Almost an hour long video? YES! My baby boy was cheering while you were brazing. Hopefully, if he wants to go into the trades, he will continue to have that enjoyment. Good work, Chris!
@craigmills62752 жыл бұрын
Hopefully if he goes into the trades his first boss isn’t a scam artist or straight a hole.
@lezlienewlands13372 жыл бұрын
Very much a "Compressors don't just die, they're murdered" situation imo. One bit of sand or a bad connection in the contactor and suddenly the compressor isn't getting the power it wants and it's not going to be happy. Contactor changeout as a preventative measure is just doing right by your customers. 👍 Watching from Australia, this stuff's fascinating. Made it to the end 😃.
@anthonybeliveau3158 Жыл бұрын
What's up , new hvac tech here ( 2 years ) , love your videos man !!! I'm gonna watch em' all for sure , keep going
@Goldstacker1972-kp2bh9 ай бұрын
Always change your contactor on 3 phase unit when you change the compressor.
@stradcar12 жыл бұрын
Wow i said I would not touch a/c s but I got a call one day from a place that uses 13 of these 3 compressor types units. The hvac guy says power problem. Turns out the condenser fan relay burnt. I fix it but this the only person that explains this stuff so well. A million tanx bro
@ianbradford4321 Жыл бұрын
I’ve been watching for about a year and a half. My friend/coworker that I respect and go to for guidance recommended you. I have recommended the videos to multiple co workers as well. I have learned a great deal, I had 20ish years in residential before coming to commercial.
@gsperanza07 Жыл бұрын
Anyone who tells you Chris , that changing contactors is an over waste , THERE DEFINITELY GOT NO IDEA AND HAVE NO PLACE IN THIS TRADE !!!!!! I’ve seen the first hand experience of low voltage and no low voltage issues, especially miss diagnostic test , over looking. ‘ pitted ‘. Burn’t contactor points , working normally they will 100% wear out and I’ve personally changed soooo many , low voltage and uneven load and phase will definitely cause. ‘ Brown - out ‘ burnt outs to occur , and house keeping has saved my clients and myself to call outs a good 40% on cooling tower fan units and especially compressor prematurely failing . It’s the basic rookie test of finding back to basics of diagnosing and testing ,mostly over looked and like your self , finding why, because , it’s the most important instead of just r & r , your statement is beyond true and I’m sure many , many , many , repeat repairs by air - con techs have gone to the same repair , more than once or replaced a new compressor to only return weeks or days later with another fault that was over looked !!! Well done and once again thanks for posting Chris, safe travels 😊 and Godbless 😊 , and I’ve watched the video , from start to end !!!
@fixerguy2 ай бұрын
Chris, in this day of corporate cost cutting by employers, talking about total man hours on jobs like this would be really useful to techs old and new. Other than that I love your videos and appreciate you sharing your knowledge, especially with the failure analysis stuff, which is my first love from my Navy ET days. That root cause stuff and the curiosity behind it truly is what makes great techs. 🎉 Thank you!
@robertogomez22972 жыл бұрын
Just wanted to say you are a troubleshooting Master! I have learned so much from your videos and I very much enjoy watching through everything, always learn something new! I’m 3 years in to the hvac trade and barely started commercial a year ago and your videos have helped me so much with troubleshooting commercial equipment, thank you sir.
@gmcxm211 Жыл бұрын
This is insane, the condition this equipment or people operate in. I live in Wyoming, We "might" have temps in the 90's 3 weeks out of the year. AC might run 3 months or 4 months out of the year. But our furnaces run 9 months out of the year. Really like you channel. Ted Cook "anti DIY HVAC gave you a shout out. You're really knowledgeable of your trade. Great workmanship and ethics. Until watching your channel, didn't realize how many of us take the contacts for granted.
@kylemcelya55892 жыл бұрын
Thank you so much for showing the testing to ground immediately. I never learned that until this video. 2 yrs into the trade and I learned more with your videos and other technicians videos. Please continue I'm now following you like a hawk!
