HVAC: Commercial FCU Not Heating/Cooling (FCU Fan Not Running) Commercial HVAC Troubleshooting

  Рет қаралды 12,898

Jumper man Tech

Jumper man Tech

5 ай бұрын

HVAC: Commercial FCU Not Heating/Cooling (FCU Fan Not Running) Commercial HVAC Troubleshooting / HVAC Service Call: York 4 Pipe FCU NIGHTMARE UNIT Not Heating (FCU Not Blowing Hot Air) HVAC FCU / HVAC Service Call: York 4 Pipe FCU NIGHTMARE (York Fan Coil Unit Not Heating/Not Cooling) Water Leak /FCU Not Heating (AC Fan Coil Unit Not Heating Or Cooling) Repair / HVAC Service Call: Fan Coil Unit Not Cooling Or Heating (HVAC Fan Coil Troubleshooting) No Heat/Cool / FCU Fan Coil Unit / No Heat / No Cool / Not Heating / Not Cooling / Fan Coil Unit Not Working / Fan Coil Unit Not Blowing Cold Air / Fan Coil Unit Not Blowing Hot Air / Fan Coil Unit Actuator Troubleshooting / How To Check A HVAC Actuator / Spring Return Actuator / HVAC Hack Job / HVAC Hack Jobs / AC Hacks / HVAC Hacks / HVAC Electrical Wiring / HVAC Electrical Troubleshooting / Actuator Valve Installation / Actuator Valve Replacement / Zone Valve Installation / 2 Pipe Fan Coil Unit Not Heating (Fan Coil Unit With Emergency Electric Heat) HVAC (Heating, Ventilation, Air Conditioning) FCU Not Heating/Cooling / HVAC Fan Coil Unit / HVAC Fan Coil Unit Not Working / HVAC Fan Coil Unit Not Heating / HVAC Fan Coil Unit Not Cooling / HVAC Fan Coil Unit Troubleshooting / HVAC FCU / FCU Not Cooling / FCU Not Heating / FCU Not Turning On / FCU Not Working / FCU Maintenance / FCU Troubleshooting / FCU Installation / FCU Thermostat / FCU Valve Actuator / FCU Transformer / FCU Control Relay / FCU SPDT Auto Changeover / FCU Pipe Sensor / Chilled Water Fan Coil Unit / Hot Water Fan Coil Unit / 2 Pipe Fan Coil Unit / 4 Pipe Fan Coil Unit #HVAC #FCU #jumpermantech
GoPro HERO8 Black (Camera Used In This Video)
amzn.to/3q4FmEz
Veto Pro Pac TECH MC
amzn.to/3gURJyZ
Fluke 902 FC HVAC True-RMS Clamp Meter
amzn.to/39wvwiK​​
Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
amzn.to/3VNYXDv
Klein Tools ET600 Megohmmeter Insulation Tester
amzn.to/409iNvu
Supco M500 Insulation Tester/Electronic Megohmmeter
amzn.to/42oy0ua
Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
amzn.to/3FcWElQ
Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
amzn.to/3E4W0Fr
Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
amzn.to/3mi8Fih
Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
amzn.to/3FbDufQ
Milwaukee M12 2-Tool Combo Kit 2598-22
amzn.to/3CtCRNC
Milwaukee Cut 1 Dipped GLOVES L
amzn.to/3s8H18O​
Milwaukee 2351-20 M12 LED Stick Light
amzn.to/3rVJKEK
Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
amzn.to/3e53ygW
Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
amzn.to/3qazJkC
Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
amzn.to/32fxC6I
Milwaukee 4932459097 Billet Torpedo Level
amzn.to/30Dh6Nw
Milwaukee Wide Blade Magnetic Tape Measure 16 FT
amzn.to/3yEN7kL
Milwaukee Fine Pt. Markers Black
amzn.to/3e4fH5W
Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
amzn.to/320XiEF
Klein Tools 11-in-1 Screwdriver / Nut Driver
amzn.to/3s3o8ql
Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
amzn.to/3e4ur4x
Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
amzn.to/321n4bW
Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
amzn.to/3J11hS1
Klein Tools 32581 4-in-1 Electronics Screwdriver Set
amzn.to/3yEj3WC
Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
amzn.to/3yRUiGJ
Yellow Jacket 18975 Charge Tool
amzn.to/3J4pfvJ
Yellow Jacket 60613 Service ratchet Wrench
amzn.to/3E8iYeZ
Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
amzn.to/3q0TQ4M
Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
amzn.to/3e0USrY
Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
amzn.to/3qqKlw7
Crescent 4" Adjustable Cushion Grip Wrench
amzn.to/3J4qsmL
Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
amzn.to/30EQmw5
Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
amzn.to/3H9iYAu
KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
amzn.to/3e3IEi7
KNIPEX Tools - Long Nose Pliers With Cutter
amzn.to/3gUSE2i
KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
amzn.to/3p6lFsZ
KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
amzn.to/3mh8K5U
KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
amzn.to/3F1VScb
KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
amzn.to/3sftr5Q
KNIPEX Tools 3 Piece Cobra Pliers Set
amzn.to/3FbRwy7
KNIPEX Tools Pliers Wrench 3-Piece Set
amzn.to/3nnRLfW

Пікірлер: 81
@billyhorton5779
@billyhorton5779 5 ай бұрын
I dont know what you are charging this hotel, its probably not near enough, to be correcting everybody else's shade tree repairs. You the man JMT!
@JumpermanTech
@JumpermanTech 5 ай бұрын
Always finding something new. Fire alarm company not only left this unit tripped but ALL of the base units were down. Can't make this stuff up 😂 Haha thank you! 🙏🔧⚡️
@christorres2063
@christorres2063 5 ай бұрын
Anytime you come across a VFD that has incoming power but doesn’t run at all in any position it’s always a safety that’s open. Fire, high static switch, freeze protection, usually they are tied together, just got isolate which safety it is. Good videos man.
@oldmetalguy4577
@oldmetalguy4577 5 ай бұрын
That water leak is great content...as long as I'm here and not there. lol
@JumpermanTech
@JumpermanTech 5 ай бұрын
Haha I hear that! As soon as there's a day that is not so cold, the building will attempt to shut that water down and we will make the repair. Not looking forward to that. Thanks for watching! 🔧⚡️
@jrh86
@jrh86 5 ай бұрын
The site that keeps on giving 😂 nice one JMT 💯💯💯
@JumpermanTech
@JumpermanTech 5 ай бұрын
Oh yes! 😂 Thank you!🔧⚡️
@izzybell11
@izzybell11 5 ай бұрын
Excellent investigative and well explained video !!! Great job as always JMT.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you very much!! 🙏🔧⚡️
@genewheeler6320
@genewheeler6320 5 ай бұрын
Nothing like falling in quicksand. Lol. I love when you get whole story. I always like who,what where ,when in diagnostic
@JumpermanTech
@JumpermanTech 5 ай бұрын
Haha I hear that. The fire alarm company not only left this unit off but ALL of the base units were shut down. The building didn't even know they were doing these tests until they all left. Somehow forgot to turn the alarms off and reset the units. Always something interesting 😂
@gregeconomeier1476
@gregeconomeier1476 4 ай бұрын
Good videos! I really like the way you methodically walk through and describe your diagnosis process.
