
Tinning the copper prevents corrosion, that's why they did it.
@AndyK.1 Жыл бұрын
Some good tips
@joesouthgate Жыл бұрын
"meter boy" here to hammer you 😅 Nah, tidier job than the majority of meter fitters manage mate, nice one.
@MrBob5y Жыл бұрын
Yeah don't copy anything I've done but you can buy all the tools I've used in my online shop 😉😉
@jakeok741 Жыл бұрын
WE NEED A WHATS IN MY TOOLBAG 2023!!!!!!!!!!!!!!!!!!!!!!!
@peterwilliams7507 Жыл бұрын
Why is this video on here? Only the local supplier are allowed to do this job.
@UKsystems4 ай бұрын
What part of being explicitly given permission is hard to understand?
@JRCElectrical Жыл бұрын
Bet you felt a g having actual permission to pull the fuse 😂
@wolvolad25 Жыл бұрын
Shame they knocking that down looks a building with great character
@joeypriestman6783 Жыл бұрын
Thought my screen was dirty bottom right 😅🤦🏻♂️
@AndyK.1 Жыл бұрын
Spirit level in temp. Board 😅
@JimWhitaker Жыл бұрын
And that's why he is always going to do a good job.
@ChampionsOfTheTrade Жыл бұрын
I can tell that you're not from my part of the world, the DNO here won't let us touch the main fuse.
@terencelawrence1050 Жыл бұрын
brilliant job from a meter monkey tut tut on the pig tails but good job
@felixodendaal736 Жыл бұрын
Why you wearing gloves? The fingers are cut off so they aren’t protecting anything anyway. I’ve been a electrician for 40 years and I can’t work with gloves. The only time I do wear gloves is if I’m doing HT phasing and it’s required to wear insulating gloves as a safety requirement.
@UKsystems4 ай бұрын
Class at the thing is cut off can be good if grabbing a lot of things with palm of your hand and your upper fingers
@0liver0verson9 Жыл бұрын
Nice job, probably better than a lot of meter changers I work with. I'm surprised the DNO didn't recommend a face visor though. There was no load, fair enough. But you'd think they wouldn't want any come-back if something still went wrong lol. You can get rubber gloves that don't require the outer leather ones btw, making it a bit easier to work.
@andysims4906 Жыл бұрын
Thé DIY guys will be having a go after seeing this video
@chazzlebazzle693 ай бұрын
Temporary building supply
@ashleystirland Жыл бұрын
goodness me meter tails should be flat against back board not them hellish loops you made and as they go into meter should have the anti tamper thimbles you removed with old cables personally i always cleat meter tails over about 30cm so they have strain relief but think thats just what suppliers i work for like to see its semt1 meter the extra bit is its comms hub great video tho buddy and not bad to say you dont fit meters ive seen fitters who do in day in day out do a worse job lol
@UKsystems4 ай бұрын
This depends on the specification of the install, but it’s fine as he was doing it the way it was before the meter and company would have to upgrade it to the latest smart meter for it to be done that way
@moodyga40 Жыл бұрын
don't lick the red part
@psychobread1 Жыл бұрын
It’s just plastic
@geraldelwood9660 Жыл бұрын
A pretty good job. You have obviously done this before or observed others doing it. Only tiny mistake I would say is that you did not plan for the routing of the tails to the meter. If you had positioned the meter a few inches higher you would have had a much neater route for these tails (not looping out into free air) I always found it crazy that there were no torque settings for the terminals in the head nor in the meter. In the meter we had to use as much force as we could on a std screwdriver !!!! Such was the paranoia of loose connection resulting in a fire. Missing Line and neutral identifiers (one each on input to meter, 2 on the outputs) Again crazy I know, especially as you used coloured tails, but thems is the rules 😀 One last thing - I would have wired the isolator so it could not be switched on without cutting the wire. But that's just me.
@ShalomBrother Жыл бұрын
Not a chance anyone in a position high enough to authorise you to move the meter has given you written permission.
@ShalomBrother Жыл бұрын
U don’t understand what I mean. I’m not doubting that someone has given you permission. What I’m saying is, the person who has given you permission, isn’t in a position high enough to authorise something like that. And if the wrong person sees this video, someone’s going to be getting their P45. It will be easy to work out where you are as the meter number is clearly visible. I’ve seen it from both sides, 17 years at the DNO and now from the IDNO side. You can get permission for all sorts you know your not supposed to be doing if you ask the wrong (right) person. You made a better job of it than most jointers would make and took a lot more care over what your doing. DNO’s & IDNO’s have slightly different rules and regs depending on which one it is your working for. I’m authorised for a few different ones, and it is overalls zipped upto the neck, visor and LV gloves for any work at a cutout. Weather it’s new, old, loaded, unloaded, dead live etc
@ShalomBrother Жыл бұрын
@@residualelectrical I don’t have any social media so I won’t be able to, but I’ve got a good idea what I think may have gone on! I’d say someone’s done something they shouldn’t have been doing and neither the dno or the meter operator has wanted to take responsibility for it. I’m not 100%, but I think that type of meter has a little button under the terminal cover and it notifies the owner when the cover has been removed. Out of curiosity, did the permission come from the meter operator?
@Arachnoid_of_the_underverse Жыл бұрын
The other issue that comes to mind is that there are no official seals on the supply now or a record of said installation.
@abdulseaforth6930 Жыл бұрын
TT rod- not disk. Only querying having seen the video with you and Paul. Nice video- good work!
@ianmiller3182 Жыл бұрын
Also supply operator would not necessarily be the same as the meter operator, so possibly needs two authorisation.
@Chris-Thistleton Жыл бұрын
Surly the glasses will just melt onto your face
@iancoles13499 ай бұрын
U will damage the edges on u brand new knipex shears doin that Deff a code v
@abdulseaforth6930 Жыл бұрын
Flexi tails, I see.
@paulcockburn9545 Жыл бұрын
oven gloves for 230v lol
@UKsystems4 ай бұрын
Well you need to realise this the safety cautions have to have because there’s not very many ways to cut the power off. Also there could be a very bad for all distribution network connecting the high voltage side to low voltage side.
@Dooguk2 ай бұрын
Leave this subject to the adults.
@toni1554 Жыл бұрын
good electrician use stanly knife not cutters stripping meter tails!!!
@UKsystems4 ай бұрын
Not really much of a difference if done properly both can be as bad
@Dooguk2 ай бұрын
DNO's don't issue Stanley knives to jointers or meter fixers. They aren't insulated.
@krissybufton Жыл бұрын
Made me cry when you used your cutters to turn the Allen key 😢😂
@kevinpickett7249 Жыл бұрын
We asked supplier to upgrade cut out as it was a mess they gave us the bits said get on with it 😂