How to use a Psychrometer for HVAC

  Рет қаралды 24,115

HVAC Service Mentor

HVAC Service Mentor

Күн бұрын

Пікірлер: 27
@derrickhudson4704
@derrickhudson4704 3 жыл бұрын
Thank you so much for your videos I know you do not get millions of views but I promise you The people like me that are viewing these videos highly appreciate you thank you
@hubercats
@hubercats Жыл бұрын
Excellent overview! Thank you.
@danielgurrola4888
@danielgurrola4888 Жыл бұрын
Great video , thanks for simplifying this information. 👍🏼
@paulrozinski1488
@paulrozinski1488 3 жыл бұрын
The yellow, General unit that you were showing next to the sling , I purchased it on Amazon for about $84 and I’m pretty happy with it. The slim design makes it easy to wedge between return grill slats especially on ceiling mounted returns. It also makes it easy to forget and leave behind 😂
@hvacservicementor
@hvacservicementor 3 жыл бұрын
Thanks for the feedback!
@rafaarroyo5438
@rafaarroyo5438 3 жыл бұрын
Thanks, great information. Keep going, we’re rocking down here in central Florida. Now with your knowledge on our side!
@superd0fad0
@superd0fad0 3 жыл бұрын
HVAC student, here. Minute 9:10 you state that Target Superheat chart is for fixed metering devices only. I had understood that we can also use the superheat chart to verify that the TXV is working properly. Did I have the wrong concept?
@hvacservicementor
@hvacservicementor 3 жыл бұрын
A TXV is meant to maintain a constant superheat across a wide variety of operating conditions. On a fixed Metering Device, superheat will change as operating conditions change.
@grok8211
@grok8211 2 жыл бұрын
@@hvacservicementor Wouldn't target superheat work for adjusting the txv?
@JohnnyJr396
@JohnnyJr396 Жыл бұрын
Thank you for doing this. I’m trying to wrap my mind around using wetbulb measurements for performance. Is or was wet bulb the standard along with dry bulb because wet bulb was easier to measure before digital psychrometer meters? Using the two points to determine RH for latent loads? Thansk
@hvacservicementor
@hvacservicementor 10 ай бұрын
When referring to performance measurements, you will need to measure dry bulb temperature across the evap and wet bulb temperature across the evap. Then there are some formulas which will translate those temperature differences into BTU/h. The dry bulb performance indicates sensible heat removal while the wet bulb performance indicates latent heat removal. In my experience, it is difficult to get a really accurate field measurement of wet bulb discharge air temperature. You really need about five duct diameters of straight duct after the evap to do it well. Failing that, you need a special instrument to take a duct traverse and average the measurement. In manufacturer's published performance specs, you will see two specifications: sensible BTU/h and Total BTU/h. The difference between the two is the latent BTU/h which you need do a little subtraction to figure out for yourself. These same specs will often also show what the evaporator dry bulb temperature difference will be at these performance points. This is much easier to measure and as long as you have all the other points covered, you can be "field certain" that you are good to go. In the world of performance contracting, they are often much more concerned with total heat removal in real time than your average service tech. Due to the aforementioned challenge getting good supply air WB measurements, I often wonder how valuable this metric is.
@jeremymcguire7069
@jeremymcguire7069 3 жыл бұрын
I've been using a pair of the Fieldpiece wireless psychrometers for a while. They're pretty slick in that you can read the results of both probes at once from a distance. The only problem is the flexible neck is a fairly large diameter, so it can be hard to get access to the supply and return air without drilling big holes.
