HVAC Service Call: Smoke in Store.

  Рет қаралды 7,354

HughesMan HVAC

HughesMan HVAC

Күн бұрын

Пікірлер
@jamienoel
@jamienoel 11 ай бұрын
I don't usually rag on other companies, but this is an exception and there's no excuse for it. I'd make it known in the write-up that the previous company bypassed the safety.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
I mentioned it for sure
@topher8634
@topher8634 11 ай бұрын
Good thing you got video. Something tells me that there will be more to this. Like who worked on it previously.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
I think so too, thanks for watching
@BillDerby-c2o
@BillDerby-c2o 11 ай бұрын
This customer probably didn't call a different company today...
@jrh86
@jrh86 11 ай бұрын
I've never seen an upside down limit switch before 😂 barking mad ! Immediately dangerous.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Definitely 👍
@Georges3DPrinters
@Georges3DPrinters 4 ай бұрын
Omg this was a close call! 😮 this was a good one! No air flow and no limit means it's an oven 😂
@HughesManHVAC
@HughesManHVAC 4 ай бұрын
Thanks for watching!
@subcoolHVAC
@subcoolHVAC 11 ай бұрын
Good job Ryan, need to issue a BOLO for the Hack installer and the vandal who worked on those units.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@BartlettTFD
@BartlettTFD 11 ай бұрын
I think it might be necessary to have the owner pull the service history on this unit. The company that performed this “work” needs to be held accountable for it. Some city inspector’s office should be notified if appropriate. That company should be fined and told that further violations will cause them to lose their business license. This is really a dangerous situation.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Extremely dangerous, totally agree 👍
@jasonjohnsonHVAC
@jasonjohnsonHVAC 11 ай бұрын
Good lord....safeties is 100% non negotiable for bypassing....i dont care how cold it is...never gonna happen....that is a disaster waiting to happen.....nice job Ryan
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Thanks Jason, thanks for watching man!
@jochemsluis8834
@jochemsluis8834 11 ай бұрын
Great job Ryan. You should never bypass any safety device unless for testing purposes. Leaving it bypassed leaves you with a whole hell of hurt. Safety is paramount and if it works is secondary.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@timothymcmahon1507
@timothymcmahon1507 11 ай бұрын
That’s just the new wireless limit switch
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
😆
@topher8634
@topher8634 11 ай бұрын
Might want to see if a wiring harness is available. If not, I'd say they need to replace it. I mean blower motor, possible heat exchanger failure, wiring damage and limits, that's half the unit.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Yeah, I submitted my report and will see what happens.
@gregbowman3598
@gregbowman3598 11 ай бұрын
Good one Ryan
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Thanks Greg
@timmorrison4107
@timmorrison4107 11 ай бұрын
You could have cooked Thanksgiving dinner in that oven, wow everything needs reworked ,I’m surprised that drain pan didn’t melt away, I say new unit is an excellent option.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
🍗
@MikeB9771
@MikeB9771 11 ай бұрын
That unit has been hacked in every bad way, lucky the building didnt burn down. Total hackery.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Agree 100%
@HVACGUY
@HVACGUY 11 ай бұрын
Dang. That was dangerous
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Yes
@ChingusTheOneAndOnly
@ChingusTheOneAndOnly 11 ай бұрын
What a find !
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@nastyhvacr
@nastyhvacr 11 ай бұрын
Good find! Last guy out has got some splaining to do.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Thanks for watching pat
@jani140
@jani140 10 ай бұрын
Please change all those wires. If they got that hot and not yet short, the plastics get very brital and isolation on "still good" wires will flake off soon.
@HughesManHVAC
@HughesManHVAC 10 ай бұрын
We quoted a new wiring harness
@zack9912000
@zack9912000 11 ай бұрын
We always drill holes on the outside of the economizer, with no reason to run the wires like that. Much less bypassing limits
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Yep
@oscalerup1129
@oscalerup1129 10 ай бұрын
That’s crazy, I had one job once we came behind the people that installed it, the one 3T RTU had a main limit bypass with a lil popper 😅. One other 10T had a hole in the condenser from a screw when they put on the hail guards. And they left the manual on top of the burners so when it fired it burned all of the wiring in that compartment
