Best explanation I've seen so far! Thank you kind sir
@chesterco95867 ай бұрын
Thank you sir for this knowledge, very well clearly expalined.
@mikerod5396Ай бұрын
What is the pipe for those pipes not within the design area? Do those pipe runs need to match the pipe diameters of the pipe within the design area? This pipe layout is interesting.
@MartinKryekurtiАй бұрын
Nice video guys. Had a question , What does : Pressure at hydraulic junction point shall balance within .5psi mean ? Is it times .5psi ? or divine .... ?
@andisuharto9728 Жыл бұрын
tanks a lot , Mr. Harland
@dennisregalado3675 ай бұрын
Thank you, clear explanation and knowledgeable. Do you conduct actual training,
@h.machaconmechanicalengine9300Ай бұрын
I don't conduct training because I am very busy and I am doing these videos on my free time. NFPA is conducting training on these topics. You can also read the different NFPA Standards on their website. Check out their website.
@leonciogarcia99893 ай бұрын
will they upgrade the pump or install a separate system for this expansion, or the capacity of the pump is enough , thank you sir for the informative presentation.
@h.machaconmechanicalengine93003 ай бұрын
Refer to our video tutorial City Water Supply Versus Fire Sprinkler Demand
@andresmata3727 Жыл бұрын
Hi sir great video. Could you please tell me how do you determine the largest area covered by any sprinkler in the design area? (Point 4).
@icutoo2699 Жыл бұрын
It's in NFPA 13, the most hydraulilly demand, usually the farest and highest from the water supply from the base of the building riser.
@mariomabaga2014 Жыл бұрын
nicely and clearly explained sir..
@andisuharto9728 Жыл бұрын
Mr. Harland, may I ask, at 8.49 minutes it was stated that there were 2 Tees, but in the end why did it say only 1 tee (10) with a 2 inc pipe schedule 40. or not 2 x 10, forgive me if I'm wrong ,explanation please
@andisuharto9728 Жыл бұрын
oh sorry, it turns out I was wrong careless
@ginoafricano88318 ай бұрын
Hello sir, may i ask is the formula for pressure drop applicable also in Fire Hose Discharge?
@h.machaconmechanicalengine93003 ай бұрын
Yes
@warunakarunarathne15232 жыл бұрын
What is the recommended software to draw the design and simulation
@h.machaconmechanicalengine11872 жыл бұрын
There are lot of commercial software available in the market. Most engineering firms use HASS Fire Sprinkler Hydraulic Analysis Software!
@h.machaconmechanicalengine93003 ай бұрын
There are several available in the market.
@zaccblack103 Жыл бұрын
Sir, when doing hydraulic analysis of combined systems, should you include the fire hose stations in the analysis, i.e., 100 gpm, 65 psi?
@icutoo2699 Жыл бұрын
When doing calculations check with the AHJ on how to perform them. Each AHJ may have different rules. You need to read the chapter in NFPA 14 and make sure your using the correct edition that complies with your local code requirements. Your local code could be different from NFPA 14 & 13. You alway need to read and re-check since they do make changes to the standards.
@aivencanales91876 ай бұрын
hi sir, how did you get 129.87 ft2 in item no. 4?
@h.machaconmechanicalengine93003 ай бұрын
From the layout, compare the area covered by each sprinkler within the design area
@The08206 Жыл бұрын
hi, why did you get only 1500ft2 for calculation. why we cant take more than 1500ft2?
@icutoo2699 Жыл бұрын
Typically you want the most economical system, smallest pipe size, smallest pump. The larger the design area the higher the water demand and therefore a more expensive sprinkler system. 1,500 sq.ft. is the smallest area on the graph.
@The08206 Жыл бұрын
Thanks for your response. so when we can consider more than 1500 ft2 area for calculation? I mean which industry. @@icutoo2699
@ronaldreybasillote64982 жыл бұрын
Good day sir.. thank you for the clear explanation... can i ask the price of your "computer program hydraulic calculations" thanks and God bless sir
@h.machaconmechanicalengine11872 жыл бұрын
I suggest you purchase commercially available Fire Sprinkler Hydraulic Analysis Software
@jaypel59272 жыл бұрын
Good video. Can you please share the slides?
@h.machaconmechanicalengine11872 жыл бұрын
Sure go to our website www.hmachaconengineering.ca and send me your email
@zaccblack103 Жыл бұрын
Are you a Filipino, Sir?
@rickyparagas5 ай бұрын
Pilipino ba kayo sir?
@ethinkgroup84923 жыл бұрын
Hi Sir Harland, your explanation is so good. We are a startup looking forward to benefit students in India with your expertise. It would be a privilege if you would partner with us. Can you share your email so I can send details. Thank you
@h.machaconmechanicalengine93003 жыл бұрын
My email is harland@hmachaconengineering.ca. You can also go to my company website www.hmachaconengineering.ca and then there you can message me directly
@ethinkgroup84923 жыл бұрын
Hi Sir, sent mail to you
@raplabrador5 ай бұрын
Hi Sir Harland, may we invite you to conduct a technical presentation to our Mechanical Engg organization chapter meetings here in the Philippines through online e.g. zoom?