@samuelaiken2570
@samuelaiken2570 5 ай бұрын
Haven’t watched full video yet only a few minutes in, but the device with the green dot is a CT that shows status for our controls. I mainly do Alerton controls but my company also does delta and distech. Nice to see some of our controls in the field lol. I love how everyone says “its a controls issue” when 9/10 it isn’t🤣🤣
@nicolerennie
@nicolerennie 5 ай бұрын
😱🤯 great video & content JMT ⭐️
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you!! 🙏🔧⚡️
@Aleksandr-zh9mb
@Aleksandr-zh9mb 5 ай бұрын
Hello. I watch your videos. I myself serviced the same York and Carrier installations in Manhattan. I am currently working as a mechanic in a car service center. but this season I want to return to hvac. I'm buying an expensive tool for hvac repair.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Hello, that's very cool! Sounds like a good plan. Thank you for watching🙏🔧⚡️
@ivanpena6774
@ivanpena6774 5 ай бұрын
Coaching. SOUNDS LIKE YOU GIT WORK MY GUY
@JumpermanTech
@JumpermanTech 5 ай бұрын
Definitely got work over here. It's not a glamorous place but that's why the service calls keep rolling in 👍 Thanks for watching! 🔧⚡️
@spaceboy7192
@spaceboy7192 5 ай бұрын
One would think if the so called building engineer gave a crap about the forever water leak his boys would install a larger pan or some kind of diverter. We have the same issues at our accounts, to busy in the maintenance shop doing nothing.
@JumpermanTech
@JumpermanTech 5 ай бұрын
I hear that. I installed that pan when they couldn't shut the water down so we can make the repair. Leak ended up getting a lot worse and it is what it is at this point. A larger pan would definitely help. That room is getting destroyed as we speak. Not looking forward to making that repair. Thanks for watching!
@stevencossaboon3237
@stevencossaboon3237 5 ай бұрын
Nice work Jumper man.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you very much! 🙏🔧⚡️
@soloch69
@soloch69 5 ай бұрын
Great video like always 🫡 keep them coming
@alexpasco6592
@alexpasco6592 5 ай бұрын
I learn more from you than trade school
@elitss8883
@elitss8883 5 ай бұрын
Is this that unit that has a bad water leak that you fixed? Your Bad ass tech bro!! Keep those videos coming!
@JumpermanTech
@JumpermanTech 5 ай бұрын
It is! We only made the temporary repair because they couldn't shut down the water. Some valves are leaking by. The leak got a lot worse as you can see 😂 Thank you & thanks for watching! I will be making the true repair on this in the near future when it's not so cold out so they can turn the heat off. 🙏🔧⚡️
@67tr876
@67tr876 5 ай бұрын
That's definitely not a local 94 ran building lol horrible maintenance. Good job tho Jumper man !!
@JumpermanTech
@JumpermanTech 5 ай бұрын
It is not haha they definitely need better maintenance here. Thanks for watching! 🔧⚡️
@mattbirchfield5421
@mattbirchfield5421 4 ай бұрын
That yellow and blue are normally closed contacts on an RIB. Yellow is common to blue/ closed and orange/ open set on the ones I install. Should be listed on the RIB it’s left. That solid green on the fire alarm normally means an issue on the controls safety circuit fire alarm shutdown. Blinking means operating normal condition. When you put a vfd in bypass and hand and it does nothing the safety circuit is broken. High static fire alarm freeze protection. Another thing on fire alarm contacts is they can be normally open or closed. Just did 7 rtus and the system there shutdown on closed contacts. Only way to see if look at the fire alarm module and see where the safety for the equipment is landed on.
@scottmaz4063
@scottmaz4063 5 ай бұрын
JMT TO THE RESCUE WELL DONE.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Reporting for duty! Haha thank you! 🔧⚡️
@dylankornegay9794
@dylankornegay9794 5 ай бұрын
That place looks like my job where I work holy hell.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Fun times 😂 Thanks for watching! 🔧⚡️
@you166mhz
@you166mhz 5 ай бұрын
good show ...
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you! Stay tuned for new videos every week🔧⚡️
@williamgildea8348
@williamgildea8348 5 ай бұрын
I know you’re not looking forward to do that repair but I think your followers are, I know I am.
