HOW TO WIRE Conventional Smoke / Heat Detector's ( FDAS) | Fire Alarm Conventional System

  Рет қаралды 46,097

RACkabayanTECH

RACkabayanTECH

3 жыл бұрын

In a conventional fire alarm system, all devices such as detectors, sounders and call points are connected to the control panel through separate wire or cable instead of shared one. In other words, the first end of the wire is connected to the detectors and second one to the control panel.
In a typical conventional fire alarm system, detectors, sounder and call points are installed and divided into different zones i.e. Zone 1 for basement, Zone 2 for ground floor, Zone 3 for first floor etc. This way, it is easy to identify the exact affecting area to the control room, building management and fire brigade. In other words, the more numbers of zones, the more accurate locating the trigger and fire location.
Keep in mind that the very accurate and exact location of fire can’t be found easily in a conventional fire alarm system as compared to the addressable fire alarm system. As the control panel won’t allow you to pinpoint the exact location of individual device or which device has been triggered but only shows the zone location by text, lamp indicator or both in case of emergency.
There are four types of fire alarm systems:
1. Conventional fire alarm system
2. Addressable fire alarm system
3. Intelligent fire alarm system
4. Wireless fire alarm system
There are five types of detectors:
1. Smoke detector
2. Heat detector
3. Manual call point
4. Carbon monoxide detector
5. Multi sensor detector
There are two types of sounder:
1. Bell sounder
2. Electronic sounder
How to WIRE Smoke / Heat Detector Addressable: • HOW TO WIRE Addressabl...
If this video helped you out, share it with your friends and give it a thumbs up, please drop a like and leave a suggestion or comment below.
----------------------------------------------------------------------------------------------------------------
Our daily routine as Maintenance Technician in our company.
#Please_Like_Share_and_Subscribe​_RACkabayanTECH​​
➦ For more videos please SUBSCRIBE! 👍
©️ Disclaimer Under Section 107 of the Copyright Act 1976,
allowance is made for "fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, and research.
Fair use is a use permitted by copyright statute that might otherwise be infringing.
Non-profit, educational or personal use tips the balance in favor of fair use.

