No video

22 - Intelligent panels - Introduction to Fire Alarms

  Рет қаралды 96,656

Joe Klochan

Joe Klochan

Күн бұрын

In this video I explain how intelligent smoke detectors communicate with intelligent panels. I also introduce monitor modules and explain how they are an interface between intelligent panels and conventional devices.

Пікірлер: 47
@melechmeek2357
@melechmeek2357 Жыл бұрын
A decade old video bro, but it’s timeless with its information. Thank you 💪🏾
@boogums1
@boogums1 2 жыл бұрын
Thank you for these videos! I’ve been able to go back numerous times.
@Vektr1
@Vektr1 9 жыл бұрын
Endlessly appreciate all of your effort put into these videos. Thank you, and best wishes.
@maxpeel2027
@maxpeel2027 2 жыл бұрын
You got me a raise at work. Thanks man.
@mike3177
@mike3177 5 жыл бұрын
Best Visuals on YT! Killed it.
@tevin1925
@tevin1925 3 жыл бұрын
You are a great teacher
@JoeKlochan
@JoeKlochan 3 жыл бұрын
Thanks!
@Angrychefofficial
@Angrychefofficial 11 жыл бұрын
Great series of videos. Good job and keep them coming!!
@carlhenke6968
@carlhenke6968 7 жыл бұрын
is it possible to program a commercial fire alarm system for more than one sound? can they be programed for 2 or more sounds for diffrent Emergency?
@peterlesko3525
@peterlesko3525 2 жыл бұрын
Awesome videos thank you
@madwillyak47
@madwillyak47 4 жыл бұрын
79k views and under 500 likes . Probably why he stopped making videos . Like the video guys !!
@nikulpanchal5286
@nikulpanchal5286 6 жыл бұрын
@Joe Klochan Very thanks for your videos I am having Sea Plus FDS System installed on our vessel for which I am getting Loop-2 & Loop-4 Fault How can i identify for W/B across addressable portion of the circuit.
@nicks7768
@nicks7768 Жыл бұрын
Joe, can you give an example of a pump room device where you would connect to COM and NC?
@JoeKlochan
@JoeKlochan Жыл бұрын
There's not a good reason I could think of, at least not with an addressable panel. If you had an old conventional panel that didn't have the capability of programming a zone as supervisory, and so a short on any zone would cause an alarm, then you'd want a tamper to open the circuit to cause a trouble.
@electricaltech4u45
@electricaltech4u45 4 жыл бұрын
V nice
@RicardoSanchez-ez6lw
@RicardoSanchez-ez6lw 3 жыл бұрын
Hi, which multimeter is best for trouble shooting fire alarm system. What brand
@JoeKlochan
@JoeKlochan 3 жыл бұрын
My opinion would be fluke, and that seems to be the industry standard. I haven't really given another brand an honest try, besides using someone else's meter here or there, so take this advice with a grain of salt. I have used a fluke 179 for as long as I can remember and have no reason to change that now.
@samargoswami3584
@samargoswami3584 6 жыл бұрын
There is only two power cable having dc supply, does SD or MCP communicating through this power cable if so than how ? Please explain... Thanks
@lampoyo
@lampoyo 4 жыл бұрын
I'm trying to figure out using devices with N.O. / N.C. and having a relay with the same. Does the relay switch as well during signaling?
@JoeKlochan
@JoeKlochan 4 жыл бұрын
I'm not sure what you're asking. Can you explain your situation in more detail?
@calumdavie9291
@calumdavie9291 4 жыл бұрын
hi Chris best way to link Conventional panel to addressable panel
@fxallo1
@fxallo1 3 жыл бұрын
First, you need to identify all of your conventional zones as well as all end-of-line resistor locations. If you have the order of connection of your detectors, it will be even better. You will need to get for your transition: one zone monitor per conventional zone to be able to supervise your system. Subsequently, replace all the components of a conventional circuit at a time with addressable modules. Start from panel to EOL if possible. Never forget that your system must be operational when you leave the client. Try doing this for the first time with someone who is used to doing it. The last piece of advice I give you is to plan and prepare yourself so that you don't have any surprises
@elijahgitanga5174
@elijahgitanga5174 Жыл бұрын