@JoseNoriega-n5z Жыл бұрын
I absolutely appreciate the time you take to be thorough on your jobs. I started watching your channel about 2yrs ago already- and recently I was able to land a position with a Commercial HVACR business- but I've learned so much just by watching your trouble shooting methods but also, I'm beginning to understand the mentality of "take the extra 15mins to check on something or to do a task", which prevents so many issues down the road. I'm from Central Texas and the work I come to find is simply laziness. Love the videos, you're thinking and attitude, stay cool and be safe!
@ВладимирИвашечкин-п4е Жыл бұрын
It is my pleasure to watch a professional work.
@AIM54A2 жыл бұрын
Solid State contractors where made for this situation. No moving parts, totally sealed. Sand will never effect them.
@HVACRVIDEOS2 жыл бұрын
I will discuss this on my livestream this evening 7/25/22 @ 5:PM (pacific) on KZbin come over and check it out… or not kzbin.info/www/bejne/a3m2YXSdasuHm9U
@pashok28 Жыл бұрын
You can't help those Americans and their regulations. It boggles mind how they live in cardboard houses with wire nuts ancient wiring.
@DalesGarage15 сағат бұрын
*contactors*
@hrvstmn312 жыл бұрын
Really digging the 80's montage music, it's like I'm learning how to type in 6th grade off a laserdisc all over again.
@DJEZNICK2 жыл бұрын
The closing words are so important to follow in this trade, be a technician, not a parts changer, figure out why it failed. 👏
@LMSILVIA2 жыл бұрын
I rebuild semi hermetic compressors for a living. Its clear when you turn the rotor on the table that shine on one side indicates the rotor was rubbing against the stator. That will cause a burn out eventually.
@peterhodgkins69852 жыл бұрын
Seems to me that changing contactors to sealed EP type (e.g. Class I Div 1/2) would be more cost effective than routine replacements. Just a thought! Another great video, Chris!
@HVACRVIDEOS2 жыл бұрын
I will discuss this on my livestream this evening 7/25/22 @ 5:PM (pacific) on KZbin come over and check it out… or not kzbin.info/www/bejne/a3m2YXSdasuHm9U
@novaorbitdragon Жыл бұрын
"Pocket sand!" - Dale Gribble
@duffman10102 жыл бұрын
Loved the 80's/90's Sitcom music while Brazing LOL
@rhinohino2 жыл бұрын
I'm not an HVACR tech. But I'm an electro mechanical tech and like the electrical troubleshooting you do well. Keep up the great work!
@digitalcircuit2 жыл бұрын
Made it to the end! I didn't even realize it was 58 minutes until halfway through - quite the journey. I appreciate your thoroughness and eye for preventative maintenance - contactors included. Thinking about future potential trouble helps in other fields, too - including software engineering, what I'm pursuing.
@MagnumOpusSRT2 ай бұрын
Always enjoy your videos. You have the heart of a teacher. What about a clear box to enclose the contactor to extend the life in sandy conditions?
@KurtM5582 жыл бұрын
I had a great time taking apart our 34 hp recip low stage compressor after we oil slugged it. It was a great learning experience.
@KoScosss2 жыл бұрын
1h video? What a treat. Thanks, yum-yum.
@chieft33576 ай бұрын
I miss some of your videos, so I'm playing catch up. I see the outside temp you work in and I feel your PAIN. I was a jet engine tech for the j-79 which was on the older C-130'S. There are many times in Arkansas summer when the temp on a wing can reach 105 to 120 deg. Believe it or not we had to wear coveralls and special gloves just to handle a prop or engine during a change and that can take between 6 and 8 hrs. Stay safe and don't go to long in the heat, it will bite you hard.
@stefanpariyski37092 жыл бұрын
I appreciate the brazing montages and the effort put into it with the music and everything, really love watching them!
@bartfoster13112 жыл бұрын
That 5 ton should have a cover plate. They probably took it off for a better hand grip during install and never put it back in. We almost always install heat strips but I don't imagine you need them in so cal!
@garousata42612 жыл бұрын
Why do you need heat strips in the frist place? That thing is an heat pump right? ( Or at least it should be....
@bartfoster13112 жыл бұрын
@@garousata4261 it's for emergency heat and they are usually set to kick on when the temp is more than 3 degrees below what heat is set to. In the south it is only used when it gets really cold or if the condensing unit stops working.
