HVAC Hacks Replaced Dead Compressor & Didn't Diagnose Failure - BUT We Did!

  Рет қаралды 11,638

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

Күн бұрын

Пікірлер: 64
@ThePete2432
@ThePete2432 Жыл бұрын
I have an option from way back in my years when I was a resi guy. If it’s not hot as balls out… check standing pressure then valve off condenser… come back in 48 hours and put gauges on… if pressure is same open valves and you’ll know what side of the system it’s on. Just a tip for you resi guys coming from me struggling to pin point frustrating micro leaks before moving up to big mf’ing systems.
@moejoe5935
@moejoe5935 Жыл бұрын
Good looking out
@throttlebottle5906
@throttlebottle5906 Жыл бұрын
don't forget to account for it being frozen/blazing hot, from things like no airflow/bad indoor blower, non-condensable contaminates. the pressures may go up or down in real life. now clearly a huge pressure loss is obviously a leak, while pressure gain could have been from frozen to hot(attic) or bad gasses mixed, but that's harder to judge overall.
@robertsmith2956
@robertsmith2956 Жыл бұрын
Why don't they put valves on the evap side so you can isolate it to remove and clean.
@evidinha12
@evidinha12 Жыл бұрын
I like how you have to touch the ice on the lines to make sure it’s frozen!! 🥶
@kangaroogod
@kangaroogod Жыл бұрын
👍 that sheet is familiar
@patthefireman100
@patthefireman100 Жыл бұрын
Mike , really love the options, so fair and upfront.... you da man
@Eddy63
@Eddy63 Жыл бұрын
Nice troubleshooting as usual ... Thx
@HERITAGEWV
@HERITAGEWV Жыл бұрын
Whipping the UEI around made me think of the old school sling psychrometers! Everyone has to love leak checking!! Every once in a while you might get lucky and get one of the easy leakers … we all know that’s not likely. At times we split the lineset and braze in access ports and put both sides under heavy pressure of nitrogen. And come back to it to check both sides. It’s not the easiest method but it’s helped us find some micron leaks we probably would have never found otherwise. Sometimes micron leaks on both halves of the system. Keep up the good work guys!
@matthewtimm5925
@matthewtimm5925 Жыл бұрын
I'll be interested in that PDF
@DevinHVACInc
@DevinHVACInc Жыл бұрын
Very well handy
@sknight0391
@sknight0391 Жыл бұрын
7:05 I thought Mikey was getting ready to throw out the first pitch at the Mets game. 😎👍😎👍😎👍
@everettstevenson2111
@everettstevenson2111 Жыл бұрын
Hey John, of John Phillips Plumbing. Got your number three wire waiting for you again. Go Navy.
@dadams7211
@dadams7211 Жыл бұрын
So was the high pressure cutoff switch bad?
@wayneguy6043
@wayneguy6043 Жыл бұрын
I can appreciate a guy who can find a leak…
@danyonka3180
@danyonka3180 Жыл бұрын
Enjoy watching your channel! Just started in this field about eight months ago and I’ve been watching your videos every day before work. You are one of those guys that has their doctorate in the AC business. I hope to one day you get there too.
@iwenive3390
@iwenive3390 Жыл бұрын
Please don’t
@jasonwb6884
@jasonwb6884 Жыл бұрын
What did you do with the high pressure switch? Looked brazed on. Leave the switch bypassed or did you put a tee on the exterior liquid line and use an aftermarket pressure switch. I never leave any safety bypassed unless the customer signs a waiver, and i absolutely never leave a furnace limit switch or roll out switch bypassed under any conditions for obvious safety reasons, even if its after hours and I need to open a shop and pay after hours fee. Its either replace the furance limit or no heat for customer on furnace.
@wayneguy6043
@wayneguy6043 Жыл бұрын
Why not just replace the switch if it’s malfunctioning, makes sense to me
@gallowaylights
@gallowaylights Жыл бұрын
00:04:32 do they have a battery door issue. I See duct tape on measuring device!
@Jon-hx7pe
@Jon-hx7pe Жыл бұрын
only thing i know of that could cause a liquid line to freeze is a restriction.
@Keith_Mikell
@Keith_Mikell Жыл бұрын
The other tech could not think like a schematic. So they just replaced the condenser. Excellent work.
@Keith_Mikell
@Keith_Mikell Жыл бұрын
@@PipeDoctor Thank you for the nice comment.
@LONGE123
@LONGE123 Жыл бұрын
Would replace the liquid line dryer inside the condensing unit The Ice on the liquid line might be from a restriction
@jimreilly917
@jimreilly917 Жыл бұрын
If ya ain't testing...you're guessing.
@enriquecalderon4356
@enriquecalderon4356 Жыл бұрын
Love your videos, why did You go to the small vans
@PipeDoctor
@PipeDoctor Жыл бұрын
Only I drive the small one.
