How to Install an EV Charger - Legrand Hardwired Level 2 EV Charger

  Рет қаралды 99,259

Mad Electrician

Mad Electrician

Күн бұрын

Пікірлер
@jamesparthun3529
@jamesparthun3529 9 ай бұрын
Great Video. One thing to check You need to check breaker 1a,1b. The original wires were on breaker 1&3 (A&B). When you put in the tandem breaker you landed them both on A Phase 1a,1b. If it’s sharing the neutral on a network it needs to be on different phases so you don’t overload the neutral.
@enriquehamilton5693
@enriquehamilton5693 7 ай бұрын
A new apprentice here how can you check the neutral ? Thanks in advance
@bryonraisch4673
@bryonraisch4673 4 ай бұрын
@@enriquehamilton5693 you can see coming out of the romex that it only has one neutral. Therfore cant be on the same phase!
@taylormills08
@taylormills08 10 ай бұрын
Great video! Your procedure of fishing the conduit up the wall is GOLD! No drywall work! Cord under the garage door is questionable if you were in a cold climate. Thanks for sharing your expertise!
@lunar5577
@lunar5577 10 күн бұрын
No no no!!!! Your fishing of wires was totally backwards! You should have started the other way! Handlindling the wires coming into the box, your hands and fish and wires were extremely close to themain live wires!!
@GlenMacNeil
@GlenMacNeil 11 ай бұрын
Do you torque your connections at the panel?
@dempower
@dempower Жыл бұрын
This was an awesome video, I really enjoy this type of content.
@MadElectrician
@MadElectrician Жыл бұрын
Thanks! That’s great to hear! I haven’t posted much “How to install” type content yet but this was a fun one! I’m definitely open to posting more videos like this ⚡️
@LarpCapitall
@LarpCapitall Жыл бұрын
post more service calls/home upgrade videos
@hjlee303
@hjlee303 Жыл бұрын
It is such a great and much detailed vid on how to. Thanks a lot. I think I am ready to install mine fir the new BMW i4. Happy holidays!
@viswan4029
@viswan4029 2 ай бұрын
Wow.. fantastic video, smooth, crystal clear audio, very detailed step by step guide.
@RunOs3
@RunOs3 2 ай бұрын
I’m so motivated to become an electrician now.
@Jomanscool2
@Jomanscool2 Жыл бұрын
Is the top breaker not feeding a MWBC? That'd be two 15 amp circuits, same phase, with one neutral, potentially overloading the neutral. Could be remedied by putting it on the other tandem, though you should also have a handle-tie I think?
@jakerasp
@jakerasp 9 ай бұрын
How do you know they share a neutral?
@gargolart
@gargolart 7 ай бұрын
Is the handle tie necessary even if the same circuit is connected to different fase?
@Jomanscool2
@Jomanscool2 6 ай бұрын
@@gargolart Handle ties are so the entire wire is dead. If you are running 12/3, which we can see that top breaker goes back to Romex with one white, a black, and a red, so it’s 12/3 or 14:3, and you have a MWBC, so two separate hot phases, and a common neutral, if you shut off one hot phase, current is still running on the neutral, and on the other hot, so it’s not safe to work on receptacles or switches on the “partially shut off phase”. We can see both phases were in use previously via a MWBC on a single Romex wire, and it was unsafely merged onto a single phase with a tandem breaker providing 15A on each hot, and a potential 30A (or 20/40A respectively for 12AWG), which can overload and overheat the neutral conductor. My understanding when moving circuits to tandems is you need to look at panel capacity, service capacity, and MWBC, and this video failed to look at the last.
@lunar5577
@lunar5577 10 күн бұрын
Why didn't you explain where the green wire is connected to? (Ground or neutral)😮
@standtall7646
@standtall7646 11 ай бұрын
Great video, Steven! Clear, great speed of explanation and clear on materials/tools used/needed. I'll save this video as reference. I'm a general/Handyman and I have wired in e few EV Charger receipts. Ive wired in many dryers(Yes electrical :). Thanks, for this video. Where did you purchase the Adjustable Pliers and the Strippers with Flat end?
@AK-qo6tx
@AK-qo6tx Жыл бұрын
How are you closing the garage door with the charger mounted on the outside of the garage?
@miguelrodfher
@miguelrodfher 11 ай бұрын
Exactly what I was going to ask! Seems that is possible, but no one makes a video about it
@allencharbonnet8585
@allencharbonnet8585 9 ай бұрын
That’s exactly what I was thinking.
@Djsami6797
@Djsami6797 9 ай бұрын
He lives in a very safe area
@S777H
@S777H 9 ай бұрын
No response to this question?