Пікірлер: 74
@RACkabayanTECH
@RACkabayanTECH 3 жыл бұрын
This video presentation is for educational purposes only
@edinaguilar12
@edinaguilar12 3 жыл бұрын
Watching your video always bro. Keep sharing your knowledge.
@RACkabayanTECH
@RACkabayanTECH 3 жыл бұрын
Thanks sis....appreciated
@johnvincent4348
@johnvincent4348 2 жыл бұрын
Thanks, man
@pejarckskilledwtv1081
@pejarckskilledwtv1081 2 жыл бұрын
new subsc. sir. ang galing malinaw at naintindihan tlga kht diagram lng.
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Appreciated partner🙏🏽👍
@ErnestoArcega
@ErnestoArcega 5 ай бұрын
Pwedi pong Makita hitsura ng daiode
@ErnestoArcega
@ErnestoArcega 5 ай бұрын
Para sa end of line sa smoke at manual callpoint
@DerrickChan-qk1su
@DerrickChan-qk1su 6 ай бұрын
Tanong lang po,Anong size Ng wire po Ang dapat gamitin?
@georgereyes4924
@georgereyes4924 Жыл бұрын
Anu po maximum dist per zone po
@markguibo3611
@markguibo3611 2 жыл бұрын
Kaya po ba isang sounder ang 5 serin with strobe light??
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Yes po👍 partner😊
@jjcelectricaljourney8151
@jjcelectricaljourney8151 2 жыл бұрын
sa end of line pwd din ilagay resistor boss. o palitan ang diode ng resistor.
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Indeed partner👍
@fandulan
@fandulan Жыл бұрын
ano pong brand ng panel nyo po sir, parang same din ng gamit ko ngayon na made in china ang wiring na programmable na conventional.
@patrickeniego8619
@patrickeniego8619 2 жыл бұрын
Lodi ano pung diod Ang pweding ilagay..
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Ang diode or resistor na pwedeng gamitin ay naka depende po sainyong FACP....I hope nakatulong.....
@psycho_w.t.g
@psycho_w.t.g 9 ай бұрын
Can fire alarm system wire run in the same conduit with light fixture
@RACkabayanTECH
@RACkabayanTECH 9 ай бұрын
No sir you need to separate conduit.....
@user-gl3ui3wp2x
@user-gl3ui3wp2x 4 ай бұрын
Pwd ba Ang diode or resistor Ang ilagay sa ending of line? Kasi kadalasan resistor Ang nka lagay
@RACkabayanTECH
@RACkabayanTECH 3 ай бұрын
Pwede partner kasama ang diode sa pagbili ng FACP😊
@robertbasijan8991
@robertbasijan8991 2 жыл бұрын
Sir paano po kung wireless po ang gagamitin sa smoke need parin poba ng panel? Tatlong palapag kasi na bahay. Salamat sir god bless
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Yes sir need parin ng pang wireless na (FACP) Fire Alarm Control Panel may video rin ako 🙂About wireless fire alarm system please watch it
@sakuragiibanez4579
@sakuragiibanez4579 2 жыл бұрын
Nakadepende pa rin ang pasok ng wire sa terminal ng device sir tama ba? Kasi ung ibang device iba nmn ang termination merong 2,3,5,6..
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Tama po kayu sir!
@tootsiecastaneda4912
@tootsiecastaneda4912 Жыл бұрын
Sir magandang araw po tanong ko lang kung paano mag test ng per device salamat po
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Hi partner salamat sa panonood! Malalamam mo ang isang device naka activate dahil may red LED naka (blink-blink)
@georgereyes4924
@georgereyes4924 Жыл бұрын
Sir bkt diode instead resistors
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Pwede diode pwede ring resistor partner! May mga panel na ginagamitan ng diode👍
@matthewfrias9618
@matthewfrias9618 2 жыл бұрын
Anu po ang mangyayari kung walang diode o resistor?
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Mag tutrouble po ang FACP hindi po sya magnonormal pag walang diode or redistor👍
@liezlianetabag3558
@liezlianetabag3558 Жыл бұрын
Ung zone 1 po bwed gawin tatlong sounder nka. Pararel lang
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Pwedeng pwede partner👍😊
@johnleansabong3621
@johnleansabong3621 11 ай бұрын
boss sana mabasa mo request sana Ako Ng video Ng wireless fire alarm system asenware brand
@RACkabayanTECH
@RACkabayanTECH 10 ай бұрын
May video na ako nyan partner panoorin mo nalang salamat
@johnleansabong3621
@johnleansabong3621 10 ай бұрын
@@RACkabayanTECH salamat boss
@robertodelacruz4525
@robertodelacruz4525 Жыл бұрын
Pls ung name po request po sana materials ng conventional at saan pedeng omorder
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
😊👍
@georgereyes4924
@georgereyes4924 Жыл бұрын
Sir pk sagot po,kung anu maximum dist per zone
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Naka depende po sa installation partner sa conventional fire alarm system sa isang ZONE 30pcs devices lang po ang allowed..... Walang specific distance ang pinag uusapan 30pcs initiating devices lang po! ang lahat na naka install sa isang ZONE I hope nakatulong...... partner😊
@ieL_bhesT24
@ieL_bhesT24 Жыл бұрын
pwedi po ba mag T top sa wiring ng conventional?
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Hindi po pwede mag T top sa conventional system partner isa lang po ang end of line sa bawat zone partner sana nakatulong😊
@papavlog-tm4hs
@papavlog-tm4hs 11 ай бұрын
pd Po ba din ako mag message sa inyo
@RACkabayanTECH
@RACkabayanTECH 11 ай бұрын
Yes via Facebook page partner😊
@juanitopolenio9482
@juanitopolenio9482 Жыл бұрын
Ano po ba ang value ng diode natin na ginagamit para sa end of line at bakit po sa iba ang ginagamit nila end of the line ay resistor
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Partner naka depende po FACP resistor or diode ang pwedeng gamitin sa end of line sana nakatulong....
@juanitopolenio9482
@juanitopolenio9482 Жыл бұрын
Sir, ibig nyong sabihin inyong value ng diode or resistor ay naka-indicate po sa FACP paano po kung wlang naka-indicatr sa panel meron po bang formula kung papaano mag compute ng value