@amigo2k10
@amigo2k10 Жыл бұрын
Mike i finally seen you on sunrise highway when i was going to work I'm not even going to lie it was like an oh shit moment and then i seen the truck later after work i hope one day to shake your hand I'm in the auto trade myself
@Swoliosis1
@Swoliosis1 Жыл бұрын
What's the success rate on the sealant?
@AustinAirCo
@AustinAirCo Жыл бұрын
@@PipeDoctor the next slow leaker you get to replace keep the coil and pump it with leak sealer conduct a not so science type experiment. It might be eye opening. If the sealer is good enough it should seal the leaks even though the coil is separated from the system. Place the coil so the sealer will run to those areas of the coil taking. If you use dye based sealer you'll know where those leaks are. If one brand of sealer doesn't work use another until success, time lapse video should be interesting. I've used 2 in field and in this kind of test. *both failed*
@spaceboy7192
@spaceboy7192 Жыл бұрын
Mikey..lm thinking you have a restricted or a kink in the liquid line somewhere. Liquid lines don't ice for no reason. Micro channel coil won't store refrigerant like a copper coil will. Just my thoughts..
@Keith_Mikell
@Keith_Mikell Жыл бұрын
Clogged dryer if equipped also?
@throttlebottle5906
@throttlebottle5906 Жыл бұрын
"it's a real piece of York", Love Steve Lav. like a big brother, even though he/many blocked/ignore comments(they still seem to read some). OK by me 😉 some may help, other may be random gibberish. 🥳
@everettstevenson2111
@everettstevenson2111 Жыл бұрын
Hey Mickey, of Mickey Pipes Plumbing not easy being cheesy. I like your podcast/social media. I guess some of your customers still checking up on you. By the way, Mickey, C-Span 1, 2, 3 it is still hanging low. When you want it again, let me know. What are you talking about biscuit. Love you buddy,jolly good show old boy, God save the King.
@martinleonard1566
@martinleonard1566 Жыл бұрын
I always learn watching your video great gluon mike. How do I e mail to get a sticker or those 5 things ?
@racegrubb2152
@racegrubb2152 Жыл бұрын
Yeah some leaks you can find in a hour but there are plenty of times it takes a lot longer for sure. Leak searches suck lol
@jasontexter1721
@jasontexter1721 Жыл бұрын
Almost looks like plugged up filter dryer or someone didn't open the.h high side service valve all the way
@jasontexter1721
@jasontexter1721 Жыл бұрын
@@PipeDoctor may have been what blew the pressure switch to begin with, or a semi closed service valve. if they had actual discharge ports to could see what your discharge pressure is not liquid line pressure. Ive never seen a liquid line freeze up like that from low charge, at least not when it has enough freon to freeze all the way back to the compressor. If they had a bad burnout I wouldn't be surprised if there's wax/winding material stuck in a semi kinked line or even the manifolds on the micro channel 🤷‍♂️ I've seen 5/16 and 3/8 lines on small 134a system condensors get shellac buildup plugging them from a small piece of braze that buildup and snagged pieces until it completed plugged. Freon pressures will look half decent but your discharge is 200+ degrees and keeps tripping internal overload and if they had a discharge pressure sensor it would trip/weaken it. I work on every kind of commercial and residential equipment around. I've never seen a high pressure switch trip THAT low unless a fan motor failed or a restriction occured. And Ive seen several 20+ year old high pressure peanut switches still working fine as long as the nahcineb
@SuperCano1997
@SuperCano1997 Жыл бұрын
Can I have the PDF ?
@scottvolage1752
@scottvolage1752 Жыл бұрын
Another well diagnosed and well-done job Mike. Hacks bringing you stacks. Make the trades great again. #LoveBosch #LetsGoBosch
@Austin23191
@Austin23191 Жыл бұрын
Mike I have a question for ya. I have a 3.5 ton AC (oversized a half ton) with a gas furnace. The thermostat is a visionpro8000. The ac normally runs for about 5 minutes before turning off resulting in poor dehumidification. Would adding a delay on make timer in the condenser help increase run times? I already set the ac cycle rate to 1 but that didn't change anything.
@hughholt121
@hughholt121 Жыл бұрын
Add some outside air to the return.
@z06rcr
@z06rcr Жыл бұрын
Lower blower speed from Hi to medium Hi…
@steveoh9838
@steveoh9838 Жыл бұрын
Have the static pressure tested, probably to high. The system has to breathe. Oversized unit doesn't help. High velocity overcools too quickly with low dehumidification.
@gtpforever
@gtpforever Жыл бұрын
Could always go outside the box and get a humidity sensor installed and a stat that can run on dehumidification to run until your desired humidity but your house will be like a meat locker. 😂🤣😂🤣
@Yodaddynyomama
@Yodaddynyomama Жыл бұрын
im subscribed shheessshhh stop yelling at me, good job! looks like that unit needs therapy
@ItsTheCostanza
@ItsTheCostanza Жыл бұрын
More stacks
@xlostf8x348
@xlostf8x348 Жыл бұрын
I'll take that challenge. I can find a leak in under an hour.