@Djsami6797
@Djsami6797 9 ай бұрын
Guys, if you actually took the time to watch the video you would have an answer, he literally says, you can close the garage door no problem. 19 min 50 seconds. Thank you
@alexsanoff585
@alexsanoff585 Жыл бұрын
Awesome video! Very clear and easy to follow, thanks for explaining the entire process. I would love to apprentice under someone like you once I get into the apprenticeship! Keep it up and thanks for posting this quality content ✌️
@borismcgiver7764
@borismcgiver7764 8 ай бұрын
Great Detailed, and nice clean work and very concise explanations . Much appreciated this. Thanks.
@b3arwithm3
@b3arwithm3 4 ай бұрын
Great tutorial. Very clear and detailed. I didn't get what the role of the junction box is. Can't we run a wire straight from the panel to the charger?
@dubmob151
@dubmob151 Ай бұрын
@@b3arwithm3 The wires provided by the EVSE were too short to reach so they had to be extended, and the connections need to be in an accessible junction box-
@b3arwithm3
@b3arwithm3 Ай бұрын
@dubmob151 in that case, it would simpler and safer just to replace with longer wires and avoid the connection.
@dubmob151
@dubmob151 Ай бұрын
@@b3arwithm3 might be, if the manufacturer designed it to be swapped for longer wires.
@b3arwithm3
@b3arwithm3 Ай бұрын
Inside the charger, the wires are inserted in the circuit board. They aren't soldered to it. Taking them out is a matter of turning a screw.
@bobbystefano
@bobbystefano 3 күн бұрын
Sorry if this is a dumb question great video. Why don’t you just go all the way from the panel right up to the charger? Why do you have a splice in a junction box before the charger? Thanks for the help!
@MccormickJr
@MccormickJr 8 ай бұрын
For the flexible metal conduit in the wall to the panel, don't you have to properly ground/bond it to the panel? Such as a grounding bushing or bonding locknut?
@cal1473
@cal1473 2 ай бұрын
Wire need to be #4 or larger to require a grounding bushing
@robbe8858
@robbe8858 Жыл бұрын
Nice video! Very detailed and thorough step by step .Thanks .
@PeaceChanel
@PeaceChanel 10 ай бұрын
Thank You for All that you are doing for our Planet Earth.... Peace.. Shalom.. Salam.. Namaste 🙏🏻 😊 🌈 ✌ ☮ ❤
@Dianfarida-g9n
@Dianfarida-g9n 10 ай бұрын
What size of wires did you hardwire ,? What brand did you choose? What brand is the 60 amp breaker?
@Fetecheney
@Fetecheney 8 ай бұрын
Late reply, but it should be #6 AWG wire. You can buy it as sheathed Romex where all the four wires are in a rubber sheathing, or you can buy the stranded wires individually but you have to make sure that you run them in conduit so they're protected. It's a lot safer to put them in metal conduit. Make sure you keep doing your research but hopefully this gives you a starting point. If you did need to know what size they are. Also, if anyone sees this and knows otherwise, please chip in
@TrendyStone
@TrendyStone 5 ай бұрын
Very well done! I had to install two Tesla Wall connectors in my garage and the process is nearly identical. Thanks for the helpful video.
@polepole9066
@polepole9066 9 ай бұрын
Thanks so much for this. It will help me install ours when we pull the trigger on an EV. Question: I will need about 25 ft of cable length from the charger to the car because I can’t park close to the garage (slope/winter). Do I lose efficiency by having a longer charger cable ? Or should I run underground wire closer to the car parking location. And mount the charger outside ? Cheers mate 🥂
@loucinci3922
@loucinci3922 8 ай бұрын
If that panel wasn’t bonded, where would you land the ground wire? Assume on ground bar. Would you then have to run a common too?
@surferdude642
@surferdude642 5 ай бұрын
If this was a sub panel, then yes. The hot wires would be connected to the double pole breaker the same way and the breaker would be in the sub panel.
@ChelsMoClark
@ChelsMoClark Жыл бұрын
Please please please upload more, LOVE your videos 😊
@MadElectrician
@MadElectrician Жыл бұрын
Thanks, Chelsea!! I definitely intend to! I’ve been pretty busy working on a lot of behind the scenes stuff for Mad Electrician lately but am now getting back into the rhythm of creating more content again. Thanks for the encouragement and thanks for watching! ⚡️🤘🏼⚡️
@ricodinero4926
@ricodinero4926 10 ай бұрын
Dude you're the Man! great vid.
@MadElectrician
@MadElectrician 10 ай бұрын
Thanks!! Glad you enjoyed the video! ⚡️🤘🏼⚡️
@GEORGEMONTEVERDE
@GEORGEMONTEVERDE 4 ай бұрын
Thank you for your very informative video. I gather you did this connection to charge your EV, OUTSIDE the garage. My newbie friend has a standard wall plug the electrician ran from the Dryer Circuit from inside the house when they build the new garage. I personally feel this upgrade was done on the cheap and charged top dollar. I warned my friend that the wires were getting too hot and to remove an extension cord and go right into the wall plug.
