I hope this information is useful. I always try to "look before I leap" when I'm doing these DIY projects. Something seemingly as simple as installing and filling conduit could have a dangerous outcome if done incorrectly. *Please leave a 👍 and share the video!* 👉 Visit our website ► DIYApprentice.com 👉 Click to Subscribe! ► bit.ly/2pEBg3m 👍▬▬Follow Us on Social Media▬▬👍 ✔️ Facebook ► bit.ly/2pAY8S3 ✔️ Twitter ► bit.ly/2G7mRDz ✔️ Instagram ► bit.ly/2ILEKII 🔧▬▬Tools and Materials▬▬🔧 ✔️ DIY Apprentice Recommended Tools and Materials ► bit.ly/2T5psFw ✔️ NEC State Adoption Map ► www.iaei.org/page/nec-code-adoption 📷▬▬Video Equipment▬▬📷 ✔️ Camera used ► amzn.to/2GcpkOb ✔️ Lens used ► amzn.to/2Deu16S ✔️ Tripod ► amzn.to/2GbaM1c ✔️ RAM Suction Mount ► amzn.to/2Wz9PXh ✔️ Cyberlink PowerDirector ► bit.ly/2jTwGxT ✔️ Adobe Photoshop ► bit.ly/2V7nyUX ✔️ Camera Slider ► amzn.to/2WtD7GW ✔️ Deity V-Mic D3 Super-Cardioid Directional Shotgun Microphone ► amzn.to/2LI1lf7 **This video was recorded in 4K resolution, so modify your settings accordingly if desired for better image quality** Disclosure: This video contains affiliate links, meaning, at no additional cost to you, I will receive a commission if you click through and make a purchase.
@fistpunder
@fistpunder 2 жыл бұрын
Thanks for the in depth detail. This goes much more into the design specifications and codes than I expected. Great reference. And you back it with source of materials presented. Top notch video for technicians and those ready to do a little math to get it properly done.
@DIYApprentice
@DIYApprentice 2 жыл бұрын
Glad you found the video useful. Thanks for watching!
@ericpelayo9872
@ericpelayo9872 2 жыл бұрын
Nice explanation, simple and detailed, thank you 👍🏼
@DIYApprentice
@DIYApprentice 2 жыл бұрын
Thanks! Appreciate the feedback.
@jeremiahrex
@jeremiahrex 3 жыл бұрын
I appreciate you putting the code screenshots up. A video like this is a great primer to get me up to speed but I always like to dig in further. Plus NEC 2020 wouldn't tell me about the helpful online tools. Thanks for the video!
@DIYApprentice
@DIYApprentice 3 жыл бұрын
Glad this video was helpful. Thanks for watching!
@lisag3495
@lisag3495 4 ай бұрын
Super helpful. Thank you
@vibesmom
@vibesmom 2 жыл бұрын
Super informative thank you!
@DIYApprentice
@DIYApprentice 2 жыл бұрын
Thanks for checking out the video!
@vgmijpn8ball
@vgmijpn8ball Жыл бұрын
I just learned, even though you can fit that many wires, the installation won't meet code unless you derate your wires per NEC 310.15 c 1. 12 gauge won't support 20 amps, and 14 gauge won't support 15 amps as is normally thought
@DIYApprentice
@DIYApprentice Жыл бұрын
Yes, I briefly mentioned "de-rating" at 8:04 as a factor to consider.
@TheJimsokoloff
@TheJimsokoloff 4 ай бұрын
If you're using THHN (a 90°C conductor), you derate from the 90°C rating in T310-16. In that table, 12 AWG THHN "starts" as a 30 A wire in the 90°C column, so even if there are 7-9 conductors (70%), that yields 21Amps for multiple-conductor derating purposes, and 14 AWG THHN would be 25 * 0.7 or 17.5 Amps.
@enufots4621
@enufots4621 4 ай бұрын
Nope, don't get it. You need to explain what the percentage of fill limit is? A 2 wire has a 31% fill limit...what does that mean?
