Nice PM I thought we did good pms but yours is 🔥🔥🔥
@EverythingHVACR3 жыл бұрын
Thank you!
@bhunter38503 жыл бұрын
Thanks for showing us the PM. And thanks for tip about using rubber tubing to prevent rub outs.
@EverythingHVACR3 жыл бұрын
Thanks for watching!
@johnwaby43213 жыл бұрын
Brilliant view. . All looking nice and clean now .. saves you having any problems later on 👍👍
@EverythingHVACR3 жыл бұрын
Thanks man!
@hkhsm3593 жыл бұрын
Nice job. Keep posting videos. Thanks for sharing
@EverythingHVACR3 жыл бұрын
Thanks man!
@jimmyp54873 жыл бұрын
Sweet pm Wish all customers with pay the money to keep their equipment up to standards... some do others don’t but pay more in the long run. Keep the videos rollin brotha. stay safe 🤘🤘🇺🇸🇺🇸
@EverythingHVACR3 жыл бұрын
Thanks for watching! It is nice when equipment is well taken care of.
@jeffleffel49052 жыл бұрын
Surprised a “super tech” hasn’t come at you about spraying the coils from the outside lol I hit it just like you do at an angle. Only thing different I’ve done is getting rid of those grease lines all together… your already walking around in there hit it at the bearing itself and wipe off the excess grease. Do you take out the plugs and put grease fittings on the motors?
@EverythingHVACR2 жыл бұрын
😆 Thanks Jeff! If the coil is clean it's clean. Eventually the motors may need grease but if you look at manufacturer data on the motors, usually a few years normal duty before I would consider greasing.
@Stickboibx3 жыл бұрын
Great video! I work at the facility that produces this unit.
@EverythingHVACR3 жыл бұрын
Nice, thanks for the support! Keep doing what you do, these are well built units 💪👏
@refrigerationconfidential43763 жыл бұрын
Very thorough awesome stuff
@EverythingHVACR3 жыл бұрын
Thanks man!
@markbell68643 жыл бұрын
Great pm on an IntelliPak👍
@EverythingHVACR3 жыл бұрын
Thank you sir!
@hvacslayer29293 жыл бұрын
Looks like not too much has changed with the intellipaks. Hopefully they changed the paint coat and doesn’t get all chalky turning you into a powder donut. Dumb idea to have contactors in a separate box I’ve seen older mcquays like that were they are underneath the comps in a control box. Still same user control module has the 2000’s year makes that I have. Watching you spray the compressors made me flitch I’ve had crankcase heaters pop on me when getting some water on them 😂 Guessing it isn’t code to drain into the roof drains over there? Also noticed on some of your zones, the boxes completely close up near setpoint. Here we have our mins and max we have to have ventilation so min would be like 150 cfm depending on box size. We got audited by UL on our RTU and some areas through out the building, lol let’s just say some interesting data and comfort for customers isn’t there priority.
@EverythingHVACR3 жыл бұрын
I am not a fan of the contactors moving either, this was the first time I've seen that, so must be on the new models. Your right, Roof drains are not code here. As far as the box minimum, harshaw actually set this up and now we have the contract. Anyway I didn't mess with much air flow, I will adjust min and max when needed but a few vav only feed 1 small office on the Interior so 150cfm may be too much, hard to say but first time p.m. I didn't want to throw everything out of whack so only a few slight adjustments. Many more will need to be made in the future to fine tune everything. I spoke to the customer about this and they understand. But to keep this short there were other issues that were going on, some things just were not right, addresses on boxes, stats in wrong area ect. Thanks for watching!
@arielhernandez29112 жыл бұрын
Ima have to steal that Vicky tubing idea
@EverythingHVACR2 жыл бұрын
Do it Ariel Hernandez! It works 💪
@neilvestervictor1803 жыл бұрын
great job on this video
@EverythingHVACR3 жыл бұрын
Thanks man!
@dirtydan678 Жыл бұрын
What kind of nozzle do you use on the hose? Water pressure isn't the best at my building, anything would help. Thanks!
@EverythingHVACR Жыл бұрын
It's a bullseye nozzle, it helps. but with really bad water pressure, you could use a booster pump to help.
@dirtydan678 Жыл бұрын
@@EverythingHVACR thank you!
@EverythingHVACR Жыл бұрын
No problem, thank you, dirtydan!
@rgmALC3 жыл бұрын
I’m a service tech for Trane. You covered everything pretty well....good job!
@EverythingHVACR3 жыл бұрын
Thanks man, we do a lot of trane, where you from
@rgmALC3 жыл бұрын
@@EverythingHVACR New Hampshire. Intellipaks are intimidating at first - I still spend time with tech support going over sequence. But you seem to be comfortable with them. As much as there is going on with them, a fully decked out Precedent (all motors on drives, re-heat, reversing valves, etc) is 100x more confusing!!
@EverythingHVACR3 жыл бұрын
Nice! have worked with some of the harshaw guys down here in KY, my company works with trane as well. Thank you for the support!
@leifhoganson69963 жыл бұрын
@Everything HVAC, do you perform RTU maintenance in the rain?
@EverythingHVACR3 жыл бұрын
Depends on how bad the rain and what I have to do. Stay out of electrical, obviously, but rinsing coils or drains can be accomplished safely, if you have to but Once you've done it for a while it's easy enough to watch the weather and plan accordingly! Thank you for your support!
@simohvac92223 жыл бұрын
great PM
@EverythingHVACR3 жыл бұрын
Thanks man!
