troubleshooting this Trane hvac Rooftop unit / RTU / RTAC no cooling / no AC service call resolution , to replace both circuit entering and leaving evaporator thermistors / temperature sensors. evaporator entering / inlet / Txv outlet temperature sensors and evaporator outlet / suction line temperature sensors
unit ran fine after that!
link to part I (1) 👇
• HVAC | AC TROUBLESHOO...
#d2dnyac #heatingventilationandairconditioning #hvacservice

Пікірлер: 63
@markbell6864
@markbell6864 3 жыл бұрын
Keep up the good work D2D. Love your style of videos 👍
@D2DNYAC
@D2DNYAC 2 жыл бұрын
Appreciate you and all who supports my HVAC journey on KZbin 🙏
@carlseiz1266
@carlseiz1266 Жыл бұрын
I love videos like this where people explain what they're doing you hvac guys make this stuff look so easy
@missionuluna5837
@missionuluna5837 6 ай бұрын
Nice one brother, thanks for helping us with this video.. Junior Hvac from papua new guinea 🇵🇬🙏👏👍👍
@D2DNYAC
@D2DNYAC 6 ай бұрын
Thanks for watching
@D2DNYAC
@D2DNYAC 6 ай бұрын
Thanks for watching
@nonfiction_4life156
@nonfiction_4life156 17 күн бұрын
I had :HIGH COMP DIFF PRESS CKT 2 on same Intellipack unit in North NJ .Leaving Evap temp 157 degrees . It was sensor in well on distributor tube in Evap. I replaced both sensors they are only like 18 dollars at Trane supply house . Replaced sensors & temp dropped to 51 degrees .
@D2DNYAC
@D2DNYAC 16 күн бұрын
Good info
@markbell6864
@markbell6864 3 жыл бұрын
You are on the right path though. intellipaks do have supply and return air temp sensors most of the time especially if they are on BAS
@RickOrtutay-gf6xv
@RickOrtutay-gf6xv 9 ай бұрын
You guys Rock! From one tech to another! Be safe out there brother!
@D2DNYAC
@D2DNYAC 9 ай бұрын
Thank you for stopping by
@WHITEBOY76305
@WHITEBOY76305 2 жыл бұрын
Thank you for your videos and guidance, You are an HVAC role model. love your since of humor 😂. Bless up, keep up the good videos. 💪👍
@D2DNYAC
@D2DNYAC 2 жыл бұрын
Thank you for watching my friend
@CreativeMaintenanceSolutions
@CreativeMaintenanceSolutions 2 жыл бұрын
Thanks for your videos brotha! I'm new to the HVAC world and I've been watching multiple videos trying to prepare myself for my new job!!!
@D2DNYAC
@D2DNYAC 2 жыл бұрын
Thanks for stopping by
@CreativeMaintenanceSolutions
@CreativeMaintenanceSolutions 2 жыл бұрын
@@D2DNYAC I'm out in LA California. I will continue to keep stopping by and I appreciate what you do! Keep up the good work!
@MetalDetectingwithCZkidd
@MetalDetectingwithCZkidd Жыл бұрын
Instead of crawling in there powered or not(I have crawled or stepped in those systems many times running), Could you have just ohm'd out the sensors back at the control boards? Once you know the tech on the sensors, then they should ohm out, if reading are out of range, easier to diagnose? Like your style of service. Well done.
@D2DNYAC
@D2DNYAC Жыл бұрын
Thank you for stopping by
@cucumbersalad9063
@cucumbersalad9063 6 ай бұрын
loving your videos, thank you so much
@D2DNYAC
@D2DNYAC 6 ай бұрын
Thanks for watching
@paulmerritt7540
@paulmerritt7540 9 ай бұрын
Yes there is two low ambient fans on that unit, one for each set of compressors. Don’t forget to check the air filters.