@tylerc4700
@tylerc4700 Жыл бұрын
i just joined the field 4 weeks ago and i want to find a great book for exam prep and training. im finding books on amazon but the reviews are all mixed and i struggle to find a book thats has good information. are there any training books that you recommend? i am in the residential field in the seattle area. thank you, your videos have taught me so much!
@carlosberrioselectrician777
@carlosberrioselectrician777 Жыл бұрын
💯Safe and clean work🙏 👋Greetings from Orange City Florida 🐊 😎✌️
@MadElectrician
@MadElectrician Жыл бұрын
Thanks! I appreciate you taking the time to watch! ⚡️🤘🏼⚡️
@erictorbet8104
@erictorbet8104 7 ай бұрын
Thank you, very clear. If it were a new home and dry wall wasn't there yet, I presume you would not use conduit and just run the wires inside the wall?
@jerrypruden887
@jerrypruden887 Жыл бұрын
Good content but you were measuring voltage and saying amps?
@MadElectrician
@MadElectrician Жыл бұрын
Thanks! Which part are you referring to? When I was measuring voltage I was mentioning 240v between phases.
@ldiamond3290
@ldiamond3290 3 ай бұрын
​@@MadElectrician7:28
@ldiamond3290
@ldiamond3290 3 ай бұрын
Btw passing the cable under the door is against code in most places.
@dubmob151
@dubmob151 Ай бұрын
​@@ldiamond3290code or not, it doesn't seem that good to rely on the weatherstripping of the door to accommodate the cable and try to maintain a seal. Hanging it inside would be ideal, or putting the whole charger installation itself behind the wall outside, if it's exclusively used for outside charging.
@surferdude642
@surferdude642 5 ай бұрын
I would prefer to have the holster and coiled cable mounted inside the garage. The way it's currently mounted it will interfere with the garage door when the charger is not in use, plus it's subject to weather and tampering. You could have mounted it on the front to eliminate garage door interference, but the weather and possible tampering issues would still exist, and it could be a bit unsightly. Mounting it inside means that you have to open the garage door to use it, but it's a better option imo since opening it is entering a code and pushing a button. The only other nitpick is that the conduit body is not really fastened where it enters the wall. A strap near that end could resolve that issue. Overall, it still looks pretty well done.
@bockalipsfinisky
@bockalipsfinisky 2 ай бұрын
What size is the liquid tight conduit and connector? Thanks.
@rtsolution11
@rtsolution11 8 ай бұрын
Curious if you have changed the location of the charging cord dock? All but that, and what James mentioned below I liked.
@apwelsh
@apwelsh 11 ай бұрын
So, red and black are L1 and L2. Was green neutral or ground? If ground, why didn’t you ground the j-box?
@MadElectrician
@MadElectrician 11 ай бұрын
Black - L1 Red - L2 White - Neutral Green - Ground I did bond the ground to the j-box 👍🏼
@apwelsh
@apwelsh 11 ай бұрын
Sorry. I thought I only saw 3 wires in the video, and must have missed the grounding.
@apwelsh
@apwelsh 11 ай бұрын
Definitely only seeing 3 wires. So that charger doesn’t need neutral.
@shawnwinget2337
@shawnwinget2337 4 ай бұрын
I am considering a Honda Prologue. My panel is at the front of my garage about where you put your charger so it would be right next to the panel. Can the wires from the charger be wired directly to the breaker in the panel? My panel is flush like yours.
@michaelsipah
@michaelsipah Ай бұрын
What kind of conduit is that flex conduit? I can't seem to find that exact kind at Home Depot.
@rayzinz5938
@rayzinz5938 10 ай бұрын
How would this install change if you were to mount the EVSE (charger) on the outside of the wall? I assume you'd probably want to run the liquid tight conduit through the wall but you'd also want to do something to prevent water getting into the wall. Thoughts? Also, do you have to change the ampacity or pick a different temp rating for that THHN while running in the liquid tight conduit?
@HanyunGong
@HanyunGong 29 күн бұрын
Is it possible to inform why you need to cut the wire and reconnect them with wire nuts inside a junction box ? why not just connect 3 long conduited-wires directly from the charger to the panel ?
@hrguille
@hrguille 5 ай бұрын
Than pannel cover needs some paint. Thanks for the video. Great hack on the tandem 15amps
@yeminacci
@yeminacci 8 ай бұрын
Great work. Very clean. But the charger rack for the cable? How do you close the garage 😮
@Matthew-tb7cc
@Matthew-tb7cc Жыл бұрын
#8 ground? Could have gotten away with a #10 just an fyi. Great video tho keep em coming.