In the wiring of beam detector to a fmm 1, do we follow the same wiring as the water flow switch?
@JoeKlochan
@JoeKlochan Жыл бұрын
Typically you would wire it more closely to a conventional duct detector, where the wires go into the alarm contacts on common / normally open, but then the resistor runs through the trouble contacts.
@elijahgitanga5174
@elijahgitanga5174 Жыл бұрын
@@JoeKlochan okay thanks
@crayons071
@crayons071 2 жыл бұрын
Can yo do some videos on old simplex panels?
@JoeKlochan
@JoeKlochan Жыл бұрын
That's not my wheelhouse. It's been years since I had to work on them, and i never worked for them so I never knew them well enough to teach anything about them.
@crayons071
@crayons071 Жыл бұрын
@@JoeKlochan No problem, Thanks so much for the videos👍 you saved my butt plenty
@zelwas
@zelwas 9 жыл бұрын
Thanks I found a lecture
@MrDjmorales
@MrDjmorales 3 жыл бұрын
How many ohms the resistor in the waterflow switch?
@JoeKlochan
@JoeKlochan 3 жыл бұрын
Always depends on the module you use. In all of my drawings, which use system sensor style devices, the EOL would be 47k Ohms, but it will be different if you're using a different type of module.
@MrDjmorales
@MrDjmorales 3 жыл бұрын
@@JoeKlochan I really appreciate your video. I am waiting the video about the addressable fire alarm system connection. Is it the same as intelligent fire alarm system?
@josephh3557
@josephh3557 9 жыл бұрын
hi is it possible to make conventional sounders addressable
@elevatorsofamerica
@elevatorsofamerica 8 жыл бұрын
I want to say you can. On eBay they have the monitor module for pulls and smokes that you can put in the unique device id
@edwardf.antopina3826
@edwardf.antopina3826 8 жыл бұрын
in Siemens addressable facp system..what's is the used for IFU( HCP type and HTRI-R type)?
@imdadhussain9688
@imdadhussain9688 6 жыл бұрын
Hello sir can you tell me how we can solve Psu trouble in agies panel
@kinkisharyocoasters
@kinkisharyocoasters 10 жыл бұрын
@Joe Klochan If not an ordinary trouble condition, what does the panel display if the wire breaks on the addressable portion of the circuit?
@Memerino-ly7yr
@Memerino-ly7yr 8 жыл бұрын
a blockage
@Androideddy1
@Androideddy1 4 жыл бұрын
You told us how u label them, but how does the panel know that 5 is the one u want to be 5. You call the smoke detector 1 and in the panel you tell it that a smoke detector is 1, but how does it know which smoke detector.. hope u understand what I am trying to say.
@JoeKlochan
@JoeKlochan 4 жыл бұрын
I do understand. All addressable devices have a way to set the address on the device. On System Sensor-style devices (which are the types of devices I draw, used by Gamewell/FCI, Notifier, Fire-Lite, & Silent Knight), it's a rotary dial that addresses the devices. Some manufacturers like Simplex use binary DIP switches, which I could do a video on. Other manufacturers require a separate handheld programmer that you place the device into and set the address. Lastly some manufacturers use an embedded serial number, and the panel learns the "address" based on that.
@muhammadsalman5746
@muhammadsalman5746 3 жыл бұрын
A/C 5ton to fire
32 - Metering a Ground Fault - Introduction to Fire Alarms
16:03
Joe Klochan
Рет қаралды 60 М.
17 - Sprinkler Systems (con't) - Introduction to Fire Alarms
12:08
ROLLING DOWN
00:20
Natan por Aí
Рет қаралды 10 МЛН
26 - FCPS  - Introduction to Fire Alarms
10:10
Joe Klochan
Рет қаралды 45 М.
Fire Training
51:37
SilmarElectronicsInc
Рет қаралды 137 М.
Why are Smoke Detectors Radioactive?  And How do Smoke Detectors Work?
18:59
Branch Education
Рет қаралды 1 МЛН
System Test 28:  AC Devices!
21:22
FrostedStrobes
Рет қаралды 169 М.
The Clever Way to Count Tanks - Numberphile
16:45
Numberphile
Рет қаралды 994 М.
31 - Metering Fire Alarm Circuits - Introduction to Fire Alarms
14:37
6 - Digital Dialers - Introduction to Fire Alarms
11:06
Joe Klochan
Рет қаралды 57 М.
What is a Fire Alarm System?
11:06
RealPars
Рет қаралды 2,1 МЛН
8 - Wireless radios - Introduction to Fire Alarms
10:31
Joe Klochan
Рет қаралды 43 М.
Hacking a weird TV censoring device
20:59
Ben Eater
Рет қаралды 3 МЛН