No video

HVAC Service Call: Smoke in Store.

  Рет қаралды 6,514

HughesMan HVAC

HughesMan HVAC

Күн бұрын

HVAC Service Call: Smoke in Store. This situation could have ended badly!
Hit me up at hughesmanhvac@gmail.com
Check out the Misfits of HVAC Podcast
/ @misfitsofhvac
misfitsofhvac@gmail.com

Пікірлер: 122
@jamienoel
@jamienoel 7 ай бұрын
I don't usually rag on other companies, but this is an exception and there's no excuse for it. I'd make it known in the write-up that the previous company bypassed the safety.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
I mentioned it for sure
@BartlettTFD
@BartlettTFD 7 ай бұрын
I think it might be necessary to have the owner pull the service history on this unit. The company that performed this “work” needs to be held accountable for it. Some city inspector’s office should be notified if appropriate. That company should be fined and told that further violations will cause them to lose their business license. This is really a dangerous situation.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Extremely dangerous, totally agree 👍
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
Good lord....safeties is 100% non negotiable for bypassing....i dont care how cold it is...never gonna happen....that is a disaster waiting to happen.....nice job Ryan
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Thanks Jason, thanks for watching man!
@MikeB9771
@MikeB9771 7 ай бұрын
That unit has been hacked in every bad way, lucky the building didnt burn down. Total hackery.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Agree 100%
@Georges3DPrinters
@Georges3DPrinters 3 күн бұрын
Omg this was a close call! 😮 this was a good one! No air flow and no limit means it's an oven 😂
@HughesManHVAC
@HughesManHVAC 2 күн бұрын
Thanks for watching!
@jrh86
@jrh86 7 ай бұрын
I've never seen an upside down limit switch before 😂 barking mad ! Immediately dangerous.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Definitely 👍
@subcoolHVAC
@subcoolHVAC 7 ай бұрын
Good job Ryan, need to issue a BOLO for the Hack installer and the vandal who worked on those units.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@nonamesplease8228
@nonamesplease8228 7 ай бұрын
Who in the heck would bypass a safety. Then walk away and say "it will be alright", No excuse
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@topher8634
@topher8634 7 ай бұрын
Might want to see if a wiring harness is available. If not, I'd say they need to replace it. I mean blower motor, possible heat exchanger failure, wiring damage and limits, that's half the unit.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Yeah, I submitted my report and will see what happens.
@HVACGUY
@HVACGUY 7 ай бұрын
Dang. That was dangerous
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Yes
@topher8634
@topher8634 7 ай бұрын
Good thing you got video. Something tells me that there will be more to this. Like who worked on it previously.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
I think so too, thanks for watching
@user-qd3pi5ji7q
@user-qd3pi5ji7q 7 ай бұрын
This customer probably didn't call a different company today...
@timmohney9737
@timmohney9737 6 ай бұрын
Scary that there are people out there that do stuff like this.
@HughesManHVAC
@HughesManHVAC 6 ай бұрын
Yep 👍
@MrJujubean
@MrJujubean 6 ай бұрын
Wow! I do not know how anyone could think it was a good idea to bypass a limit or any other safety.
@timothymcmahon1507
@timothymcmahon1507 7 ай бұрын
That’s just the new wireless limit switch
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
😆
@oscalerup1129
@oscalerup1129 6 ай бұрын
That’s crazy, I had one job once we came behind the people that installed it, the one 3T RTU had a main limit bypass with a lil popper 😅. One other 10T had a hole in the condenser from a screw when they put on the hail guards. And they left the manual on top of the burners so when it fired it burned all of the wiring in that compartment
@REWYRED
@REWYRED 7 ай бұрын
Hmmm... cooked motor, possible comprmised exchanger, comprimised wiring, comprimised condensate pan...... The entire thing baked itself.. If that was my unit it would be getting replaced and i would be going after whoever jumped the limit for replacement value plus.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@zack9912000
@zack9912000 7 ай бұрын
We always drill holes on the outside of the economizer, with no reason to run the wires like that. Much less bypassing limits
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Yep
@jani140
@jani140 7 ай бұрын
Please change all those wires. If they got that hot and not yet short, the plastics get very brital and isolation on "still good" wires will flake off soon.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