@Calebjones87
@Calebjones87 Жыл бұрын
This was a great video. You lucky your wife don’t mind the pipe. My didn’t want to see a pipe so I had to open up the wall and get my carpenter friend to put it back up
@MadElectrician
@MadElectrician Жыл бұрын
Thanks! I enjoyed the installing part but it was tricky setting up my camera and light for every shot 😂 I actually really considered doing that but I wanted to do “simpler” install for the video. That’s definitely the cleaner route to go though ⚡️🤘🏼⚡️
@DiegoVargas3773
@DiegoVargas3773 Жыл бұрын
Hey Steven I just applied for limited residential 2.5 and got a ranking of 382 is that good?
@Dianfarida-g9n
@Dianfarida-g9n 10 ай бұрын
Hello could you please let me know if we can use #6 white in place of #6 black? And will it be an overkill if we use all #6 thhn red, black and green wires ?
@taylormills08
@taylormills08 10 ай бұрын
By code you are not to re-phase conductors unless they are 4awg or larger. 6awg and smaller should be color phased from manufacturer. You must buy colored conductors according to NEC.
@jmahtab
@jmahtab Жыл бұрын
Just curious why you chose to use fmc from the box to the lb instead of seal tight like you used from charger to the 4 11/16 box? Nice clean install.
@cal1473
@cal1473 2 ай бұрын
More flexible than a seal tight
@ShirleyMa-r9w
@ShirleyMa-r9w 18 күн бұрын
It's very helpful!Thank you!
@brothermanvlogs3767
@brothermanvlogs3767 Жыл бұрын
Can you please do a video on how to prepare for and take the state exam 🙏🏽
@williamgrissom9022
@williamgrissom9022 6 ай бұрын
An advantage of hard-wiring vs using a charger w/ plug is that you need only run 3 wires - 2 hots and gnd, with no neutral since chargers don't need it. A 4-wire plug has a neutral terminal, though perhaps you could not wire it if only an EV charger would be using that plug, that would seem strange. Good for me since I have a 50 A 240 VAC wire to a former electric oven, so can re-purpose that long cable for future EV charging by terminating it in a box and continuing conduit to the nearby garage to a box for future hard-wiring. That cable had no neutral wire, which surprised me until I found typical, at least in the past, for large appliances like stoves and clothes dryers. A 2nd reason for not using a plugged charger is that the latest NEC code requires an outlet to have GFCI protection. A 3rd reason is that plugs can give resistance to melt and cause a fire. Re the video, I'm surprised your local code allows using a wire-nut to connect ground wires. I thought one had to twist the wires and use a copper crimp, though I've seen many youtubes wiring overhead lights where they use a Wago lever connector on the ground wires (to code?).
@johnpayton4633
@johnpayton4633 6 ай бұрын
Great detail explained. Thank you brother
@MadElectrician
@MadElectrician 6 ай бұрын
Glad you found this useful! Thanks for watching!
@freshgino
@freshgino 8 ай бұрын
Great job, keep up the good work
@cal1473
@cal1473 2 ай бұрын
I thought when using the 48amp output on a 60amp breaker, you use #4 instead of #6 due to the 80% rule?
@rgET758
@rgET758 Ай бұрын
The conductors must also be sized at 125% since it’s a continuous load (nec 210.19(A)(1) so the wire needs to be rated for 60 amps as well as the ocpd. #6 is rated for up to 65A based on the 75 degree column (most likely what his breakers are rated for). A breaker should never be loaded more than 80% of its maximum rating which 48amps is 80% of 60.
@jamesking6174
@jamesking6174 8 ай бұрын
Is it a bi directional charger.
@antoniojones1356
@antoniojones1356 Жыл бұрын
Craftsmanship superb makes me excited as an apprentice
@Djsami6797
@Djsami6797 9 ай бұрын
👏👏👏 only issue i would have i imagine is my garage door would just open on it's own cuz there's resistance from the hose
@k20909
@k20909 10 ай бұрын
A gfci breaker is not required?
@MadElectrician
@MadElectrician 10 ай бұрын
Nope! I actually specifically asked my local inspector about that before doing this install and he said no.
@TrendyStone
@TrendyStone 5 ай бұрын
I know the Tesla Wall Connector specifically says NOT to use a GFCI. The reason is that it is already built into the car and an additional GFCI may cause problems.
@erikkarling2176
@erikkarling2176 Жыл бұрын
Nice, clean work.