@ILOVECALGARY2024 Жыл бұрын
19:50 what’s the point of having fuses if it’s not gonna short?
@davidmorton51372 жыл бұрын
thank you for your videos. one of the reasons i watch them (aside from pure learning, which there is alot of) is at the end you sometimes you dismantle the components, in this case a compressor and contactor. you then explain how they work, and give excellent insight as to why they failed. i appreciate all you do to help educate myself and all the other folks who pursue this never ending industry of woes.
@pineychristian2 жыл бұрын
Chris, Awesome video and diagnosis. I like how your approach is very carefully planned and cautious. I have a story on a 40ton McQuay RTU. The unit had two circuits with 4 stages of cooling. 1st stage compressor had one blown fuse feeding compressor contactor. Checked all basics before checking compressor. Compressor checked out ( electrically) using Copeland mobile app , ohms were good in spec and no shorts to ground. Very handy app. So at this point I decided nothing left to do but to put fuse in and check under power. WELL.... the compressor had a mechanical problem and broke. Blew compressor terminal plug out like it was hit with a shotgun buckshot with a massive arch of quick flash fire. It immediately went out. Blew the refrigerant charge out. Thank God I was like 8ft back away from unit when it came on. I immediately killed the disconnect and went off the roof to change my underwear..... scary stuff. I found out later the TXV was completely plugged and bad. It was banging off high pressure control and would reset later to continue to do it again. Always use caution and be careful cause usually there is a reason something broke.....
@northparallel6913 Жыл бұрын
Recommend contactors to be installed inside closures to protect from sand damage. You can still service them
@jimfiedlerRR-5462 жыл бұрын
Keep up the good work I think you got the best hvac channel on KZbin. You do a great job explaining your thought, & execution process on things. I am a residential/ commercial tech that's disabled with multiple sclerosis. I really loved the trade, & videos like yours still makes me feel apart of the trade still.
@eddevoe2519 Жыл бұрын
I always change contactors with a compressor.
@gregmercil39682 жыл бұрын
I work and live in the high desert, and that sand is no joke. A couple months ago I did a spring PM on a residential AC. I removed a Home Depot bucket’s worth of sand out of the condensing unit and then some. I make a point of getting all the dirt and sand out of condensing units before hosing down the coil, otherwise it will turn into a huge muddy mess and becomes a time consuming headache. I learned this the hard way last summer. I’ve also been making a point lately to take apart fan motors that I’ve replaced to see what went wrong in them when I have the time for it, for a learning experience and out of shear curiosity. I had one blower motor that I could hear arcing in the attic while I was at the Tstat, just before it tripped the breaker. Took that one apart, it appeared that the bearings failed and caused the rotor to make contact with the stator. The windings were a blackened charred mess as well.
@carolriley93923 ай бұрын
I really can't wait to keep sharing your channel! Been a sub for a while, and i must say you are simply the best! Your ability to explain every step you do plus your accountability to be honest, sets you apart from every other tech that is in the same trade. Thanks so much!
@SpazyFunk2 жыл бұрын
Instead of replacing all the contactors every PM you can sell them ICM450 phase monitors. This will prevent phase imbalance and low voltage problems. it will save the compressors.
@gabiold2 жыл бұрын
I just diagnosed a compressor short in a household portable dehumidifier. They used in in an industrial setting with fine dust and never cleaned the stuff out, the whole thing was full. So it was an overheating issue. The thermal switch probably saved it a hundred times already, but it eventually welded shut and failed to protect the last time. Probably. All I want to say is, there is all that electronics control, why no self-diagnostic for overheat too? When there are overheat events, possibly with increasing frequency, then after the n-th one, shut the system dowm with an error code as an early warning. There is no use of that auto-resetting thermal switch, if no one is getting notified that it is happening. Just as an example that similar thing already exists: in safety-critical industrial systems, a lot of stuff, for example contactors, sensors, etc are duplicated, in case if one fails the other will still do the job. BUT! If there would be no notfication about it, then the system would become as unsafe as with just one contactor or sensor or anything. For this exact reason, the system (safety relays) monitor everything that is duplicated, and when the paired things does not match state, it always disables the system (into a known good, safe state) and/or notify staff about the degraded safety, depending on how critical is to keep operating.