@D2DNYAC
@D2DNYAC 9 ай бұрын
Thanks for watching
@dimaslespier2688
@dimaslespier2688 3 жыл бұрын
That could be? But I had the same issue. And the reason why in my case it thought the system was short of refrigerant was because the unit logic is run by both the return and supply air sensors. So it was not shutting off the compressors due to the high reading of the discharge sensor so the compressor would run until it went off on low pressure. The only device that can give that board a low refrigerant reading is the low pressure or pipe temp sensors.
@D2DNYAC
@D2DNYAC 3 жыл бұрын
@Dimas lespier Agreed you are saying the same thing I discovered while troubleshooting, when the suction temperature is too high the system views it as high super heat which can be associated with lost of refrigerant charge! Thanks 🙏 for stopping by old sport
@michaelbarcia6242
@michaelbarcia6242 2 жыл бұрын
Best videos I seen so far very helpful,thank you
@D2DNYAC
@D2DNYAC 2 жыл бұрын
Thank you for stopping by
@johnholsapple6649
@johnholsapple6649 2 жыл бұрын
I don't usually comment on videos but I had to on this one. Whether you know what your doing or not you should shut the unit down defore entering over that belt. Accidents happen so safety first.
@D2DNYAC
@D2DNYAC 2 жыл бұрын
Indeed they do , thank you for stopping by .
@YoDoneSa
@YoDoneSa 2 жыл бұрын
Nice videos dred. Real life movements. Keep it up star
@D2DNYAC
@D2DNYAC 2 жыл бұрын
@Jermain Carty thanks for stopping by
@jasonostrowski3972
@jasonostrowski3972 11 ай бұрын
I have also found that there will be corrosion on these sensors that will cause them to insulate themselves. Just a little Emory cloth can get you out of a pinch
@D2DNYAC
@D2DNYAC 11 ай бұрын
Good tip thanks for sharing
@timothysambolin5293
@timothysambolin5293 11 ай бұрын
Right track
@D2DNYAC
@D2DNYAC 11 ай бұрын
Thanks for watching
@Erikmiles87
@Erikmiles87 2 жыл бұрын
Trane uses 10k ohm resistors. They tend to have a chart in the manual. You could also google a 10k ohm resistor chart and reference the resistor to the ambient of the sensor space.that’s for any thermistor.
@D2DNYAC
@D2DNYAC 2 жыл бұрын
Thank you for stopping by
@alikhalid76dxb
@alikhalid76dxb 3 жыл бұрын
D 2 d n y We love h mairay bhai
@DontHaveToDream
@DontHaveToDream Жыл бұрын
Love the videos!
@DontHaveToDream
@DontHaveToDream Жыл бұрын
Check this bro. That red bird feeder on top of the unit should be angled at a 45 degree to prevent water from collecting inside of it eventually siphoning into the tubing back to the transducer.
@D2DNYAC
@D2DNYAC Жыл бұрын
Dope, thanks 😊 for watching
@jeffgrant6914
@jeffgrant6914 2 жыл бұрын
Good video 👍
@D2DNYAC
@D2DNYAC 2 жыл бұрын
@jeff grant Thank you🙏 for stopping by
@markbell6864
@markbell6864 3 жыл бұрын
Just check the resistance of the sensors. Trane manual will give you the values
@D2DNYAC
@D2DNYAC 3 жыл бұрын
@mark bell Great point old sport! FYI unit ran fine post replacement of sensors
@RJMaker
@RJMaker 3 жыл бұрын
This 100%! I would add the check should first be made at the control, and if OOR at control then checked at the sensor. While you're at the control, you should also check sensor input voltage to help eliminate a control board issue (That is my 1st check). This is IMO how a diagnostician finds the root cause, before ordering any parts, outside of that,... it's guessing. EDIT: the "it's guessing" comment is not fair. It is an "Educated Guess"
@globaltecnicianworldsbest3031
@globaltecnicianworldsbest3031 3 жыл бұрын
@@RJMaker SMH 🤦‍♀️ First of all for most of you if it had not being for videos like this on KZbin, if you were placed in a situation like this you wouldn’t know where to start, to say that it’s guessing that’s false because there were several steps taken prior to coming to the conclusion! Sensors or logic board and the sensors was the most viable option based on the troubleshooting process.