@jhseam
@jhseam 4 ай бұрын
Great video. It's easy to setup. If i have the toolkit i hope i can also do that 😅
@dougsprelude1
@dougsprelude1 Жыл бұрын
Good job sparkie
@MadElectrician
@MadElectrician Жыл бұрын
Thanks! ⚡️🤘🏼⚡️
@Antiorganizer
@Antiorganizer Жыл бұрын
rrrrrrrrrrrrrrrrrrrrrrrr
@Vxvx22
@Vxvx22 2 ай бұрын
Great tutorial video, thanks
@Silent_spk
@Silent_spk 6 күн бұрын
What state are you in????
@MrAcruz2
@MrAcruz2 8 ай бұрын
great video, hows the garage door gonna close if u have it in the way like that ?
@Fetecheney
@Fetecheney 8 ай бұрын
Cut a 1½" slot in the garage door from about 4' to the ground. Piece of cake.
@zhongmingwu
@zhongmingwu 11 ай бұрын
i have 200amp panel with all 30 breakers used up. One company give me an estimate with your solution involving tandem breaker with about $1400 quote. Two others insist to install a subpanel next to it with $2700 to $3500. Now that i have seen your work i feel good that first solution is not really wrong. anyone know why two companies insist on new subpanel; one of them didn't even visit though he did work on my house 3 yrs ago. i am in dallas and google does not say that i need a permit but one company says that i need it very good video ❤
@Dianfarida-g9n
@Dianfarida-g9n 10 ай бұрын
Legendary video!!!
@MadElectrician
@MadElectrician 10 ай бұрын
I’m glad you think so! Thanks for watching! ⚡️
@Dianfarida-g9n
@Dianfarida-g9n 10 ай бұрын
@@MadElectrician one question I have though is how to call an inspector? Do they charge money ?
@dubmob151
@dubmob151 Ай бұрын
​@@Dianfarida-g9nI'd expect so, since they work for money.
@ErnestoMunoz2075
@ErnestoMunoz2075 19 күн бұрын
Awesome !!! 😃😃😃
@FishFind3000
@FishFind3000 Жыл бұрын
6:30 just gotta be carful with those tandums. The panel needs to be rated for their use and location.
@MadElectrician
@MadElectrician Жыл бұрын
100% ⚡️
@briandillard8125
@briandillard8125 11 ай бұрын
Does the top tandem have both conductors from multi wire branch circuit terminated to it?
@Mike0in0Texas
@Mike0in0Texas 11 күн бұрын
If the wire could run under door with no problem why didn't you install the holster inside garage and then when charging just plug in and holster protected
@carlosedgarcruzcorrea1615
@carlosedgarcruzcorrea1615 2 ай бұрын
Great video thank you
@kennethreddy5749
@kennethreddy5749 5 ай бұрын
Straps are installed wrong. Screw holds the pipe up not the strap . Very important in commercial. Other than that I would’ve just used black taps/clear taps . Big blues no if it was my own house
@dubmob151
@dubmob151 Ай бұрын
Are they normally only installed with one screw?
@loucinci3922
@loucinci3922 8 ай бұрын
Great video. Thanks for sharing
@lohmiperez5258
@lohmiperez5258 4 ай бұрын
Very detail instructions. Good Job!
@don1estelle
@don1estelle Жыл бұрын
They should make a gard plate to protect you from the live wires.
@matta5160
@matta5160 Жыл бұрын
Not sure why they don’t UK fuse boxes (the more modern ones) usually have a plastic cover for the incoming wires.
@don1estelle
@don1estelle Жыл бұрын
It would that seem nearly US power pannels seem to have bare wires in them, electricians nead to carry a temporary plastic barrier plate to make it safer when working inside one.
@ken62310
@ken62310 3 ай бұрын
doesn't that block your garage door?
@Antiorganizer
@Antiorganizer 3 күн бұрын
Why bother with the EMT bit when you could have simply run the Liquid-tight from EVSE to the B body all in one go?
@MadElectrician
@MadElectrician 2 күн бұрын
It really just came down to the location. That and I also wanted to demonstrate an install that was a little more tricky in case other people were in a similar situation. I thought it might be a little more helpful ⚡️
@cadelawlor3457
@cadelawlor3457 Жыл бұрын
So how much do you make as an electrician
@chad10006
@chad10006 Жыл бұрын
They typically charge $150-$200 per hour.
@Hatim.13
@Hatim.13 Жыл бұрын
He is part of Local union 46, so as an employee he makes 70$/H (140k) on the check + benefits (different retirement plans, medical, dental, vision...) Total package is around 97$/H.
@mathewshoyt1763
@mathewshoyt1763 3 ай бұрын
i would have left the cord inside the garage to prevent any damage to the cord and garage door as well as having anyone drive up your drive way for a free charge when no one is home. hope you put a disconnect later after this video. great video though
@jeffjackson6358
@jeffjackson6358 3 ай бұрын
Next time show/tell your viewers they should torque their lug points to the specified torque amount shown on the breaker. Also, why not just run continuous wire from the breaker to the charger and eliminate the wire nuts? Improper wire nut tightening will result in a big problem. You are just adding a fail point for no reason. Unless the charger did not allow you to open it and attach longer wires. Otherwise loved the video!