@رافدرائع
@رافدرائع Жыл бұрын
Compressor does not compress gas only works without pressure
@joshsegg2814
@joshsegg2814 Жыл бұрын
78.1 =79 mikey pipes 23'
@dailytricks6161
@dailytricks6161 Жыл бұрын
Great job, I've been watching your videos a lot and looking forward to your visit to my house, I'll invite you for a beer!😆😁😍
@dailytricks6161
@dailytricks6161 Жыл бұрын
@@PipeDoctor Should we have a party, sir?
@benf7259
@benf7259 Жыл бұрын
Looks like Man Baby got removed from his apprentice position. Or, he is still sleeping 18 hours a day. No Bueno.
@benf7259
@benf7259 Жыл бұрын
@@PipeDoctor The Shabbos nap that lasts all week….Rinse and repeat.
@throttlebottle5906
@throttlebottle5906 Жыл бұрын
by 2:21 I am howling like an pack of banshee's 🤡 frozen liquid line, gas gas blow it out your, uh-oh what gas? **edit, those two "TINY" returns on a 5 ton system? 😏😏😏😏😏
@heatpump8566
@heatpump8566 Жыл бұрын
I would never just add refrigerant, it’s putting a plaster on a gun shot. Amateurs
@kat2641
@kat2641 Жыл бұрын
Hay your doing what I do … if you don’t do A this can happen if you do B or C your poring money down the drain or D ! But the bullet and forget your problems for a few years.. wealthy people is replace it middle is can we bandaid it?? An the poor?? We really need it but can’t afford it….😢😢 some times?? I take it in the booty an help them out an?? Sometimes it works in my favor an many times? I get Fk’ed 🤷🏻‍♂️ life is chances an rolling the dice.. but them was some nasty filters…. But great job on SC
@wayneguy6043
@wayneguy6043 Жыл бұрын
Looks like someone’s needs a duster and a wet rag and some motivation to clean…..
@repairmonkeyservicegroup8795
@repairmonkeyservicegroup8795 Жыл бұрын
"I can find a leak and fix it in an hour" I've heard that a lot and they never can prove it, just talk at that point.
@kens.3729
@kens.3729 Жыл бұрын
“If You’re Not Testing, You’re Guessing” 🤪👎 Only a Hack and a Dumb Jack 🤪 would Replace a Compressor without Confirming the Compressor was Bad🤪👎
@bryanharayda1975
@bryanharayda1975 Жыл бұрын
The title of this video is very misleading, you didn’t properly diagnose the unit and having a PDF of options when the system is low on gas doesn’t make anything official. Did you ever think that maybe the filter drier is partially blocked? That would cause it to freeze up, not to mention the high pressure switch is in the discharge line, before the drier and before where you hook up the high side gauges! Wow, it’s almost as if the system looks low on gas at the high side and low side service ports because of a restriction before those points! And you called the previous techs hacks! Did you even see the drier? Did you even try to do a temp drop reading across it? Do you realize that to someone who does this for a living you look like a hack? By the way, I’m just a sales rep for a clothing chain, what do I know?
@bryanharayda1975
@bryanharayda1975 Жыл бұрын
@@PipeDoctor good point, congrats on the following, I’m subscribed and am looking forward to more of your videos!
@DCHVAC
@DCHVAC Жыл бұрын
First
“We Found The Filter!” Central A/C System Not Cooling & Frozen Solid
13:56
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 7 М.
Another HVAC Contractor Condemned AC System We Brought Back to Life!
23:23
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 39 М.
小丑教训坏蛋 #小丑 #天使 #shorts
00:49
好人小丑
Рет қаралды 54 МЛН
Quando A Diferença De Altura É Muito Grande 😲😂
00:12
Mari Maria
Рет қаралды 45 МЛН
UFC 310 : Рахмонов VS Мачадо Гэрри
05:00
Setanta Sports UFC
Рет қаралды 1,2 МЛН
Failed Compressors - Don't JUST REPLACE IT
24:59
HVAC School
Рет қаралды 69 М.
Is He Ready? Peter Running 1st Central AC Service Call - No Cooling on 3rd Floor
9:16
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 21 М.
How To Diagnose A BAD Compressor | HVAC Troubleshooting
9:46
Quality HVACR
Рет қаралды 199 М.
Step by Step Guide: How to Locate and Repair Refrigerant Leak on Heat Pump Outdoor Unit
31:13
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 13 М.
Proper Techniques When Replacing Central AC Equipment Explained
20:08
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 9 М.
York Heat Pump Not Cooling. #hvacguy #hvaclife
29:20
HVAC GUY
Рет қаралды 20 М.
Absolutely Most Disgusting HVAC System Encountered & Refurbished in Half Day Full Cleaning
24:46
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 20 М.
Home A/C Compressor Not Running - Fixed
13:59
stuzman
Рет қаралды 411 М.
How to Leak Test an AC With Nitrogen Pressure
8:00
HVAC School
Рет қаралды 244 М.
Tenant Keeps Complaining About No Heat - Landlord Says "Fix It Regardless of Cost!"
22:18
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 162 М.