@REWYRED
@REWYRED 11 ай бұрын
Hmmm... cooked motor, possible comprmised exchanger, comprimised wiring, comprimised condensate pan...... The entire thing baked itself.. If that was my unit it would be getting replaced and i would be going after whoever jumped the limit for replacement value plus.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Studentofhvac
@Studentofhvac 11 ай бұрын
Excellent. Interesting.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Many thanks!
@fshn76
@fshn76 11 ай бұрын
Good stuff Ryan. Just dealt with a unit that caught fire because someone had bypassed safeties all I had to do was go take pictures, total loss.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@timmohney9737
@timmohney9737 10 ай бұрын
Scary that there are people out there that do stuff like this.
@HughesManHVAC
@HughesManHVAC 10 ай бұрын
Yep 👍
@MrJujubean
@MrJujubean 10 ай бұрын
Wow! I do not know how anyone could think it was a good idea to bypass a limit or any other safety.
@jenna_1221
@jenna_1221 11 ай бұрын
Wow. Can’t believe people sometimes 🤦🏼‍♀️
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@adamdnewman
@adamdnewman 11 ай бұрын
Surprised if any of the wires in the blower area are good insulation wise
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Probably not, they were hard and brittle.
@Brutis-1983
@Brutis-1983 11 ай бұрын
Looks like what we call Chuck in a Truck was there. Is was a service tech that trained when I started would call them. Plus filter change in December and did not cut the heat off. SMH . Good luck with that unit.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Farley445
@Farley445 11 ай бұрын
Bring back the melted filters to your shop and show your guys
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@danpresson
@danpresson 11 ай бұрын
Great job Ryan you are so thorough
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
I appreciate that!
@10minutenewhampshirebreak77
@10minutenewhampshirebreak77 11 ай бұрын
Some tech, somewhere has some explaining to do!
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Zackrutledge1998
@Zackrutledge1998 11 ай бұрын
Nice work man. Good video👍🏻 You ever see anything like that before? I never have.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
I have not, thanks for watching
@brianliles4859
@brianliles4859 11 ай бұрын
Need to replace the unit
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@stevencossaboon3237
@stevencossaboon3237 11 ай бұрын
Nice work Ryan.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Thanks!
@Paul-IE-Repairs
@Paul-IE-Repairs 11 ай бұрын
i would replace the wire, that insulation is compromised, the way it was creaking and cracking it exceeded its rating, 90C is 194F and a new insulation pad.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
I agree, I’ve filled out my report and also have the video. Appreciate the input, thanks!🙏
@vincentmcclelland9179
@vincentmcclelland9179 11 ай бұрын
I wonder if the whole unit needs to be condemned and replaced
@BryanGullickson
@BryanGullickson 11 ай бұрын
i know i would as it would be cheaper to replace than sit there and rewire and replace 90%of the unit
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@qomco
@qomco 11 ай бұрын
Thats why you dont bypass safeties...
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Exactly 👍
@nonamesplease8228
@nonamesplease8228 11 ай бұрын
Who in the heck would bypass a safety. Then walk away and say "it will be alright", No excuse
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@ryanisaacson118
@ryanisaacson118 11 ай бұрын
That ac you looked at with the plug pulled looked like a single circut system
@Farley445
@Farley445 11 ай бұрын
Start for fire burning smell on the wires check in see if there all connected you can’t not let the customer turn on the unit for safety reasons
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@acrservicesmathewr7565
@acrservicesmathewr7565 11 ай бұрын
What’s your opinion on the plastic pulleys on VFDs? Have been bypassing vfds due to unavailability and after bypassing we change the pulleys to steel since bypassing gives to much torque on startup and blows them apart. All this nonsense just to meet efficiency standards. Carrier going downhill
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Not a fan of the plastic pulleys either
@zekenzy6486
@zekenzy6486 11 ай бұрын
Great Video. Thank you for sharing. May I ask, what is the same and different between roll out switch and high limit switch ?
@mitchell8204
@mitchell8204 10 ай бұрын