@Fluxy3332 жыл бұрын
I’m going to tech school next year and I chose hvac as one of my trades and I honestly am so excited to learn about this stuff, your videos teach me a lot!
@HVACRVIDEOS2 жыл бұрын
Awesome bud, I’m going live on KZbin this evening 7/25/22 @ 5:PM (pacific) to answer questions from the live chat, emails and KZbin comments, come over and check it out…or not kzbin.info/www/bejne/a3m2YXSdasuHm9U
@jasonjohnsonHVAC2 жыл бұрын
This job like many jobs is about CYA ( cover your a** ). You perform "big picture diagnosis" to cover the customer, to cover yourself and your company. You provide solutions to all problems found and let the customer choose what they want to do....as Chris stated. It the best, professional and proper way to be a quality tech. The money isn't ours to spend. You handled that in every aspect like a true pro Chris......job well done......I'd hire you 😁😆😄
@craigmills62752 жыл бұрын
Love how Chris said he was going to “inspect” that contactor. He knows damn well for 100000% he isn’t leaving that roof without changing it lol. No reason not to change that contactor if the compressor burnt up. Did the windings go out or did one of the legs short to ground? There’s an idea for your next compressor trouble shooting videos Chris. Show people how you test resistance between windings and each leg to ground. I’m sure you’ve done it in many videos.
@ericmichaud33312 жыл бұрын
You do amazing videos!! I always look forward to watching them. Learned a bunch of content from you. Watched the entire video from the beginning!! Be safe
@dragonrider42532 жыл бұрын
I love your big picture thing. Get in there and LOOK for problems or potential problems and bring it up to the customer. A nearly hour long video and I watched it all. I love your work.
@rival_son2 жыл бұрын
Just so you know, some (usually older) breaker panels don't have isolation for the connection points where the wires will connect to the panel for the individual, breakers so it can be risky to work inside the panel (ie replacing the wires) as you can be very close to live busbars or connections. That's maybe why they needed to shut the whole building (panel) down.
@rcctech13562 жыл бұрын
Or the piece of crap Zinsco breakers and panels...still in use out there.
@semifavorableuncircle69522 жыл бұрын
Why dont they have overload relays on the compressor contactors? Would help in case of phase loss too...
@caerusdharken572 жыл бұрын
There is nice combination monitor relays, Phase rotation, Phase loss, over and undervoltage, all in one Unit. In Europe they are pretty common.
@mtucker34012 жыл бұрын
100% agree with not charging anymore on the split. You probably have a TXV that’s over feeding right now because it’s so hot. And don’t get me started on those wires sticking out the top. I’ve seen way too many dry rot and short. I always wrap my exposed wires in electrical tape. Trevor Matthews is an awesome asset! Great guy and great knowledge. Thank you, sir, for your dedication to the channel and and the industry!!
@danpresson Жыл бұрын
I watch from beginning to end its great when you take them apart you have all kinds of awards
@GigglyWolf902 жыл бұрын
As much as I watch these videos, the more I admire who do this job. Stuff is way more complicated than I ever could have imagined
@ivancano58314 ай бұрын
I believe that compressor fail due to refrigerant in liquid state flushed the oil .a mechanical issue ending in an electrical failure.part of the problem loose blower motor belt you corrected the problem. Congratulations I enjoyed your videos. Thanks again
@r3tr0nic Жыл бұрын
Great teardown and analysis of the compressor failure. I do agree, I believe the blowing sand seems the root cause of the contactor failure and thus, compressor failure. My thoughts: Contactor contacts are accessible to the enviromentals, so sand contaminated them. Because the 3rd stage is used less then the 2nd and 1st stage, the contacts in the 3rd stage contactor remain open overall longer, and had more time to have sand/dirt build up. One or more phases may have become open, or a resistance developed in the contacts of the contactor and resulted in a low voltage condition. Eventually the overload in the compressor will have cut. Once the overload reset, and stage 3 call initiates, the process repeated with each time degrading the overload and windings. Eventually the overload may have failed stuck on or shorted, causing the compressor winding to heat up until the winding varnish failed and a short to ground developed and tripped the breaker. Perhaps the winding varnish failed first. Thats my educated guess. The contactor is def the Achilles heel. Makes me ponder how great it would be to have something monitoring the 3 phase power to the compressor itself, in addition to the normal protections. Such microprocessor powered monitoring could disable the stage much faster, throw an error code and alert for service call. Perhaps such already exists (I never messed with large systems like that). Your maint PM plan on regularly changing the contactors is a great idea. That is much less expensive then a catastrophic failure and extended unexpected down time vs a lesser planned down time.