@alexxp503
@alexxp503 11 ай бұрын
watch out with that multibranch circuit bro!!!!! You should kw that already (overload neutral)...... booooom
@deas1anguy
@deas1anguy 11 ай бұрын
Couldn’t you just run emt straight to the ev charger?
@MadElectrician
@MadElectrician 11 ай бұрын
I could have but it wouldn’t have been where I wanted the charger mounted and I also wanted my EMT to be ran down low so that it wasn’t taking up too much wall space. This was more work but I’m happier with the placement of everything.
@beltrams
@beltrams 5 ай бұрын
Dirty, stained panel covers drive me crazy. You need some grey spray paint 🙂
@tomballman5243
@tomballman5243 6 ай бұрын
GREAT VIDEO!! My only question is, how can you close your garage door?? LMAO!!
@leedaq7767
@leedaq7767 8 ай бұрын
how is the owner closing the garage door?
@MadElectrician
@MadElectrician 8 ай бұрын
This is my house. I didn’t explain it in this video but there was an existing gap in the corner of my garage door that the cable fits under without being squished. Not a great solution but it works fine in my situation.
@dubmob151
@dubmob151 Ай бұрын
​@@MadElectrician I thought you had a weatherstripping seal on the bottom of the garage door, didn't realize you had a gap; that's a unique situation.
@goosfraba911
@goosfraba911 6 ай бұрын
Why didn't you pull all the way through instead of splicing?
@MadElectrician
@MadElectrician 6 ай бұрын
I would have much rather done that but the internal terminations weren’t designed to be undone. I didn’t want to mess with the listing of the car charger either. Also, this was a video that I partnered with Legrand to make and I wanted to show how someone would do an installation the way that they designed it to be done. The best situation would be going right into the side or bottom of a surface mounted panel without needing to use any extra wire. That just didn’t work for my situation unfortunately.
@dubmob151
@dubmob151 Ай бұрын
​@@MadElectricianwas the 18' a bit too short to mount the charger next to the panel and still be able to reach your car? Usually chargers seem to have longer 25’ cables, which would seem to have been able to make up the difference in the positioning. It'd be nice if manufacturers offered options on the cable length to let you fit it for your particular needs. Some might even find a short cable to work better and be more tidy, if they happen to have the charge port right next to the EVSE unit.
@don1estelle
@don1estelle Жыл бұрын
Grate Job exept those old Wire Nuts shurly there is a better Solution!
@MadElectrician
@MadElectrician Жыл бұрын
Thanks! The wire nuts are fine and legal, but there is a better, probably more mechanically sound solution. I could have used small Polaris lugs. They take up a little bit more space but will never come undone. They are just more expensive and I didn’t have them on hand when making the video.
@sedona1234566
@sedona1234566 Жыл бұрын
Definitely, they are compliant but with that load and length of time it is pulling a full load I would recomeend a type of crimp or mechanical connector.
@darwinfussle5031
@darwinfussle5031 10 ай бұрын
Always use a regular hammer 🔨 to punch a hole. Not a hole saw or a screw driver. It can be easily patched once your finish....i suggest this method it takes a neat hole no dusk no debris.
@dubmob151
@dubmob151 Ай бұрын
You mean the hole in the sheetrock? How neat a hole would that be?
@darwinfussle5031
@darwinfussle5031 Ай бұрын
@dubmob151 no I use a rock hammer 🔨 or take your time and do a quick punch with a regular hammer.....saves time.... Trace with hot patch when ready to mud...
@dubmob151
@dubmob151 Ай бұрын
@@darwinfussle5031 is a rock hammer a pointy thing and not like a regular hammer?
@darwinfussle5031
@darwinfussle5031 Ай бұрын
@dubmob151 yes
@barriepkr
@barriepkr Жыл бұрын
Current equals voltage / resistance. The same amount of current will pass through you touching a main lug as it would a regular outlet. Why are people so scared of panels
@MadElectrician
@MadElectrician Жыл бұрын
Good ol’ ohm’s law baby. A couple of reasons, though definitely not all: It’s very easy to make a mistake and touch a main lug working in an energized panel, especially for someone who isn’t very experienced. It would be easier to get hung up or be in an arc flash/ blast situation vs just by working on a regular outlet. There’s the potential of a phase to phase to short, resulting in a very high fault current. Etc. Thanks for watching!
@allencrider
@allencrider 2 ай бұрын
Nice, though I think it is sad you can't park your car inside the garage.