@AndreasAndersson344
@AndreasAndersson344 5 ай бұрын
👍👍👍👍👍👍👍👍👍👍👍👍👍
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you🙏👍🔧⚡️
@ivanpena6774
@ivanpena6774 5 ай бұрын
Always A Great Thing
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you! 🔧⚡️
@joshuabest100
@joshuabest100 5 ай бұрын
Soon as i saw the green light on that alarm panel i thought thats what is holding it off
@JumpermanTech
@JumpermanTech 5 ай бұрын
Nice. I thought the opposite honestly. Need to keep an eye out for that stuff from now on. Thanks for watching! 🔧⚡️
@joshuabest100
@joshuabest100 5 ай бұрын
@@JumpermanTech soon as I saw all the rest of the fire panels blinking and the one connected to the air handler was solid it told me that the fire panel is in alarm
@jasonjohnsonHVAC
@jasonjohnsonHVAC 5 ай бұрын
​@@joshuabest100 same here...i was talking to my phone like....theres the problem......noooo...where you going homie....you found the issue with the fan. The green light is the source of confusion....people expect a red light or something other than green
@shafishaikh2404
@shafishaikh2404 5 ай бұрын
Very nice
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you very much! Stay tuned for new videos every week🔧⚡️
@joekonopka5161
@joekonopka5161 5 ай бұрын
There is usually a small abb disconnect inside the small enclosure directly underneath the VFD. Sometimes they burn up or are off. Easiest thing to do would be to take the cover off the VFD and check the input voltage. If there’s no voltage check the small disconnect inside the enclosure below. More then likely the drive failed long before you were there and they have been running in bypass for awhile. If you have input voltage to the VFD then either the display is bad of the VFD is bad.
@Doug4367
@Doug4367 4 ай бұрын
As soon as you showed the fire modules I saw this issue. His "guys" will not fix that fan they just leave it in bypass and it runs 24/7
@jmead6121
@jmead6121 4 ай бұрын
had the Fire detectors trick me one twice w/ an open run circuit esp after they just left the site & had a few leaks develop also ..iam to big to crawl in on that leak location O boy Have Fun & also had build maintenance could NOT find a cut off on hi rise leakin bad .on 9 th floor ..its crazy
@zekenzy6486
@zekenzy6486 5 ай бұрын
Great Video. Good Job and Nice Work. Thank you for sharing. Is this Building Hvac unit for Hotel ?
@JumpermanTech
@JumpermanTech 5 ай бұрын
Thank you! Yes, this is one of their large fan coil units serving the main spaces of the hotel. Stay tuned for new videos every week🔧⚡️
@andrewshock8703
@andrewshock8703 5 ай бұрын
You said it was 18 degrees, go back and check you're freeze limits, it's a safety in series that cuts unit on freeze limits, door switch, fire, ect ... Anything in that safety cuts, it cuts the circuit and opens the preheat valve. Putting it in hand bypasses the safety and at 27 degrees you will freeze your chilled water coil FAST and have yourself a flood😮. Just push the whie button on the gray box that's connected to the temp probe Infront of the chilled water coil. It will probably trip a few times because as soon as it resets the preheat valve will close to go back to set point, cold air rushes in and puts the probe under 38 degrees, trips, repeats. You can drop the OA damper (bypass the end switch on the OA damper temporarily) then open the OA slowly and let the preheat catch back up (man I really don't make enough). Better then 90% this is your issue 😊
@andrewshock8703
@andrewshock8703 5 ай бұрын
P.s., the fire trip is in series so it would show as dead. These are crazy tricky systems and you really do a great job!
@douro20
@douro20 4 ай бұрын
What kind of chiller is it connected to? The drive is an ABB one...they probably took it out because it was giving them too much trouble...either that or it just died and they didn't bother to replace it.
@Andres-zm4tu
@Andres-zm4tu 12 күн бұрын
Hi Jumper Man I have a question, the FCU need Outside air? Thank you for your help.