@armandisais871
@armandisais871 6 ай бұрын
How to get the outdoor temperature in °C?
@linlee2140
@linlee2140 10 ай бұрын
Do these work reliably in refrigeration?
@hvacservicementor
@hvacservicementor 10 ай бұрын
Refrigeration tries to remove as little moisture as possible. I'm not aware of a good use for psychrometers in typical refrigeration applications.
@blackened89
@blackened89 2 жыл бұрын
Hi! Is a digital psychrometer suitable to measure air conditions at the outlet of small cooling towers? Thanks :)
@MrDabulls73
@MrDabulls73 7 ай бұрын
Great video
@hvacservicementor
@hvacservicementor 7 ай бұрын
Glad you enjoyed it
@vrejbaghoomian7765
@vrejbaghoomian7765 2 жыл бұрын
I have a room we have just replaced a 4 ton rooftop unit , the old unit was burned out , now my grills are sweating , if I take the room temp WB and DB and read the DP , how can I apply these info to make corrections so we wont have this issue These are the info I think I have to obtain 1- room temp WB 2- Room Temp DB 3- return Air WB and DB 4- SUPPLY AIR TEMP AT GRILLS 5-RH OF ROOM 6- RH OF RETURN AIR 7- RH OS SUPPLY AIR
@MichaelDavis-bz2wi
@MichaelDavis-bz2wi Жыл бұрын
Hey I'm applying for a grant and need a mentor can you help?
@brunoshvac2578
@brunoshvac2578 3 жыл бұрын
Great video. Thanks for sharing.
@zesty2023
@zesty2023 3 жыл бұрын
I like my UEI Psychometer, it's fragile but its got a nice big display and gets readings fast.
@realSamAndrew
@realSamAndrew 3 жыл бұрын
Why is dry bulb measured by outside air while wet bulb is taken inside? Isn't that apples and oranges? Of course outside will be higher wet or dry. Outside air is not conditioned and is not going to be run through the system. What am I missing?
@hvacservicementor
@hvacservicementor 3 жыл бұрын
Outdoor dry bulb air temp influences the head pressure which changes the flow rate of refrigerant into the evaporator on fixed metering device systems. You need to know that in order to analyze superheat with a fixed metering device. Indoor wet bulb is the factor which influences how quickly the refrigerant in the evaporator boils off.
@realSamAndrew
@realSamAndrew 3 жыл бұрын
@@hvacservicementor thanks for the quick reply! That makes sense. What is edl?
@pedrocastano6410
@pedrocastano6410 8 ай бұрын
Fluke = waste of money, i got two and they read totally different
@johnadams3800
@johnadams3800 4 ай бұрын
Gotta keep em calibrated
The top 5 mistakes HVAC techs make when troubleshooting.
16:09
HVAC Service Mentor
Рет қаралды 93 М.
Mastering Superheat: The Trick to Charging an HVAC Unit
15:33
Mechanical Pros
Рет қаралды 34 М.
Sigma Kid Mistake #funny #sigma
00:17
CRAZY GREAPA
Рет қаралды 30 МЛН
IL'HAN - Qalqam | Official Music Video
03:17
Ilhan Ihsanov
Рет қаралды 700 М.
小丑女COCO的审判。#天使 #小丑 #超人不会飞
00:53
超人不会飞
Рет қаралды 16 МЛН
Psychrometrics Part 1 - How To Read the Psychrometric Chart
1:03:47
What is the proper temperature drop for air conditioning?
15:32
HVAC Service Mentor
Рет қаралды 21 М.
IR thermometers:  Are they worth it?
12:42
HVAC Service Mentor
Рет қаралды 41 М.
HVAC 052 Measuring Wet Bulb, Dry Bulb and Humidity
12:11
Love2HVAC with Ty Branaman
Рет қаралды 35 М.
Psychrometrics Made Simple
48:04
CaptiveAire
Рет қаралды 116 М.
How to Read a Psychrometric Chart
11:21
Tec Tube
Рет қаралды 386 М.
How To Check Superheat & Subcooling On An HVAC System
16:03
The DIY HVAC Guy
Рет қаралды 121 М.
Wet bulb temperature - why & when is it used?
9:16
Process with Pat
Рет қаралды 83 М.
Finding Target Superheat
15:58
HVAC School
Рет қаралды 21 М.
Sigma Kid Mistake #funny #sigma
00:17
CRAZY GREAPA
Рет қаралды 30 МЛН