@DIYApprentice
@DIYApprentice 4 ай бұрын
@2:07: Fill % is based on the cross-sectional area. Two conductors or cables can fill no more than 31% of the cross-sectional area. Each wire or cable has a specific size that's used in the fill% calculation. Hope this helps. You may want to re-watch the video.
@hippo-potamus
@hippo-potamus 2 жыл бұрын
I didnt understand a damm thing you said mate. Talk about over complication subdividing everything to individual wire with jargon terminology and you total inability to just break the information down into laymans diy terms so we can understand. Most of us here just want ot know how many sets of 14/2, 12/2, or 10/2 we can fit inside a half inch emt conduit. The search continues.
@DIYApprentice
@DIYApprentice 2 жыл бұрын
Sorry that what I explained didn't come across clearly; I haven't received similar feedback from other viewers. It sounds like your primary complaint about the video was that I didn't go into depth about fitting residential cable in conduit, which is actually referenced around the 3:30 mark. There are all sorts of possible combinations, which is why I didn't get too specific and just mentioned cable diameter being a factor. Most installations I've come across run individual THHN or THWN wires in conduit. Here are the major diameters I was able to find for residential cable that would have to be included in the calculations: 14/2 (0.36"), 12/2 (0.4"), and 10/2 (0.49").
@hippo-potamus
@hippo-potamus 2 жыл бұрын
@@DIYApprentice Are they running solid or stranded THHN? Another thing that's not really explained well in the NEC is if "conduit" specifically means the pipe from box to box, I'm just trying to run a couple outlets so I've read others say that a simple drop run isnt considered "conduit" but rather just a protective sleeve in which case romex is acceptable and the heat concern isnt really applicable. But I guess the code and your reading assumes the use of THHN or the like single cables. Another concern is supposedly solid cable is able to support higher ampicity so Im not sure if I do run stranded THHN I should use 12g THHN instead of the 14g I wanted for simple 15amp outlets. Appreciate your feedback.
@DIYApprentice
@DIYApprentice 2 жыл бұрын
​@@hippo-potamus I don't want to speak out of turn, since I'm not an expert, but it seems like stranded vs. solid comes down to personal preference when it comes to residential wiring. Stranded is easier to pull through conduit for longer runs that include bends, while solid is easier to push through conduit; I've only ever used solid wire. My understanding is that solid is able carry more current than stranded. Personally, I would go with solid, but I don't think the difference between the two for simple residential wiring is significant enough to warrant 12-gauge wire if stranded is chosen for a 15-amp circuit. Distance of the cable run can be a factor, with solid performing better over longer distances. Chapter 9 of the NEC, which I referenced in the video, lists several conduit types: EMT, RMC, PVC, Liquidtite, FMC, IMC, etc. It's basically the pipe that protects the wire or cable from damage.
The Lost World: Living Room Edition
0:46
Daniel LaBelle
Рет қаралды 27 МЛН
Thank you mommy 😊💝 #shorts
0:24
5-Minute Crafts HOUSE
Рет қаралды 33 МЛН
Caleb Pressley Shows TSA How It’s Done
0:28
Barstool Sports
Рет қаралды 60 МЛН
Conduit Fill / Different Insulation types
9:41
Craig Michaud- Electrical Instructor
Рет қаралды 61 М.
How to Calculate Conduit Fill
14:24
AccessToPower
Рет қаралды 81 М.
Electrical Troubleshoot Tone And Trace Like A Pro THIS IS HOW
11:12
Tools And Tactics
Рет қаралды 30 М.
Why Romex Doesn't Belong in Conduit: Quality and Longevity
6:20
abrelectric
Рет қаралды 79 М.
Neutral Imbalance in Multiwire Branch Circuits (Two Hots, One Neutral)
16:41
How to bend and install electrical conduit
20:14
Bob Clarizio
Рет қаралды 1,4 МЛН