@kikodelacruz96
@kikodelacruz96 Жыл бұрын
Will a neck tattoo affect my interview for the apprenticeship?
@mikenormandy9250
@mikenormandy9250 Жыл бұрын
It should not BUT with that said, you cannot rule out people’s own opinions and judgments- so maybe hold off until you get in! Good luck!
@chief5981
@chief5981 Жыл бұрын
Yeah. If you don’t have at least 1 neck tat and 1 felony they probably won’t take you serious. You’re applying to a trade not a bank.
@surferdude642
@surferdude642 5 ай бұрын
60 amp breaker? Should be 50 amp with 6 gauge wire.
@MadElectrician
@MadElectrician 5 ай бұрын
@@surferdude642 It’s considered a continuous load (operating for minimum of 3 hours at max current). 48A x 1.25 (multiplier for continuous loads) = 60A.
@surferdude642
@surferdude642 5 ай бұрын
@@MadElectrician Shouldn't the wire be 4 gauge then? Personally, I'd be more comfortable with a 50 amp breaker and from what I understand, no EV is going to draw close to that much current anyway.
@surferdude642
@surferdude642 5 ай бұрын
​@@MadElectricianI understand the 1.25 multiplier and how you arrived at the 60 amp breaker. I did some research and your charger I believe is rated for 48 amps and THWN wire is apparently rated for 65 amps, so you are correct. My concern is using wire nuts for this much current allowance. I would prefer using terminal blocks rated for 60 amps for the hot wires.
@rj-zn3cw
@rj-zn3cw 6 ай бұрын
Both, you and Legrand seem pretty "generous" if you know what I mean... wink wink
@cynthiaayers7696
@cynthiaayers7696 6 ай бұрын
At home charging systems should come with the price of the vehicle.
@zebadiahsprenkle8395
@zebadiahsprenkle8395 5 ай бұрын
Thats a whole lotta vamps
@jamieeisenhower1560
@jamieeisenhower1560 7 ай бұрын
😂 my question is how you going to shut the garage door
@MadElectrician
@MadElectrician 7 ай бұрын
It doesn’t affect the garage door at all. There’s unfortunatly a slight gap already in that corner so this fits right underneath without getting smashed.
@MWorsa
@MWorsa 8 ай бұрын
A generous 3 feet 😂
@hillppari
@hillppari 11 ай бұрын
why tf would you put the holster outside????
@MadElectrician
@MadElectrician 11 ай бұрын
Most of the time my garage door is shut, and it’s rated to be installed indoor or outdoor. I don’t want to open my garage door every time I need to charge and any car I charge will be parked in the driveway.
@dubmob151
@dubmob151 Ай бұрын
​@@MadElectrician depends on the area you live in, but the other option would be to install the EVSE unit on the outside wall, but that may not be good if there are enterprising people around that might think they want to try swiping a live unit wholesale. Maybe the manufacturer should implement a micro switch trigger for an alarm notification on tampering if this is actually a problem for people. Some of these units are pretty pricey, so I suppose it could be a lucrative market. The more sophisticated units using Wi-Fi access probably could be disabled and rendered inoperable to remove the theft market, like Ring with their doorbells. If they swipe it, it's useless, so they'll learn to stop stealing them, becoming a self correcting problem.
@faheemuddina
@faheemuddina 3 ай бұрын
Easy peasy lemon squeezy. Csgo much?
@ldiamond3290
@ldiamond3290 3 ай бұрын
240 amps? 😬
@MadElectrician
@MadElectrician 3 ай бұрын
@@ldiamond3290 Did I accidentally say 240 amps somewhere?
@ldiamond3290
@ldiamond3290 3 ай бұрын
@@MadElectrician 7:28 I'd be stressed out dealing with a 56kw device.
@MadElectrician
@MadElectrician 3 ай бұрын
@@ldiamond3290 Shoot, I definitely misspoke 😅 Good catch! I think you’re the first person to point that out. I didn’t even catch that while editing this.
@vladbagdasarov1672
@vladbagdasarov1672 6 ай бұрын
50 amps of constant current for 8 hours daily, I don't know if I'd trust those wire nuts.
@surferdude642
@surferdude642 5 ай бұрын
Most of the EV's allow the user to select the current draw and/or they max out at 35 amps or less. Still, 6 gauge wire and a 50 amp breaker is appropriate.
@vladbagdasarov1672
@vladbagdasarov1672 5 ай бұрын
@@surferdude642I think you misread, the wire is appropriate, the wire nuts on the other hand is sketch.