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Hi partner, sensya na now ko lang nabasa comment mo actually nakadepende po yan sa brand ng FACP! May brand po ng FACP na resistor ang gamit ng EOL may FACP na diode po ang ginamit na EOL......
@crismarano9632
@crismarano9632 2 жыл бұрын
Resistor po ba ilalagay sa end of line?saka yung heat detector po ba pwede po sya sa end of line?kasi lagi sya nasa gitna eh
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Diodes or Resistor ang ilalagay sa EOL ang heat detector pwede naman sya ilagay sa pang huli as long as na makakadetect sya ng mainit 😄 Sana nakatulong partner🤓
@crismarano9632
@crismarano9632 2 жыл бұрын
@@RACkabayanTECH slmt po hehe baguhan lang kasi ako ,,hehehe❤️
@nashdennielevangelista2599
@nashdennielevangelista2599 Жыл бұрын
@@RACkabayanTECH ask qo lang po dpo sa likod ng panel naka indicate dun ang value ng resistor na ilalagay qo sa eol.
@novievillegas6867
@novievillegas6867 5 ай бұрын
sir, pwede kayang paghaluin ang conventional at saka addressable na mga smoke detector? example, sa loob ng apartment, conventional ang mga SD, then sa hallway naman, addressable SD ang gagamit? thanks and looking forward mo sa sagot nyo
@RACkabayanTECH
@RACkabayanTECH 5 ай бұрын
Sa ganyang setup partner gagamit lang po kayo ng module para magawa mo yang gusto mo! may video po ako nyan panoorin mo nalang salamat
@irvinavresaldo8212
@irvinavresaldo8212 Жыл бұрын
Manual call point ba tlga mauunang device bos
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Any device ang pwedeng mauna boss sana nakatulong😊
@jayjaraba1113
@jayjaraba1113 2 жыл бұрын
Boss bkit po diode nilagay s end of line?
@RACkabayanTECH
@RACkabayanTECH 2 жыл бұрын
Hello partner...... sa (EOL) diode o resistor ay pwedeng ilagay sa EOL depende po sainyong (FACP)👍
@carlovicacuevas186
@carlovicacuevas186 Жыл бұрын
Bakit po kailangan lagyan ng resistor or diode
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Hi partner salamat sa panonood! SOP po yan partner kapag ang control panel mo ay conventional system S.O.P po Diode/Resistor sa installation😊
@eutimioytac853
@eutimioytac853 Жыл бұрын
DIODE OR RESISTOR?
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Depende sa Fire Alarm Control Panel na conventional na gamit mo may mga panel na ang gamit ay diode may mga panel din na resistor ang gamit partner😊
@marioespiritu4295
@marioespiritu4295 Жыл бұрын
Yung tamper switch at flow switch asan po?
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Wach here partner: kzbin.info/www/bejne/a3aceXdua5mFhZI
@marioespiritu4295
@marioespiritu4295 Жыл бұрын
Maraming salamat po. Magkaiba pala sa addresable
@zachyjovs1645
@zachyjovs1645 Жыл бұрын
Boss halimbawa po 10 ang smoke detector pwedi rin ba 10 din ang manual call point? Yung manual call point pwedi ba doon na rin ilagay sa kwarto isa sa bawat smoke detector? Ok lng ba yon?
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Ok lang yan boss basta hindi lang lalagpas don sa allowable device sa isang zone/loop.....ang manual call point boss ay naka design sa mga hallway or any visible area para accessible sa tao just incase magka roon ng sunog Kung ilalagay mo sa kwarto ang MCP hindi po sya advisable at hindi papasa sa commissioning ng civil defense😊 Sana nakatulong partner🙄
@zachyjovs1645
@zachyjovs1645 Жыл бұрын
@@RACkabayanTECH ah ok boss may wiringan sana ako boss d2 sa amin kompanay di pa ako nakapag wiring or nakapag install ng fire alarm, nakabili sila conventional, bali smoke detector, strobe light at manual call point lng ang device, yung smoke nakalagay lng sa base number lng, 1,2,3,4, diko madetermine saan ang - at +, ok lng ba boss na isang manual call point ang isama ko sa walong smoke detector sa isang zone, at isang strobe light at isang manual call poin sa sounder?
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
Yes partner pwedeng pwede👍
@zachyjovs1645
@zachyjovs1645 Жыл бұрын
@@RACkabayanTECH yung sa smoke detector boss, saan kaya ang negative at positive kasi yung sa base number lng nakalagay 1,2,3,4 di ko malaman kung saan don ang negative at positive?
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
E continuity test mo partner para malaman mo alin ang magkapares dyan L1in L1out Common usually sa ganyang configuration (1in 2out) 3 or 4 common double check lagi for sure sana nakatulong
@joelkangleon134
@joelkangleon134 Жыл бұрын
Ang hina naman ng sound full volume cp ko halos indi k marinig ang boses.
@RACkabayanTECH
@RACkabayanTECH Жыл бұрын
🤥✌️
How to wire FIRE MONITOR MODULE in Fire Detection Alarm System
5:35
RACkabayanTECH
Рет қаралды 4,9 М.
Scary Teacher 3D Nick Troll Squid Game in Brush Teeth White or Black Challenge #shorts
00:47
I Can't Believe We Did This...
00:38
Stokes Twins
Рет қаралды 104 МЛН
Who has won ?? 😀 #shortvideo #lizzyisaeva
00:24
Lizzy Isaeva
Рет қаралды 62 МЛН
22 - Intelligent panels - Introduction to Fire Alarms
11:28
Joe Klochan
Рет қаралды 96 М.
What is a Fire Alarm System?
11:06
RealPars
Рет қаралды 2,1 МЛН
WIRING & TERMINATION OF CONVENTIONAL FIRE ALARM SYSTEM
25:34
Himmax Electronics Corporation
Рет қаралды 114 М.
How to Connect Fire Alarm System in our Home @TheElectricalGuy
13:09
The Electrical Guy
Рет қаралды 47 М.
Actual Wiring Connection of Fire Alarm Control Panel to Accessories
19:46
sirib ni ILOKANO Channel
Рет қаралды 44 М.
The Essential Guide to Fire Alarm Grades
6:48
eFIXX
Рет қаралды 7 М.
HOW TO INSTALL FIRE ALARM SYSTEM FDAS
30:07
DEPED TESDA TV
Рет қаралды 464 М.
Smoke Detector and Fire Alarm Panel Connection
9:56
Pranav Shastry
Рет қаралды 1 М.
Scary Teacher 3D Nick Troll Squid Game in Brush Teeth White or Black Challenge #shorts
00:47