@lastin1out1 Жыл бұрын
Saw belt deflection being tested. Wanted to share: the other day, someone taught me a formula for belt tension. 1/64 per inch on belt for deflection. So an example: an ax-64 belt should have 1 inch of deflection. An ax-32 belt should have 1/2" deflection... And so on. Hope it helps someone...
@MinecraftAedda2 жыл бұрын
Made it to the end, love listening to your job debriefings.
@pacificairsystems96832 жыл бұрын
You’re the most awesomeness HVAC guy in America
@TheNemosdaddy2 жыл бұрын
How's that boot taste?
@dillonallen96262 жыл бұрын
It possible the the reason why the electricians want to shut power down the the mail breaker panel / building is due to , pulling a home run they will be working dangerously close to a live bus bars.
@fitybux46642 жыл бұрын
Weird. They do sell very highly insulated rubber gloves for such occasions. (And face masks for arcing.)
@merlynsamazz18122 жыл бұрын
Hi here in the UK we have three phase and neutral plus where possible we always use solid-state contactors with DC voltage
@brendonnel66312 жыл бұрын
No Idea how I ended up here but DAMN it was interesting, this dude knows his craft.
@Anver_Silyaev2 жыл бұрын
Probably 3rd stage contactor damaged because of it works less and contacts are open most part of time, sand settles between contacts. Meanwhile 1st & 2nd stage contacts are closed and not so damaged. IMHO. Cool work and investigation 🔎!
@johnbell69562 жыл бұрын
I like your videos. Very professional. Worked on identical unit last week. 2nd stage compressor shorted internally. Only difference was it blew out the L2 pin and the entire refrigerant and oil charge. Was a serious mess.
@willspeed45852 жыл бұрын
The saxophone music. Perfect. 🤣
@chaosminecraft33992 жыл бұрын
Hi, it's awesome the work you do, I'm really happy to hear that the restaurant is getting properly cooled.
@albertoldschool69502 жыл бұрын
Maybe Try sealing contactor so sand can't get in. Do Quality work tighten wires to spec. reduce contact resistance and overheating. Replacing cover and panels to prevent Sun UV deterioration and sand infiltration. These thing may help. All the best to you. Thanks for the video.
@mistalee27 Жыл бұрын
Hey. I sanded in between my pavers and swept sand under the ac unit. I also blew the excess sand off the pavers which was causing a lot of sand to blow around the ac unit. My AC unit is now not working. Any advice?
@jordanhenshaw Жыл бұрын
Based on that info alone, may just have a dirty condenser but would need much more info to know. Maybe try condenser cleaning foam.
@clake8964 Жыл бұрын
Great video, very entertaining! This case specifically makes me wonder why the manufacturers of these AC units don't put a dustproof, well insulated box for the contactors to be in. The failure rate could go down drastically, as well as repair costs (especially in this case). What I mean is that it could lower the rate of catastrophical failure, like this one where it possibly single-phased the compressor, destroying it, not regular failure, like for example a compressor wearing out over time naturally. This applies to defrost clocks as well. Delicate parts are exposed to the outside influences when they can be very simply protected from them. Just a thought, feel free to correct me if there is a reason it's not done this way, maybe it's not up to code or something, idk. :D Have a wonderful day everyone!