@markbell6864
@markbell6864 3 жыл бұрын
: The cooling circuit of interest has been active for 10 minutes and the difference in the entering and leaving evaporator temperatures has been greater than the Evaporator Temperature Differential Setpoint for 10 continuous minutes. He did it right. The MCM is good because it’s getting the readings and you know by the valve given one is not reading correctly. You can verify buy resistance but really no need. Good techs don’t always waste time going through all the steps in the troubleshooting process when they know which ones can be skipped.
@RJMaker
@RJMaker 3 жыл бұрын
@@globaltecnicianworldsbest3031 I'm not "most of you", and yes I'll give you it was an ** educated ** guess. My point is, in this case there is NO reason why you can't absolutely know what the problem is before ordering parts.
@dimaslespier2688
@dimaslespier2688 3 жыл бұрын
This is especially an issue with the R410A units.
@D2DNYAC
@D2DNYAC 3 жыл бұрын
@ Dimas lespier Like the the one in the video 😆
@roqueherrera8471
@roqueherrera8471 Жыл бұрын
Is this an intelli-pack?
@D2DNYAC
@D2DNYAC Жыл бұрын
Yes sir
@D2DNYAC
@D2DNYAC Жыл бұрын
I have several other troubleshooting videos with them!
@roqueherrera8471
@roqueherrera8471 Жыл бұрын
Send me link please my new AMIGO
@roqueherrera8471
@roqueherrera8471 Жыл бұрын
U HVAC BATHOMBRE (BATMAN)
@D2DNYAC
@D2DNYAC Жыл бұрын
🤣😂
@jasonjohnsonHVAC
@jasonjohnsonHVAC Жыл бұрын
I work on a lot of intellipaks. I enjoy it
@D2DNYAC
@D2DNYAC Жыл бұрын
Thank you for stopping by
@captaincat40
@captaincat40 2 ай бұрын
I just had my first experience with them. Question: where is the outside air sensor physically located? I've found where it's wired inside the electrical compartment from the schematic.
@nonfiction_4life156
@nonfiction_4life156 16 күн бұрын
@@captaincat40 under vfd in supply fan section gotta remove back side panel with the screws
HVAC TROUBLESHOOTING |   A/C NOT COOLING
35:49
D2D NY Real World HVAC Simplified
Рет қаралды 8 М.
HVAC TROUBLESHOOTING
22:33
D2D NY Real World HVAC Simplified
Рет қаралды 17 М.
This Dumbbell Is Impossible To Lift!
01:00
Stokes Twins
Рет қаралды 42 МЛН
At the end of the video, deadpool did this #harleyquinn #deadpool3 #wolverin #shorts
00:15
Anastasyia Prichinina. Actress. Cosplayer.
Рет қаралды 15 МЛН
Now it’s my turn ! 😂🥹 @danilisboom  #tiktok #elsarca
00:20
Elsa Arca
Рет қаралды 11 МЛН
Commercial Rooftop Units Troubleshooting- Fall 2020
1:47:59
Gustave A. Larson Company
Рет қаралды 45 М.
TRANE VOYAGER NOT COOLING
15:02
HVACR VIDEOS
Рет қаралды 59 М.
trane unit with bad RTRM board
14:30
Anthony Reardon hvacr
Рет қаралды 33 М.
Carrier rtu AC not cooling
18:08
Curious HVAC Guy
Рет қаралды 20 М.
TROUBLESHOOTING, DIAGNOSTICS AND RESOLUTION OF A HVAC OR AC UNIT ON A SERVICE CALL
26:38
D2D NY Real World HVAC Simplified
Рет қаралды 65 М.
intellipack P.M. and controls overview
22:21
Everything HVACR
Рет қаралды 10 М.
TRANE VOYAGER NOT COOLING
23:21
HVACR VIDEOS
Рет қаралды 120 М.
AC Pressures, Subcooling and Superheat
29:52
HVAC School
Рет қаралды 258 М.
This Dumbbell Is Impossible To Lift!
01:00
Stokes Twins
Рет қаралды 42 МЛН