We quoted a new wiring harness
@timmorrison4107
@timmorrison4107 7 ай бұрын
You could have cooked Thanksgiving dinner in that oven, wow everything needs reworked ,I’m surprised that drain pan didn’t melt away, I say new unit is an excellent option.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
🍗
@gregbowman3598
@gregbowman3598 7 ай бұрын
Good one Ryan
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Thanks Greg
@Farley445
@Farley445 7 ай бұрын
Bring back the melted filters to your shop and show your guys
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@jochemsluis8834
@jochemsluis8834 7 ай бұрын
Great job Ryan. You should never bypass any safety device unless for testing purposes. Leaving it bypassed leaves you with a whole hell of hurt. Safety is paramount and if it works is secondary.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@Paul-IE-Repairs
@Paul-IE-Repairs 7 ай бұрын
i would replace the wire, that insulation is compromised, the way it was creaking and cracking it exceeded its rating, 90C is 194F and a new insulation pad.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
I agree, I’ve filled out my report and also have the video. Appreciate the input, thanks!🙏
@jenna_1221
@jenna_1221 7 ай бұрын
Wow. Can’t believe people sometimes 🤦🏼‍♀️
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@adamdnewman
@adamdnewman 7 ай бұрын
Surprised if any of the wires in the blower area are good insulation wise
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Probably not, they were hard and brittle.
@ChingusTheOneAndOnly
@ChingusTheOneAndOnly 7 ай бұрын
What a find !
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@nastyhvacr
@nastyhvacr 7 ай бұрын
Good find! Last guy out has got some splaining to do.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Thanks for watching pat
@10minutenewhampshirebreak77
@10minutenewhampshirebreak77 7 ай бұрын
Some tech, somewhere has some explaining to do!
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@Studentofhvac
@Studentofhvac 7 ай бұрын
Excellent. Interesting.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Many thanks!
@vincentmcclelland9179
@vincentmcclelland9179 7 ай бұрын
I wonder if the whole unit needs to be condemned and replaced
@BryanGullickson
@BryanGullickson 7 ай бұрын
i know i would as it would be cheaper to replace than sit there and rewire and replace 90%of the unit
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@qomco
@qomco 7 ай бұрын
Thats why you dont bypass safeties...
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Exactly 👍
@brianliles4859
@brianliles4859 7 ай бұрын
Need to replace the unit
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@fshn76
@fshn76 7 ай бұрын
Good stuff Ryan. Just dealt with a unit that caught fire because someone had bypassed safeties all I had to do was go take pictures, total loss.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@danpresson
@danpresson 7 ай бұрын
Great job Ryan you are so thorough
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
I appreciate that!
@joecorbin5158
@joecorbin5158 7 ай бұрын
Wowser….😳😳😳🔥
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@Brutis-1983
@Brutis-1983 7 ай бұрын
Looks like what we call Chuck in a Truck was there. Is was a service tech that trained when I started would call them. Plus filter change in December and did not cut the heat off. SMH . Good luck with that unit.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@Zackrutledge1998
@Zackrutledge1998 7 ай бұрын
Nice work man. Good video👍🏻 You ever see anything like that before? I never have.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
I have not, thanks for watching
@zekenzy6486
@zekenzy6486 7 ай бұрын
Great Video. Thank you for sharing. May I ask, what is the same and different between roll out switch and high limit switch ?
@mitchell8204
@mitchell8204 7 ай бұрын
Roll out switches are typically manual reset so they have a little button you need to push if it trips otherwise it will not close again by itself. High limits on the other hand tend to be automatic reset because they can be tripped by dirty filters, low airflow, etc but they will automatically reset and the unit will light back up. They should not trip during normal operation with clean filters, so if a unit is cycling on limit (running until it hits high limit then shuts off then lights up when limit recloses) there is usually a problem to fix somewhere.
@acrservicesmathewr7565
@acrservicesmathewr7565 7 ай бұрын
What’s your opinion on the plastic pulleys on VFDs? Have been bypassing vfds due to unavailability and after bypassing we change the pulleys to steel since bypassing gives to much torque on startup and blows them apart. All this nonsense just to meet efficiency standards. Carrier going downhill