@tdev042 жыл бұрын
I’m surprised you don’t have a molecular transformator for 410a recovery in that heat! I just got one to recover about 30lbs of 410a for a compressor change. It was high 90s in the Michigan summer and that thing made a HUGE difference in recovery time. Just dropped it in a bucket of ice water and let that machine suck. Never got over 300psi in the tank.
@HVACRVIDEOS2 жыл бұрын
I will discuss this on my livestream this evening on KZbin 8/1/22 @ 3:PM (pacific) come over and check it out kzbin.info/www/bejne/foSsgIedhL2rjJI
@adventurefishingscotland39182 жыл бұрын
Yet another great video. Been busy over in the uk aparently our ac units cant handle a bit heat
@djenson2 жыл бұрын
9:12 Would the contactor not show no voltage drop even if there was a bad contactor due to there being no load?
@legionofanon2 жыл бұрын
Possibly, could be the voltage drop is too little to be accuratly measured, but it could potentally be a granule of sand got in causing issues and when the contactor opened it fell out an then no issues later, but the damage has been done
@codywiggins93872 жыл бұрын
There was a blank plate in that location at once. Only supposed to remove it if you're installing an electric heat strip though. Great video as always!
@Jilocasindragon2 жыл бұрын
Thank you so much for making all those videos, the autopsy and and the discussion part. I only recently learned that the initial intent was to release those videos internally for your employees, so again, thanks for letting all of us take part in what you're doing :D Wish I had your beard!
@aaronharrison77292 жыл бұрын
I agree with you. Dirty micro channel and 410A= multiple head preassure trips could have caused contactor to stick and phase out compressor.
@ickipoo2 жыл бұрын
Jeez, that burned wiring on the first unit is bad. They're very lucky they still have a business and not just an insurance claim.
@skutahuniai48302 жыл бұрын
Not sure of California code but in my area, an LB is not allowed to be used as a junction box. Proper method would have been to pull the conductors from the panel(along with a ground) and then use liquid flex from the LB to the disconnect. Bad electrical work IMO.
@fitybux46642 жыл бұрын
I doubt this even stays under the box fill for the LB with that gauge of wiring.
@josephtramutola5922 жыл бұрын
Took the words right out of my mouth
@slamdvw2 жыл бұрын
I wonder if a phase monitor could help those compressors live longer? Single phase - shuts down and logs the fault.
@HVACRVIDEOS2 жыл бұрын
I will discuss this on my livestream this evening 7/25/22 @ 5:PM (pacific) on KZbin come over and check it out… or not kzbin.info/www/bejne/a3m2YXSdasuHm9U
@shadowbanned692 жыл бұрын
This is why I put phase monitors on all my equipment...needed or not. Condom principle...better to have and not need than need and not have...one day it will safe thousands if not more...
@lawrencecavens57605 ай бұрын
being that this video is 2 to 3 years old - you have to remember that even though you are not reading a voltage drop at that time - it will happen when you least expect it and contactors when they start to arc - over time get worse and worse and amperage gets higher and higher trying to do the work - add the heat load from the sun and - Meltdown - Its like you said sand contamination probably added to the scenario - Can a protective covering be installed to keep the sand out or would that add to the heat stress to the contactors ?? Just a thought...
@sosayweall19522 жыл бұрын
EET here! Could have been a rub in the insulation of the magnet wire, happens from time to time when manufacturing motors and transformers. This kind of issue could be dormant for years, then one day the winding get shorted to another one and the motor gets oversaturated and overheats.
@jrmcferren2 жыл бұрын
I see quite a few comments indicating potential failure points on this compressor, I do want to add a few other electrical things that may have led to this. That contactor looks like it took a lot of heat on all three phases. Now it was already mentioned that the third stage is going to cut in and out far more than the others when it is operating, but that also started to make me think. You could have had single phasing, but you could have just had a plain case of low voltage. The overload looks like it also took a lot of heat due to the bluing I see. Now that could mean excess current flowing. A few electrical conditions that will cause excess current over a longer period of time would be single phasing, under-voltage, and even mechanical overload which was also mentioned in another comment regarding the rotor rubbing the stator. I think all of these factors (Single phasing included or not) lead to the burn out. The third stage activates when there is a heavy load during high heat, this is when the power grid is at high load meaning the potential of lower line voltages. Even if the voltage was in specification, you have the stator and rotor in contact with each other, this means slightly more time at locked rotor current and you could...at least in theory have failure to start and the overload cutting in and out a bit. If there were cases of single phasing this would be greatly amplified.