@xraybravo71802 ай бұрын
I have an intellipack that has 6 compressors only 2 large ones are on and I'm not sure what the small compressor do and when and how they come on ? Stage- 1 3 compressor only 1 runs 2 stand by contsctors don't close for them. Stage -2 3 compressor. It's same as one for this one.
@EverythingHVACR2 ай бұрын
Is it maintaining supply air temperature? Are there any alarms? If there are no alarms and it's maintaining supply air temperature, it may not stage up.
@xraybravo71802 ай бұрын
@@EverythingHVACR It says RTM ? Supply air temp input 57 °F
@xraybravo71802 ай бұрын
@EverythingHVACR how to test them to run ? In test mode ?
@EverythingHVACR2 ай бұрын
You should be able to test them via the HMI.
@alwayslost30083 жыл бұрын
I like to use a vacuum cleaner for drain pans if they that dirty. I think, but stand corrected, the moved the larger contractors because it could interfere with low voltage control signals esp com signals.
@EverythingHVACR3 жыл бұрын
Any way you do these intellipack units is a pain, you just can't access the drain pan well.
@alwayslost30083 жыл бұрын
@@EverythingHVACR I live in South Africa. we don't have the same equipment that you guys have over there. Our regulations arn't as strict as the US. Africa is in short the dumping ground for out of date and equipment that don't meet the 1st world regulations. Eventually those type of units will become available here.
@EverythingHVACR3 жыл бұрын
These units are reliable and work great especially in large office buildings with multiple rooms and offices, intellipack VAV is the way to go. Thank you for your support!
@jasonjohnsonHVAC3 жыл бұрын
Thats a big unit. How many tons?
@EverythingHVACR3 жыл бұрын
100 tons, may be slightly bigger dont know the exact BTU but yes it is a biggun. Thanks for watching!
@jasonjohnsonHVAC3 жыл бұрын
@@EverythingHVACR ya I'd say thats pretty big.
@benjaminmeester75578 ай бұрын
hello, what software are you using to access the intelipak like that?
@EverythingHVACR8 ай бұрын
Tracer TU software is connected to the main SC controller. It does require a license through trane. Most adjustments, if needed, can be done from the HMI at the intellipack.
@benjaminmeester75578 ай бұрын
@@EverythingHVACR thank you. my new employer has an intellipack so im brushing up on them, but they dont have the software so thats my next move.
@EverythingHVACR8 ай бұрын
It may have a front end or a main computer connected to the building that you can view and make adjustments. The software probably has a few extra benefits, but for the most part, you could make any necessary adjustments from this computer. Understanding VAV system operations is a must, more so than the software.
@PBS-nm1uu2 жыл бұрын
do you have any videos on sequence of operation. ???
@EverythingHVACR2 жыл бұрын
Good question PBS! Not specifically on the intellipack, though I have a few more videos on intellipack units. A more recent video shows diagnosis of the burner control.
@EverythingHVACR2 жыл бұрын
kzbin.info/www/bejne/fYaseGiYraiMp7M
@JimLopez-q8b Жыл бұрын
Nice you have a computer to check unit my company don’t give us nothing
@Jamie-po9zk3 жыл бұрын
what kind of hose attachment are you using?
@EverythingHVACR3 жыл бұрын
What do you mean "attachment" to what?
@EverythingHVACR3 жыл бұрын
Not sure how I misread this, it's called a bullseye, simple and effective. My favorite nozzle to use
@mauricekendallii36583 жыл бұрын
What tonnage is that?
@EverythingHVACR3 жыл бұрын
80 to 100 tons, not 100% sure. Serves a 4 story office building.
@stevem96293 жыл бұрын
👍
@AAmr-y5r11 ай бұрын
I have this intelipack i can't find zone sensor . I looked behind fan compartment found nothingn
@EverythingHVACR11 ай бұрын
There is not a single zone sensor. This is a vav system, so each vav has a zone sensor that controls the space temp using the vav box. The intellipack only maintains a constant supply temperature and duct static pressure.
@AAmr-y5r11 ай бұрын
@EverythingHVACR under what menus can I find that constant supply tempreture. It's controlled by backnet and company who monitors it is unknown.
@AAmr-y5r11 ай бұрын
@@EverythingHVACR Controlling sensor sub menus-> RTM Supply air input is: 59F. Active daytime WU temp sensor input from bas network: 69.1F.
@EverythingHVACR11 ай бұрын
Supply air input is the supply temperature. Daytime warm up is a sensor in the space to allow Daytime warm up if needed. What is the problem here? You may need to read over the manual to understand the operation better.
@jonnymac313 жыл бұрын
Yeah man
@EverythingHVACR3 жыл бұрын
Thanks John!
@geraldschilli88703 жыл бұрын
Suggestion; when needed, replace the plastic grease tubing with copper tubing. Problem solved.
@EverythingHVACR3 жыл бұрын
That is a great idea, I'll keep that in mind Thanks for watching!
@gr8gmblr3 жыл бұрын
Cool, thanks for sharing. But rinsing the condenser coil will not cause a high pressure fault.it Might cause less dehumidification.
@jfrancis983 жыл бұрын
Micro channel coils will when full of water
@EverythingHVACR3 жыл бұрын
Truth, thanks HVACtech!
@geraldschilli88703 жыл бұрын
Condensate draining directly out onto the roof is definitely against mechanical codes. Whoever the installation contractor was needs to be called out about this issue.