Roll out switches are typically manual reset so they have a little button you need to push if it trips otherwise it will not close again by itself. High limits on the other hand tend to be automatic reset because they can be tripped by dirty filters, low airflow, etc but they will automatically reset and the unit will light back up. They should not trip during normal operation with clean filters, so if a unit is cycling on limit (running until it hits high limit then shuts off then lights up when limit recloses) there is usually a problem to fix somewhere.
@MariosACandRefrigeration
@MariosACandRefrigeration 11 ай бұрын
2:00 no wires at the limit ?
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Yes someone bypassed it
@joecorbin5158
@joecorbin5158 11 ай бұрын
Wowser….😳😳😳🔥
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@MariosACandRefrigeration
@MariosACandRefrigeration 11 ай бұрын
I would be surprised ,if you do not have that limit in your van.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Me too
@aa999xyz
@aa999xyz 11 ай бұрын
that is crazy!
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Thanks for watching
@ryanmarlatt5726
@ryanmarlatt5726 11 ай бұрын
Those machines have fixed orifices. Pick yourself up a mini Guage so your not bringing up a whole hose.
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
These units have txv’s
@roqueherrera8471
@roqueherrera8471 10 ай бұрын
Where u located?
@hvacblogger
@hvacblogger 11 ай бұрын
What did it smell like? 😆
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
😂
@mmorrison6775
@mmorrison6775 11 ай бұрын
one question Why didnt the duct smoke shut down the ac?
@BryanGullickson
@BryanGullickson 11 ай бұрын
well if the disabled safety is any indication i'd have to assume either bypassed or not equipped also that fire department needs to go back to training as it took them 3 times of coming out to shut the unit down
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
It may have, the alarm company and fire department were both there before me and it was shut off by the time I showed up.
@jonathanhensel8929
@jonathanhensel8929 11 ай бұрын
That return smoke detector sampling tube is backwards.
@bryann2633
@bryann2633 7 ай бұрын
I think it got hot
@HughesManHVAC
@HughesManHVAC 6 ай бұрын
Me too, this unit has since been replaced
@Randylazz
@Randylazz 11 ай бұрын
What are the chances that the person who did all that managery is watching this video……..
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
🙏
@steveblake8766
@steveblake8766 11 ай бұрын
121 thumbs uP
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Farley445
@Farley445 11 ай бұрын
Owes inspect the job
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Kevin-wj4ed
@Kevin-wj4ed 7 ай бұрын
Replace the unit!!!!!!!!!
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
We did
@ThunderPantz01
@ThunderPantz01 5 ай бұрын
Replace the whole unit. it can't be trusted after that.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Agreed! This unit has already been replaced. Thanks for watching!
@Farley445
@Farley445 11 ай бұрын
Them Raheem is much better
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Farley445
@Farley445 11 ай бұрын
Are group will do the job and take off and not do the job the right way
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
👍
@Eddy63
@Eddy63 11 ай бұрын
Nice vid ... Thx
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
Thanks Eddy!
@ValDominator
@ValDominator 11 ай бұрын
i feel patronized
@HughesManHVAC
@HughesManHVAC 11 ай бұрын
?
HVAC Service Call: Tripped Smoke Detector
25:35
HughesMan HVAC
Рет қаралды 4,3 М.
Service Call: Following another company!
35:09
HughesMan HVAC
Рет қаралды 39 М.
I'VE MADE A CUTE FLYING LOLLIPOP FOR MY KID #SHORTS
0:48
A Plus School
Рет қаралды 20 МЛН
«Жат бауыр» телехикаясы І 30 - бөлім | Соңғы бөлім
52:59
Qazaqstan TV / Қазақстан Ұлттық Арнасы
Рет қаралды 340 М.
УЛИЧНЫЕ МУЗЫКАНТЫ В СОЧИ 🤘🏻
0:33
РОК ЗАВОД
Рет қаралды 7 МЛН
Another Carrier Gas Furnace Failed heat exchanger
17:13
Anti DIY HVAC
Рет қаралды 48 М.
How To Replace Your HVAC System And Save THOUSANDS.
31:14
The DIY HVAC Guy
Рет қаралды 266 М.
HVAC/Refrigeration Service Technician Van Setup 2024
46:01
Midwest HVACR Technician
Рет қаралды 3,1 М.
The AC isn't working! Multiple Issues Found
30:24
HughesMan HVAC
Рет қаралды 5 М.
Stripped out Threads on Gas valve
19:07
HughesMan HVAC
Рет қаралды 1,6 М.
All About Telephone Power Plants
30:32
Connections Museum
Рет қаралды 77 М.
TXV Replacement on Ruud Air Handler! #hvacguy #hvaclife
45:48
THE DINING AC IS NOT WORKING
33:05
HVACR VIDEOS
Рет қаралды 108 М.
1st No Heat Service Call of the Season
20:26
HughesMan HVAC
Рет қаралды 13 М.
THE SYMPTOMS KEPT COMING
22:56
HVACR VIDEOS
Рет қаралды 60 М.