@Loftis862 жыл бұрын
This music reminds me of the Saved by the Bell , Full House and Family Matters days haha. Love it
@wickedxe2 жыл бұрын
The armature looks like it was contacting the steel laminations of the field windings; my guess is that the lower motor bearing failed and the drag caused by the bearing failure caused the motor to be incinerated
@kylemcelya55892 жыл бұрын
Also could you go into more detail on how to use setup, remove a micron gauge. I flooded mine with refrigerant and am saving for a new one
@NameHere022 жыл бұрын
Is there a reason you don't install loss of phase or UVLO relays on the load side of the contractors to break control voltage in these locations?
@danielelise7348 Жыл бұрын
You're showing your age with these daggy 80's soundtracks Chris. 😆😆🔥❄️
@Blasterxp2 жыл бұрын
Would a small compressor of blower on battery help to clean contactors and clocks? Blow the sand out of them?
@matiasmena7518 Жыл бұрын
Excelente contenido, mi rubro es la refrigeración y aire acondicionado domésticos en Argentina desde hace unos 9 años, y en mi opinión sobran los motivos para reemplazar contactores mucho más en éstas condiciones, sin dar demasiadas explicaciones a quien diga que no es necesario, es porque evita mayores reparaciones y costos asociados, podrías también hacer un video para orientarnos sobre cómo y dónde cortar compresores sería genial ver eso, excelente tu trabajo y realización del contenido!
@allenheineck23592 жыл бұрын
Un-brazing the discharge line of a scroll compressor is a bad idea. That said, you're a quality tech and I like your videos.
@rocker86922 жыл бұрын
How do you get a compressor on the roof,do you need a crane for that one.Thanks
@CavinCavintv2 жыл бұрын
Nope, compressors are heavy but not enough for the use of a crane. You just got to be real careful lifting it up with some rope. If you look carefully there's a loop on the top of the compressors. Also, some places might have a staircase for roof access inside, so it's just alot of lifting lol
@legionofanon2 жыл бұрын
Good tip on keeping your grinder to shallow cuts, one to keep debris out, but also two it can preserve the life of a cutting wheel. In my experience plunging the wheel wears it out so much faster, especially since little twists can wear out the faces of the disk making them just disintegrate
@inductoservice98662 жыл бұрын
I think your hypothesis is correct. I know what sand does to your relays and contactors. Sand is a very good isolator. So it is very easy to get one phase missing situation which burns your motor. That is why motor protection circuit breakers are recommended.
@thephantom14922 жыл бұрын
For the shutting fown the whole building: it is against OSHA to work in live panel (with a few exceptions). The electrician might be one of the few that care about their safety.
@josuelujan77362 жыл бұрын
Everything you said you make a lot of sense man thank you I learned a lot from you but I have a question about the white cooler with wheels. 45:02
@renetrevino98292 жыл бұрын
Hey bud thank you for taking the time to make these videos. Your approach to trouble shooting the best I’ve ever seen and very educational
@c117ls72 жыл бұрын
Always make it to the end! I've said forever that I'd love to be able to put a motor starter/contactor cabinet down in the building. It would take a ton of wiring from each unit but if you could put all the VFDs and contactors inside the building, it would certainly prevent a lot of failures.
@gorak90002 жыл бұрын
They sell sealed contactors that have enough of a cover to keep sand out. And the unit could be designed to keep it's own control electronics cool even if it's mounted outside - it's a f'ing box that literally makes COLD AIR. My first thought is "mount the control and VFD in the conditioned air space", but then "what if the VFD blows up? All that crap gets sucked inside - that's bad" - ok fine. Idea #2, mount the control and VFD on a heatsink that sits on the cold air side of the unit, but the parts themselves are still on the outside side. These things are just designed to be cheap, and fail. They could also include current monitoring on every compressor and fan motor in this thing, and detect failures long before they actually happen, and for not very much BOM cost, but they don't do that either.