@michaelcarney8941
@michaelcarney8941 5 күн бұрын
First clue you might not be a Master Electrician (maybe on paper).....you said 240 AMPS PHASE TO PHASE its VOLTS not AMPS. You should have an access hole through the siding to put your cord through and mount to the siding. No way a good... Any kind of HANDYMAN would ever run that cord under the garage door. Let alone hang it where the door will hit the cord on the hanger and floor,EVERYTIME the door goes up and down. The junction box wires should be stripped more than that for the connections. Use Lineman pliers not Strippers to twist wires if your going to twist wires.People can say all they want about my comment,but then you have to explain where im wrong.
@MadElectrician
@MadElectrician 5 күн бұрын
It’s very easy to mean to say one thing and misspeak on video. I can only assume you’ve never once misspoken about anything regarding electrical work? Otherwise you may just be an electrician on paper by your logic. Doing an installation is one thing, and making a video, explaining everything, and getting all of the different shots, is a lot different. The wires didn’t need to be stripped more. The length was more than sufficient. Though I do think Polaris lugs would have been a lot better than wire nuts in this situation. Regardless, I made due with what I had on me and it was still a solid legal installation. There is no right or wrong tool to pre-twist wires with, though I agree that lineman pliers are one of the best options. The Knipex forged wire strippers are fantastic for it as well and don’t require me to reach for another tool. Regarding the cord under the garage door, as explained in the video, there was an existing gap under the garage door that the cable fit perfectly without being even slightly crushed. Further, the car charges in the driveway, not in the garage, so it wouldn’t make sense to open the garage door every time I needed to grab the charger and then leave it open while the car charges. Putting a hole big enough in the siding for the charging plug to fit through would be crazy. I can understand a hole for just the cable, but the cable comes factory attached, rendering that not an option unless I want to void warranty (if it’s even something that can be done. Didn’t check). For my situation at my house, this made the most sense. I didn’t take the time in the video so show all of the spots that didn’t make sense to mount the charger. Short story though is that this was the best option given my situation. And it has worked fantastic with no issues.
@fordsrmaster
@fordsrmaster 4 ай бұрын
I take it that charger didn't use a neutral.
@dubmob151
@dubmob151 Ай бұрын
Haven't seen any EVSE units that use a neutral, they generally have no use for 120V.
@davidmerkrebs9967
@davidmerkrebs9967 6 ай бұрын
don't understand the cord under garage door there had to be a better way totally not professional
@MadElectrician
@MadElectrician 6 ай бұрын
It’s a little weird for sure. It’s at my house though, not somebody else’s. This is also for charging a car in the driveway, not in my garage. The best place to mount the charger was in the garage (no good spaces anywhere outside my garage). There was also a gap under my garage door which this cord has no affect of. At the end of the day, this made the most sense to me for my situation. It’s been over 6 months of it being like this with no issues and no marks or anything on the cable. I also saw somebody else in my neighborhood do the same thing and it worked great for him with no issues. I can always put the cord holster in the garage if I ever want to move it in the future.
@Mohammad-bq5hh
@Mohammad-bq5hh 3 ай бұрын
Is it ok to use Number 2 or 4 or it has to be number 6?
@stevekight1955
@stevekight1955 9 ай бұрын
Does it make any sense to show people how to do your job? When you're out of work, maybe you can watch plumbing videos and learn a new trade.
@MadElectrician
@MadElectrician 9 ай бұрын
It sure makes sense to me ⚡️🤘🏼⚡️
How to Install an Electric Vehicle Charger Receptacle
14:27
Electrician U
Рет қаралды 455 М.
How Many Amps Do You Need For Home EV Charging?
26:08
State Of Charge
Рет қаралды 547 М.
IL'HAN - Qalqam | Official Music Video
03:17
Ilhan Ihsanov
Рет қаралды 700 М.
СИНИЙ ИНЕЙ УЖЕ ВЫШЕЛ!❄️
01:01
DO$HIK
Рет қаралды 3,3 МЛН
99.9% IMPOSSIBLE
00:24
STORROR
Рет қаралды 31 МЛН
Tesla Wall Charger Installation
7:38
Brandon Whitley
Рет қаралды 8 М.
Level 2 EV Charger Hardwire Install (Chargepoint Homeflex)
14:28
Cost to install an EV charger $1,200 - $2,500 - $10,000 ?!
3:44
My Electric Home
Рет қаралды 20 М.
How To Install An EV Car Charger | Easier Than You Think!
10:17
Everyday Home Repairs
Рет қаралды 163 М.
Best Home EV Chargers 2024 - The Only 6 To Consider Today
10:30
Consumer Betterment
Рет қаралды 10 М.
3 Mistakes I Made Installing a NEMA 14-50 Outlet
9:53
Josh Charles
Рет қаралды 389 М.
I Bought a Military Surplus Diesel Generator to Power my House
35:24
Waldo's World
Рет қаралды 6 МЛН
IL'HAN - Qalqam | Official Music Video
03:17
Ilhan Ihsanov
Рет қаралды 700 М.