@zack9912000
@zack9912000 5 ай бұрын
I would wash my hand of that location
@JumpermanTech
@JumpermanTech 5 ай бұрын
I wash my hands then go right back for more. Many service calls and they pay their bills. Huge accumulation of work for the years or neglect and messy work lol thanks for watching & stay tuned for new videos every week! 🔧⚡️
@ILoveKittys78
@ILoveKittys78 5 ай бұрын
😻💚💜💚
@JumpermanTech
@JumpermanTech 5 ай бұрын
💜🔧⚡️
@alphabears6342
@alphabears6342 5 ай бұрын
We fix the leaks at my work as soon as it’s not busy.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Nice. As soon as it's not so cold out, they will attempt to shut the water down. They tried before but some valves weren't holding so we couldn't make the repair. At this point, it's really bad. Thanks for watching! 🔧⚡️
@James-zm6qf
@James-zm6qf 4 ай бұрын
Soooo did you ever fix the wire that made a clicking noise when you moved it?
@STONEDay
@STONEDay 5 ай бұрын
FlexTape and run.
@JumpermanTech
@JumpermanTech 5 ай бұрын
And never come back 😂
@roboo8460
@roboo8460 4 ай бұрын
I dint think you won the game lol too much time left on the clock 😂
@brians9875
@brians9875 5 ай бұрын
Please tell me this wasn’t a local 68 site lol
@JumpermanTech
@JumpermanTech 5 ай бұрын
Definitely not 😂 Let's the service calls keep on callin' 👍 Thanks for watching! 🔧⚡️
@brians9875
@brians9875 5 ай бұрын
@@JumpermanTech you are the best HVAC page on KZbin!
@JumpermanTech
@JumpermanTech 5 ай бұрын
@brians9875 I really appreciate you saying that! 🙏 I'm trying my best at work and at making videos. Have a great day and be safe 🔧⚡️
@gerardallamano9179
@gerardallamano9179 5 ай бұрын
So actually what was the problem with the unit please elaborate...
@genewheeler6320
@genewheeler6320 5 ай бұрын
Owner not wanting to spend money
@JumpermanTech
@JumpermanTech 5 ай бұрын
A bit of that mixed in with that they tried shutting the water down twice but some valves aren't holding. They will attempt again when the weather isn't so cold as thats the hot water to supply heat for many units. Thanks for watching!
@mjpena53
@mjpena53 5 ай бұрын
So it was a reset.
@JumpermanTech
@JumpermanTech 5 ай бұрын
Yes, reset of the fire alarm panel. They did a test earlier and left all the hvac units off 😂 Thanks for watching & stay tuned for new videos every week🔧⚡️
@mjpena53
@mjpena53 5 ай бұрын
Thanks for keeping it real.
@ghopk3
@ghopk3 5 ай бұрын
🤣
@JumpermanTech
@JumpermanTech 5 ай бұрын
Always running into a unique situation 😂
@genewheeler6320
@genewheeler6320 5 ай бұрын
That is code violation in any book
@JumpermanTech
@JumpermanTech 5 ай бұрын
What exactly is code violation?
ТАМАЕВ УНИЧТОЖИЛ CLS ВЕНГАЛБИ! Конфликт с Ахмедом?!
25:37
Мы никогда не были так напуганы!
00:15
Аришнев
Рет қаралды 6 МЛН
Mr S. teaching HVAC fundamentals.
20:35
Harman House
Рет қаралды 8 М.
HVAC Commercial rooftop package unit Beginners Guide
9:17
Taddy Digest
Рет қаралды 115 М.
Lennox Prodigy Playing Games RTU Not Cooling
23:19
HVACR Survival
Рет қаралды 10 М.
ECM Multi-Speed Blower Motor Troubleshooting!
16:40
AC Service Tech LLC
Рет қаралды 301 М.
Собери ПК и Получи 10,000₽
1:00
build monsters
Рет қаралды 2,6 МЛН