@HVACRVIDEOS2 жыл бұрын
I will discuss this on my livestream this evening 7/25/22 @ 5:PM (pacific) on KZbin come over and check it out… or not kzbin.info/www/bejne/a3m2YXSdasuHm9U
@hgbugalou2 жыл бұрын
Seems like condensers should have a self cleaning option for environments like this. Just a water supply and a nozzle that sprays the coils down every week or so would be helpful. It doesn't replace normal manual cleaning but would help in between. Does that kind of thing exist? I'm also curious if solid state semiconductor based switches can replace contactors in sandy environments like this. Sand just kills moving mechanical components in no time.
@stephenhunter702 жыл бұрын
I wonder if a phase failure relay would be helpful, across the line outs of each of those contactors.
@HVACRVIDEOS2 жыл бұрын
I will discuss this on my livestream this evening 7/25/22 @ 5:PM (pacific) on KZbin come over and check it out… or not kzbin.info/www/bejne/a3m2YXSdasuHm9U
@lgunderso21172 жыл бұрын
Only $1000 for all the contractors on all the equipment? What do contractors cost? Would you mind disclosing what a service call to that location costs? Seems like a good idea to me. Something else that might be worth looking into- and I will a little tomorrow- is contractors with a better IP rating. I’m an electrical engineer designing high voltage systems on EV’s- we have some fantastic sealed contractors but they’re quite expensive. I’m curious if there’s a good middle ground that would be suitable for that location. Another idea is putting the contractors/electric components in sealed boxes. Difficult and expensive but potentially worth it in the long run. If not, and without cost info on service call cost/assuming it’s $500+ for that location- it seems like a great deal for the business to have their contractors changed at least annually after a dust storm.
@2xKTfc2 жыл бұрын
Yeah, I'm surprised so much equipment is mounted basically outside in cabinets that mostly only protect people against reaching into voltage and equipment against direct rain, but in a known dusty environment does nothing to protect against the dust. All that equipment and labor is not cheap, after all. Speaking of - did you mean to write contactors or indeed cont*r*actors? I might be missing the obvious, but only in the last sentence I can tell you probably meant the former, the other ones are ambiguous and work either way.
@lgunderso21172 жыл бұрын
@@2xKTfc yep, and usually it works. It would not be be acceptable elsewhere. I meant contactors. I’m on mobile and autocorrect kept trying to replace it. I thought I caught them all, thanks for catching.
@2xKTfc2 жыл бұрын
@@lgunderso2117 Thanks for clarifying :) Cheers!
@ehsnils2 жыл бұрын
I'd consider to use a big lathe (works for round compressors, not oval) or a milling machine to cut the compressor open. But you use what you have at hand.
@colinclingan82462 жыл бұрын
Lately it feels like we’re living in the SOCAL desert Oklahoma has reached record temps. OKC was 110 and western OK was 116
@fitybux46642 жыл бұрын
Welcome global warming. I guess this just means more HVAC revenues, lol.
@larryboy49052 жыл бұрын
I like to do an acid test on the oil and add an HH filter drier and acid scavenger if it is positive.
@customcreations-rickkramer53572 жыл бұрын
I love the music around the 30 min mark. Was half expecting the camera to turn and show John & Ponch riding up the road, turning on lights and sirens 🚨 and then nailing the throttle!!
@Tactical-Black2 жыл бұрын
Really thinking about getting into air-conditioning now, i use to work in the feild only on the electrical and controls side
@DavidKing-vb9ux4 ай бұрын
I’m not sure on Carrier but yes it should have a knock out panel from the factory for electric heat package! My guess installer knocked out! You should cut a patch panel and cover that!
@keithfarnham87203 ай бұрын
Hey Chris , you mention that you look for a voltage drop across a contactor to determine the condition of the points. Voltage is nothing but the pressure of current flow and looking for a voltage drop is arbitrary and meaningless. I prefer to use a bench meter and measure milliamp loss by creating a parallel current flow through the meter. If your contacts are true and clean the meter will measure no amperage , if your contacts are faulty or failed the meter will measure amperage.