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Not a fan of the plastic pulleys either
@Randylazz
@Randylazz 7 ай бұрын
What are the chances that the person who did all that managery is watching this video……..
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
🙏
@ryanisaacson118
@ryanisaacson118 7 ай бұрын
That ac you looked at with the plug pulled looked like a single circut system
@stevencossaboon3237
@stevencossaboon3237 7 ай бұрын
Nice work Ryan.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Thanks!
@Farley445
@Farley445 7 ай бұрын
Start for fire burning smell on the wires check in see if there all connected you can’t not let the customer turn on the unit for safety reasons
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@steveblake8766
@steveblake8766 7 ай бұрын
121 thumbs uP
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@ryanmarlatt5726
@ryanmarlatt5726 7 ай бұрын
Those machines have fixed orifices. Pick yourself up a mini Guage so your not bringing up a whole hose.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
These units have txv’s
@MariosACandRefrigeration
@MariosACandRefrigeration 7 ай бұрын
I would be surprised ,if you do not have that limit in your van.
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Me too
@bryann2633
@bryann2633 3 ай бұрын
I think it got hot
@HughesManHVAC
@HughesManHVAC 3 ай бұрын
Me too, this unit has since been replaced
@ThunderPantz01
@ThunderPantz01 Ай бұрын
Replace the whole unit. it can't be trusted after that.
@HughesManHVAC
@HughesManHVAC Ай бұрын
Agreed! This unit has already been replaced. Thanks for watching!
@MariosACandRefrigeration
@MariosACandRefrigeration 7 ай бұрын
2:00 no wires at the limit ?
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Yes someone bypassed it
@hvacblogger
@hvacblogger 7 ай бұрын
What did it smell like? 😆
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
😂
@Farley445
@Farley445 7 ай бұрын
Owes inspect the job
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@Kevin-wj4ed
@Kevin-wj4ed 3 ай бұрын
Replace the unit!!!!!!!!!
@HughesManHVAC
@HughesManHVAC 3 ай бұрын
We did
@roqueherrera8471
@roqueherrera8471 6 ай бұрын
Where u located?
@mmorrison6775
@mmorrison6775 7 ай бұрын
one question Why didnt the duct smoke shut down the ac?
@BryanGullickson
@BryanGullickson 7 ай бұрын
well if the disabled safety is any indication i'd have to assume either bypassed or not equipped also that fire department needs to go back to training as it took them 3 times of coming out to shut the unit down
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
It may have, the alarm company and fire department were both there before me and it was shut off by the time I showed up.
@jonathanhensel8929
@jonathanhensel8929 7 ай бұрын
That return smoke detector sampling tube is backwards.
@Farley445
@Farley445 7 ай бұрын
Them Raheem is much better
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@user-hi4sh9um7x
@user-hi4sh9um7x 6 ай бұрын
Hi sir I am AC technician I need job u r have job i have experience 15 Saudi Arabia package unit your career train
@Farley445
@Farley445 7 ай бұрын
Are group will do the job and take off and not do the job the right way
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
👍
@aa999xyz
@aa999xyz 7 ай бұрын
that is crazy!
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Thanks for watching
@Eddy63
@Eddy63 7 ай бұрын
Nice vid ... Thx
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
Thanks Eddy!
@ValDominator
@ValDominator 7 ай бұрын
i feel patronized
@HughesManHVAC
@HughesManHVAC 7 ай бұрын
?
HVAC Service Call: Tripped Smoke Detector
25:35
HughesMan HVAC
Рет қаралды 3,2 М.
Simple Mistake Generates HVAC Service Call
7:08
HughesMan HVAC
Рет қаралды 9 М.
SCHOOLBOY. Последняя часть🤓
00:15
⚡️КАН АНДРЕЙ⚡️
Рет қаралды 16 МЛН
هذه الحلوى قد تقتلني 😱🍬
00:22
Cool Tool SHORTS Arabic
Рет қаралды 91 МЛН
Commercial HVAC Preventative Maintenance
16:34
HughesMan HVAC
Рет қаралды 26 М.
WOW!!! I saved $900 by trying this first
13:28
Do-n-Stuff
Рет қаралды 2,6 М.
No AC Service Call: Seagulls Attack!!
24:47
HughesMan HVAC
Рет қаралды 1,7 М.
2 Bad Compressors In Weeks WHY? Freezer Down
29:40
HVACR Survival
Рет қаралды 19 М.
Limit Bypassed and The Blower Stopped! #hvacguy #hvaclife
19:29
Unit Still Has The Original 1978 TXV
19:32
Nor-Cal Refrigeration & H.V.A.C
Рет қаралды 7 М.
Real World Refrigeration Service Call
26:14
Nor-Cal Refrigeration & H.V.A.C
Рет қаралды 11 М.
Another Carrier Gas Furnace Failed heat exchanger
17:13
Anti DIY HVAC
Рет қаралды 46 М.
SCHOOLBOY. Последняя часть🤓
00:15
⚡️КАН АНДРЕЙ⚡️
Рет қаралды 16 МЛН